- 3 -  

 

 

 

LED INDICATORS 

The SiXCOMBO has a multi-color top LED:  

Green = Supervisory indication; blinks during power on, reset, 
and during normal operation 
Amber = Signal maintenance and trouble events 
Red = Alarm condition (either Smoke or CO) 

Side LED windows indicate alarms:  

red = smoke 
blue = CO 

 

CLEANING 

NOTE:

 Notify the proper authorities when the system will be 

temporarily out of service. 

IMPORTANT:

 This detector must be tested and maintained 

regularly following NFPA-72 requirements.  The detector should 
be cleaned at least once a year.

 

1.  Remove the detector from the base plate by turning 

counterclockwise. 

2.  Clean the outside casing with a cloth. Ensure that the holes 

on the front of the alarm are not blocked with dirt and dust. 
Canned air can be used to remove any dust or debris. 

3.  Reattach the detector to the base plate by rotating 

clockwise.  

4.  Test the detector to insure it is fully functional. (See Testing 

section). 

5.  Notify the proper authorities and Central Station when the 

system is back in service 

REPLACING THE BATTERIES 

5800combo QG-006

2

3

1

5

4

30

0

45

20

10

Panasonic CR123A
batteries only

~ 10
sec / seg

  

 

CAUTION:  

The batteries used in this device may present a fire 

or chemical burn hazard if mistreated.  Do not recharge, 
disassemble, heat above 100°C (212°F) or dispose of in fire.  
Use only Panasonic CR123A Lithium batteries. Use of other 
batteries may present a risk of fire or explosion. Keep used 
batteries away from children.  Dispose of used batteries 
properly. 

 

Remove old batteries.  Wait 10 seconds and then replace with 
four new batteries. To avoid a low battery indication when 
installing new batteries, all 4 batteries must be installed within 
15 seconds of installing the first one. Any low battery condition 
that may have occurred should clear when the base plate is 
installed.  

 

NOTE:

 Constant exposure to high or low temperature or high 

humidity may reduce battery life. 

 

LIMITED LIFE OF CO SENSOR

 

This detector is manufactured with a long-life electrochemical 
carbon monoxide sensor. Over time the sensor will lose 
sensitivity and will need to be replaced. The life span of the CO 
sensor is approximately ten years from the date of manufacture. 
Periodically check the detector’s replacement date. Remove the 
detector head and refer to the ‘replace by’ sticker placed on the 
underneath side of the detector. The sticker will indicate the 
date the detector should be replaced. 

Reminder:

 This detector is also equipped with a feature that will 

signal the panel once the CO sensor has passed the end of its’ 
useful life. If this occurs, it is time to replace the detector. 

What to do if the detector goes into CO alarm: 

If the detector goes into CO alarm (4 beeps), immediately 
move to a spot where fresh air is available, preferably 
outdoors, where the air is safe and call your security service 
provider.  Tell your provider the detector alarm status, and that 
you require professional assistance in ridding your home of the 
carbon monoxide.   

This detector is NOT: 

   A substitute for the proper servicing of fuel-burning 

appliances or the sweeping of chimneys. 

   To be used on an intermittent basis or as a portable alarm 

for the spillage of combustion products from fuel-burning 
appliances or chimneys. 

Carbon monoxide gas is a highly poisonous gas which is 
released when fuels are burnt. It is invisible, has no smell and 
is therefore is impossible to detect with the human senses. 
Under normal conditions in a room where fuel burning 
appliances are well maintained and correctly ventilated, the  

amount of carbon monoxide released into the room by 
appliances should not be dangerous. 

 

 

CAUTIONS

:  

  This device will only indicate the presence of carbon 

monoxide gas at the sensor. Carbon monoxide gas may be 
present in other areas. 

  This device is designed to protect individuals from the acute 

effects of carbon monoxide exposure. It will not fully 
safeguard individuals with specific medical conditions. If in 
doubt consult a medical practitioner. 

  Installation of the device should not be used as a substitute 

for proper installation, use, and maintenance of fuel-burning 
appliances, including appropriate ventilation and exhaust 
systems. 

 

MAINTENANCE 

Do not paint, and do not use cleaning agents, bleach or 
polish the detector. 

NOTE:

 Before performing any maintenance on the detector, notify the 

proper authorities and Central Station that maintenance is being 
performed and the system will be temporarily out of service. Disable 
the zone or system undergoing maintenance to prevent any unwanted 
alarms. Power must be removed from the detector before performing 
maintenance of any kind. 

