Control Panel Installation
151450
4-15
4.7
Configuring Module
This section describes how to configure the 5635 Annunciator that has been added to the
system. Each SBUS device requires a unique address. 5635 Series DIP switch S21 is used to
set the address. This address will be displayed on the LCD display as the Station ID number.
4.7.1
Assigning Module IDs
When installing the 5635 you must use the DIP switches on the module to assign an ID# to the
module. A maximum of 2 devices can be connected to the FACP SBUS communication
circuit. The SBUS device address needs to be set to 01or 02.
Note: Note that 00 is not a valid address.
Figure 4-13 shows the DIP switch positions and their correlation to a numerical ID.
Figure 4-13 DIP switch settings
ID Number
(Address)
(not valid) 00
01
02
DIP Switch