Programming
151450
6-7
6.6
Panel Programming Options
All customized programming options for the 5600 control panel are described in this section
and are available to be edited using the embedded web server of the control panel.
6.6.1
System Options
6.6.1.1 Synchronized Strobes Active When Horns Silenced
The default configuration for this option is No. If set to Yes, strobes will remain on when
horns are silenced until a panel reset is issued.
6.6.1.2 Silence/Reset Inhibit Enabled
The default configuration for this option is NO. If set to Yes, Pressing either Reset or Silence
Buttons will be ignored for the duration of the delay (set to 30 seconds). The inhibit feature
delay is only active for the first alarm/supervisory signal.
6.6.1.3 Water Flow Delay
The water flow delay is a debounce time that is generally used to help reduce false alarms
during brief periods of water pressure fluctuation in a water riser. The default setting is 1
second which is the minimum debounce time. You can set the water flow delay within the
range 1-90 seconds.
6.6.1.4 Installer Code (User ID)
This is the password used to lock the list of SLC devices found during the JumpStart auto
learn process. It is defaulted to 123456 and can be changed to any 4 to 8 digit number.
6.6.1.5 Alarm Verification Time
Alarm verification is an optional false alarm prevention feature for smoke detectors that
verifies an alarm condition by resetting the smoke detector. The alarm verification time can be
set within the range of 1-250 seconds. For UL 864 installations this option must be greater
than 59 seconds. The default setting is 60 seconds.
6.6.1.6 Auto Test
Enter the hour/minutes (in 24 hour format) that you desire the control panel to send the
automatic test report.
6.6.1.7 Low AC Report Delay
This option determines the number of delay hours before a loss of AC is reported to the
central station. It is defaulted to 3 hours and must be within the range 0-30 hours. For U.L.
864 installation this option must be set within the range 1-3 hours.
Summary of Contents for Silent Knight INTELLIKNIGHT 5600
Page 2: ......
Page 10: ...Model 5600 Installation Manual 6 151450 ...
Page 16: ...Model 5600 Installation and Operation Manual 1 6 151450 ...
Page 54: ...Model 5600 Installation and Operation Manual 4 24 151450 ...
Page 82: ...Model 5600 Installation and Operation Manual 7 10 151450 ...
Page 86: ...Model 5600 Installation and Operation Manual 8 4 151450 ...
Page 102: ...Model 5600 Installation and Operation Manual 12 151450 ...
Page 106: ......
Page 108: ......
Page 109: ......