 

The SiXCOMBO detector reports maintenance issues to the 
control panel and communicates them visually and audibly per 
Table 2. 

Trouble feature:

 When the sensor (supervision) is in a trouble 

condition (such as a detector that is dirty or CO sensor non-
functioning), the detector will send a trouble signal to the 
control panel. Depending on the issue, the detector must then 
be serviced or replaced. 

NOTE:

 Smoke detectors are not to be used with detector 

guards unless the combination is evaluated and found suitable 
for that purpose. 

 

SYMPTOMS OF CARBON MONOXIDE POISONING 

Carbon monoxide bonds to the hemoglobin in the blood and 
reduces the amount of oxygen being circulated in the body. 
The following symptoms are examples taken from NFPA 720; 
they represent approximate values for healthy adults. 

 

Concentration 

(ppm CO) 

Symptoms 

200 

Mild Headache after 2-3 hours of exposure 

400 

Headache and nausea after 1-2 hours of exposure 

800 

Headache, nausea, and dizziness after 45 minutes 
of expo- sure; collapse and unconsciousness after 2 
hours of exposure 

Many cases of reported carbon monoxide poisoning indicate 
that while victims are aware that they do not feel well, they 
become so disoriented that they are unable to save 
themselves by either exiting the building or calling for 
assistance. Also young children, elderly and pets may be the 
first to be affected. 

CO ALARM ACTIVATION 

Per UL standard 2075, the SiXCOMBO detector has been 
tested to the sensitivity limits defined in UL standard 2034. 

CO Alarm Thresholds 

Parts per Million (ppm) 

Detector Response Time (Min.) 

30+-3ppm 

No alarm within 30 days 

70+-5ppm 

60-240 

150+-5ppm 

10-50 

400+-10ppm 

4-15 

 

SPECIFICATIONS   

Electrical Specifications 

Voltage: ...................................................................... 3 volts DC 
Battery Type: ..................................................... CR123A lithium 
Battery Manufacturer: .......................... Panasonic CR123A only 
Number of Batteries: ................................................................ 4 
Sensitivity: .... UL limits .9 to 3.50%/ft / ULC limits .9 to 3.08 %/ft  
Thermal alarm: .................................................... 135° F (57° C) 
Freeze trouble: ............................................. 41° F typical (5° C)  
Audible Signal: ................................................................ 85dBA 

Physical Specifications 

Diameter: ................................. 6.3 in. Diameter x 1.65 in. Thick  
 ...................................................... (16.002 cm x 4.19 cm Thick) 
Weight: ............................................................... 14.3 oz (406 g) 
Operating Temperature Range: ........... 32° - 100° F (0° - 38° C) 
Storage Temperature Range: .............. 14 - 158° F (-10 - 70° C) 
Operating Humidity Range: ...................................... 20-95% RH

Summary of Contents for SiXCOMBO

Page 1: ...e announces successful enrollment If the LED does not light steady enrollment failed Retry by pressing either Test switch for less than 3 seconds All services Smoke Heat and CO are automatically enrolled in sequential or next available zone numbers with the following default attributes Zone Device Type Zone Response Type Smoke Det Smoke Detector Fire No Verification Heat Det Heat Sensor Fire No Ve...

Page 2: ... CO sensor inside the detector must be replaced If unresolved for 30 days the detector will chirp every 45 seconds The typical life of the CO sensor is ten years from the date of manufacture It is recommended to periodically check the Replace by date located on the label on the back of the detector head CO Test Button Smoke Test Button 5800 Combo ii 005 Follow instructions on the Can CO Gas Port T...

Page 3: ...fuels are burnt It is invisible has no smell and is therefore is impossible to detect with the human senses Under normal conditions in a room where fuel burning appliances are well maintained and correctly ventilated the amount of carbon monoxide released into the room by appliances should not be dangerous CAUTIONS This device will only indicate the presence of carbon monoxide gas at the sensor Ca...

Page 4: ...and 2 This device must accept any interference received including interference that may cause undesired operation SUPPORT WARRANTY For the latest documentation and online support information please go to https mywebtech honeywell com For the latest warranty information please go to www honeywell com security hsc resources wa For patent information please go to www honeywell com patents MyWebTech W...

Reviews: