background image

 

- 2 -  

 

 

TESTING 

Test communications between the detector and the control panel.  The 
detector mode has two test buttons; one for smoke testing and one for 
CO testing. 

 

The detector may also be functionally tested using canned smoke and 
canned CO.  If the detector fails any of the test methods, the detector 
should be replaced. 

NOTE:

 Testing the detector will activate the alarm and send a signal to the 

panel. 

Before testing, notify the proper authorities to avoid any 

false alarms.  

Smoke Test  (Alarm Test)

 

Press and hold the Smoke Test button for 1 to 2 seconds. The 
detector will sound and illuminate per Table 2 and send a smoke alarm 
signal to the control panel (all programmed smoke detector loops are 
signaled). Verify that the smoke alarm signal was received at the 
control panel.  

Smoke System Test (Functional Smoke Test) 

Press and hold the Smoke Test button for 3 to 5 seconds to enter the 
functional smoke test mode. 

See Functional Smoke Test section below.

 

Functional Smoke Test 

With the detector in smoke system (functional) test mode, spray 
canned smoke into the detector. The canned smoke that can be used 
and is approved for test include: Home Safeguard Industries 25S, SDi 
CHEK02 and CHEK06, SDi SOLOA4, and SDi SMOKESABRE. 

1. 

The detector will sound and illuminate per Table 2 and a smoke 
alarm signal will be sent to the panel.   

2. 

Verify the smoke alarm signal was received by the control panel. 

CO Test (Alarm Test) 

Press and hold the CO Test button for 1 to 2 seconds. The control 
panel should display and sound a CO alarm (all programmed CO 
detector loops are sent). 

CO System Test (Functional CO Test) 

Press and hold the CO Test button for 3-5 seconds to enter the 
functional gas test mode. 

See Functional Gas Test section below.  

 

Functional Gas Test 

Solo C6 brand canned CO may be used to verify the detector’s ability to 
sense CO by utilizing the RealTest® feature as follows: 
1.  Press and hold the CO test button for 3 to 5 seconds. The green 

LED will start blinking once per second indicating the detector is in 
RealTest® mode. (If the detector will not go into RealTest® mode, 
the CO sensor may be in fault or at end-of-life.) 

2.  While the green LED is blinking once per second, spray a small 

amount of canned CO directly into the CO gas entry port.  

3.  Upon successful gas entry and if functioning properly, the detector 

will go into CO alarm and send an alarm to the control panel. 

4.  The CO test will automatically clear when the CO clears from the 

sensor or in 30 seconds if no CO was introduced. 

 

HUSH FEATURE / ALARM SILENCE

 

If required, the audible alarm for smoke and CO conditions can be 
silenced for 5 minutes by pushing the “Test/Hush” button. In addition, 
low chirping can be silenced for 12 hours when the Test/Hush button is 
pressed.  
During a Smoke alarm, if an alarm condition still exists after the 5 
minute hush period, the alarm will sound.  The hush feature will not 
operate at levels above 4%/ft smoke concentration. 
During a CO alarm, if carbon monoxide is still present after the 5 minute 
hush period, the alarm will sound. The hush feature will not operate at 
levels above 350 ppm (parts per million) carbon monoxide. 

CO SENSOR END-OF-LIFE FEATURE 

When the CO sensor has passed end-of-life, a trouble signal will be 
sent to the control panel (if programmed). This indicates that the CO 
sensor inside the detector must be replaced. If unresolved for 30 days, 
the detector will chirp every 45 seconds. The typical life of the CO 
sensor is ten years from the date of manufacture. It is recommended to 
periodically check the “Replace by” date located on the label on the 
back of the detector head. 

 
 

 

 

CO Test Button

Smoke Test Button

5800 Combo ii -005

Follow

instructions

on the Can

CO Gas Port

Test

Buttons

HEAT

    ≥ 12” 
(30.48 cm)

SMO

K

E

*

So

lo

 C

6

    

    

C

O

1

2

3

4

(    )

 

30

0

45

5

~ 5 sec/seg

15

or

(    )

 

 

 

 

 

Table 3: Carbon Monoxide Detector: Events & 

Contact ID Codes

 

Event 

Alpha Keypad 

CS Report 

CO alarms 

CO Alarm 

CO alarm (CID 162) 

CO test 

CO Alarm 

CO alarm (CID 162) 

Low battery 

Lo Bat 

RF low-battery  
(CID 384) 

Detector 

supervision 

CO Trouble 

RF sensor supervision  
(CID 381) 

Detector end-

of-life/trouble 

CO Trouble 

Sensor trouble - end-

of life (CID 380) 

Tamper 

disarmed = CO Trouble  
armed = CO Alarm

 

