background image

Mounting Remote indicator 

Summary  Remote Indicator models can be attached to a two-inch (50.8 millimeter) 
vertical or horizontal pipe using Honeywell’s optional pipe mounting bracket. Honeywell’s 
optional wall mounting bracket is also shown in figures below. 

Mounting Dimensions

 

Refer to Honeywell drawing number 51455045

*

 for detailed electronic housing 

dimensions.  Refer to Honeywell drawing numbers 32306827

*

 for detailed pipe mounting 

dimensions, 50124813

*

 for Detailed Pipe Angle mounting dimensions and 32306828

*

 for 

detailed wall mounting dimensions.

  

THE TRANSMITTER ENCLOSURE CAN BE ROTATED A TOTAL OF 90° FROM THE 
STANDARD MOUNTING POSITION 
* Honeywell drawings can be supplied on request.

 

 

Bracket Mounting  

If you are using an optional bracket, start with Step 1.  

1. 

Pipe Mount Option -Refer to Figure 2

Align the two mounting holes at the 

bottom of the Remote Indicator with the two slots in the mounting bracket 
and assemble the (2) M8 hex cap screws, (2) lock washers and (2) flat 
washers provided. 

 

 

2. 

Rotate the Remote Indicator assembly to the desired position and torque the 
M8 hex cap screws to 27,0 Nm/20,0 Lb-ft maximum  

3. 

Position the bracket on a 2-inch (50.8 mm) horizontal or vertical pipe, and 
install a 

“U” bolt around the pipe and through the holes in the bracket. 

Secure the bracket with (2) M10 hex nuts, (2) flat washers and (2) lock 
washers provided. Refer to Figure 4

.

 

 

Figure 2: Typical Pipe Mounted Installations 

 

 

 

Figure 3: Mounting Bracket Secured to a Remote indicator 

 

Figure 4: Pipe Mounting Bracket Secured to a Horizontal or Vertical Pipe

 

 

 

4.

 

Wall Mount Option 

– Refer Figure 5 Position the bracket on the mounting 

surface at the desired location and secure the bracket to the mounting 
surface using the appropriate hardware (Wall mounting hardware 
requirements to be determined and supplied by the end user).

 

 

Figure 5: Remote Indicator Secured to a Wall Mounting Bracket 

Wiring a Remote Indicator 

Overview 

 

The Remote Indicator is designed to operate in normal 4-20mA analog mode with HART 
enabled transmitters across SmartLine Devices. In DE mode, only STT250 and STT700 
Honeywell SmartLine transmitters. 
 
For improved noise performance, it is recommended to provide earth ground for both 
transmitter and RMA housing. 

 

Figure 6: DE/ANALOG Terminal Block   

 

 

 

Figure 7: RMA801 Terminal Block 

Terminal Block 

The RMA801 has 3 terminals. Following table provides the connection details- 

 
Three screw terminals suitable for wirings up to (16AWG) 
 

 

Shielded, twisted-pair cable such as Belden 9318 or equivalent must be used for 
all signal/power wiring. 
 

 

The cable shield must be connected at only one end of the cable. Connect it to 
the power supply side and 

leave the shield insulated at the transmitter side 

and RMA side. 

 

 
Loop Terminals 5 & 6 shall be connected in series with the 4-20 ma loop for both analog 
and DE modes. Additionally, third wire (Terminal 9) is required for DE communication in 
DE mode only. 
Loop wiring for analog and DE mode is shown in figure below.

 

 
NOTE: 
After wiring the Transmitter as outline in the next sections, torque the screws to 
1.1 Nm (10 lb-in)

 

 

Terminal No. 

Description 

Loop +ve 

Loop -ve 

DE COMM 

 

Summary of Contents for SmartLine RMA801

Page 1: ...perating in a 4 20 mA current loop The RMA801 is a DE Analog Remote Indicator which can be connected anywhere along the current loop For analog PV the RMA801 measures the loop current and displays the equivalent PV value on the display The RMA801 will autoconfigure when connected to Honeywell STT700 STT250 DE transmitters when a database upload is performed This document provides the information f...

Page 2: ...a Remote indicator Figure 4 Pipe Mounting Bracket Secured to a Horizontal or Vertical Pipe 4 Wall Mount Option Refer Figure 5 Position the bracket on the mounting surface at the desired location and secure the bracket to the mounting surface using the appropriate hardware Wall mounting hardware requirements to be determined and supplied by the end user Figure 5 Remote Indicator Secured to a Wall M...

Page 3: ...h ground Connect the Loop Power shield to earth ground at the power supply end and not at RMA end The shield shall be continuous from transmitter through RMA till the power supply DEVICE CONFIGURATION Once the loop is powered the RMA will be turned ON with a scrolling message SmartLine appearing on the display For DE devices the RMA is autoconfigured For any DE configuration change in the transmit...

Page 4: ...to 85o C Enclosure Type IP66 IP67 ALL ALL STANDARDS EN 60079 0 2012 A11 2013 EN 60079 1 2014 EN 60079 11 2012 EN 60079 31 2014 EN 60079 7 2015 D IECEx Flame proof Ex db IIC T6 T4 Gb Ex tb IIIC T 95o C Db Note 1 T6 50ºC to 65ºC T4 T5 50 ºC to 85ºC Intrinsically Safe Ex ia IIC T4 Ga Note 2 50o C to 70o C Non Incendive Ex ec IIC T4 Gc Note 1 50o C to 70o C Enclosure IP66 IP67 ALL ALL STANDARDS IEC 60...

Page 5: ...LOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 Intrinsically Safe Divisions 1 Zone 1 and Zone 2 Environments WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY WARNING DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT Explosion Proof Division 1 and Zone 1 Environments WARNING DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS ...

Page 6: ...44 0 1202645583 FAX 44 0 1344 655554 Email Sales sc cp apps salespa62 honeywell com or TAC hfs tac support honeywell com AMERICAS Honeywell Process Solutions Phone 1 800 423 9883 or 1 215 641 3610 TAC hfs tac support honeywell com Sales 1 800 343 0228 Email Sales FP Sales Apps honeywell com Knowledge Base search engine http bit ly 2N5Vldi WARRANTY REMEDY Honeywell warrants goods of its manufacture...

Reviews: