S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL
69-1955
14
Fig. 5. S8610U connections in a heating system with power-assisted combustion.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ALTERNATE LIMIT CONTROLLER LOCATION.
MAXIMUM CABLE LENGTH 3 FT. [0.9 M].
CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.
LEAVE VENT DAMPER PLUG (P1) UNCONNECTED.
FOR SINGLE ROD APPLICATIONS: CONNECT JUMPER WIRE TO THE REMOTE SENSE
CONNECTOR.
FOR TWO ROD APPLICATIONS: REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS
POSSIBLE TO THE BASE OF THE MODULE, DISCARD CLIPPED WIRE, AND FIRMLY ATTACH
THE SENSOR WIRE FROM THE IGNITER/SENSOR ASSEMBLY TO THE REMOTE SENSE
CONNECTOR.
1
2
3
4
5
6
REMOTE
SENSE
JUMPER WIRE
CLIPPED CLOSE
TO BOARD
TWO ROD
SENSOR WIRE
FROM IGNITER/
SENSOR
6
THERMOSTAT
L1 (HOT)
L2
1
LIMIT
CONTROLLER
2
4
3
M23586
AIR
PROVING
SWITCH
COMBUSTION
AIR BLOWER
RELAY
L1
(HOT)
L2
1 COMBUSTION
AIR BLOWER
MOTOR
2ND
OPERATOR
1ST
OPERATOR
PILOT COM
MAIN
VALVE
DUAL VALVE COMBINATION
GAS CONTROL
GROUND
PILOT GAS SUPPLY
SPARK
ENVIRA
COM ™
S8610U
REMOTE
SENSE
MV
MV/
PV PV
GND
(BRN)
24V
GND 24V TH-W
P1
5
6
JUMPER
WIRE
PILOT BURNER/
IGNITER