RF sensor tamper  
(CID 383)

  

 

 
 

Table 2: LED Indication & Sounder during Test and Trouble 

MODE 

Status LED 

(Top) 

Side LED 
Windows 

Sounder 

Speaker 

Smoke Test 

Blink Green 

once every 

second 

Dark 

Temp-3 

Warning of 
alarm signal  
transmission.  
Voice smoke 
warning 

Smoke System 

(functional) Test 

Blink Red 

once every 10 

secs 

Blink once 

every  

10 secs 

 

 

RealTest™ 

Functional CO  gas 
entry test – 

Waiting 

for gas entry 

Blink Green 

once per 

second 

Dark 

Silent 

Voice 
instructions for 
testing; warning 
of alarm signal 

RealTest™ 

Functional CO  gas 

entry test  -

Upon 

successful gas 

entry

 

Blink Red 

once every  

10 secs 

Blink blue 

every  

10 secs 

Modified 

Temp-4 

Voice carbon 
monoxide 
warning 

Low Battery 

Blink Amber 

every 10 secs 

Dark 

Chirp 

every 45 

secs 

after 7 

days 

Voice instruc-
tions when 
chirp is 
silenced by 
pressing either 
test button 

Smoke 

Maintenance 

Blink Amber 
every 5 secs 

Dark 

Silent 

Voice smoke 
maintenance 
instructions if 
either test 
button is 
pressed 

CO Trouble 

Double Blink  

Amber  every 

5 secs 

Dark 

Silent 

 

CO End of Life – 

First 29 days

 

Double Blink 

Amber  every 

3 secs 

Dark 

Silent 

Voice end-of- 

life instructions 

when either test 

button is 

pressed

 

CO End of Life – 

after 30 days

 

Double Blink 

Amber every 3 

secs 

Dark 

Chirp 

every 45 

secs 

Voice end-of-life 

instructions when 

either test button 

is pressed

 

Power Up 

Blink Green, 
for 30 secs  

Dark 

Silent 

Language set 
instructions only 
on first time 
power-up  

Normal (Standby) 

Single Blink 
Green every 
10 secs 

Dark 

Silent 

Silent 

Freeze Warning 

(low temp) 

Blink Red 

every 10 secs 

 

 

 

 

TESTING SIGNAL STRENGTH

 

Perform this test in accordance with NFPA 72 inspection, testing and maintenance requirements to determine a strong communication 
path with the control panel.  
1.   Activate the wireless system’s GO/NO GO TEST mode. 
2.   Press the detector’s Smoke TEST button (•) for 1-2 seconds. The detector should immediately transmit an alarm signal to the control 

panel. The built-in horn will start to sound about 2.5 seconds after pressing the button.  

3.   The wireless system’s keypad should emit at least three beeps when the alarm transmission is received and display the transmitting 

detector’s zone number.  

4.   When the console has received the test signal, the horn will stop and a few seconds later the detector’s zone number will clear from 

the console display.  

5.   If the console does not respond as noted, and if this is an initial installation, try moving the detector to another location that provides 

proper reception. Also be sure that the detector has been “enrolled” by the control panel (see Enrollment section). Then, repeat the 
test. 

6.   Turn off the system’s TEST mode (typically security code + OFF).
 

 

Summary of Contents for SiXCOMBO

Page 1: ...e announces successful enrollment If the LED does not light steady enrollment failed Retry by pressing either Test switch for less than 3 seconds All services Smoke Heat and CO are automatically enrolled in sequential or next available zone numbers with the following default attributes Zone Device Type Zone Response Type Smoke Det Smoke Detector Fire No Verification Heat Det Heat Sensor Fire No Ve...

Page 2: ... CO sensor inside the detector must be replaced If unresolved for 30 days the detector will chirp every 45 seconds The typical life of the CO sensor is ten years from the date of manufacture It is recommended to periodically check the Replace by date located on the label on the back of the detector head CO Test Button Smoke Test Button 5800 Combo ii 005 Follow instructions on the Can CO Gas Port T...

Page 3: ...fuels are burnt It is invisible has no smell and is therefore is impossible to detect with the human senses Under normal conditions in a room where fuel burning appliances are well maintained and correctly ventilated the amount of carbon monoxide released into the room by appliances should not be dangerous CAUTIONS This device will only indicate the presence of carbon monoxide gas at the sensor Ca...

Page 4: ...and 2 This device must accept any interference received including interference that may cause undesired operation SUPPORT WARRANTY For the latest documentation and online support information please go to https mywebtech honeywell com For the latest warranty information please go to www honeywell com security hsc resources wa For patent information please go to www honeywell com patents MyWebTech W...

Reviews: