9
8
7
6
5
4
3
2
1
0
0
1
2
34
56789
TENS
ONES
ADDRESS
LOOP
0
78
6
5
4
32
1
9
FROM PANEL OR
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
MONITOR
CONNECT MODULES TO LISTED COMPATIBLE
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
SILENT KNIGHT CONTROL PANELS ONLY
PREVIOUS DEVICE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
COMMUNICATION LOSS (OPTIONAL CONNECTION FOR
PANELS WHICH SUPPORT THIS FEATURE)
47 K EOL
RESISTOR
ELR-47K
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 230A MAX @ 12 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
MODULE
14K SERIES RESISTOR
SIGNAL LINE CIRCUIT (SLC)
9
8
7
6
5
4
3
2
1
0
0
1
2
34
56789
TENS
ONES
ADDRESS
LOOP
0
78
6
5
43
21
9
MODULE
FROM PANEL OR
(+)
(-)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
MONITOR
CONNECT MODULES TO LISTED COMPATIBLE
SILENT KNIGHT CONTROL PANELS ONLY
PREVIOUS DEVICE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9.
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
32 VDC MAX
SHIELDED-TWISTED PAIR
IS RECOMMENDED
COMMUNICATION LOSS (OPTIONAL CONNECTION
FOR PANELS WHICH SUPPORT THIS FEATURE)
SIGNAL LINE CIRCUIT (SLC)
9
8
7
6
5
4
3
2
1
0
0
1
2
3
4
5 6
7 8 9
TENS
ONES
ADDRESS
LOOP
0
7 8
6
5
4
3
2
1
9
(+)
(–)
(+)
(–)
(+)
(–)
MONITOR
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
COMMUNICATION LOSS (OPTIONAL CONNECTION FOR
PANELS WHICH SUPPORT THIS FEATURE)
47 K EOL
RESISTOR
ELR-47K
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 230A MAX @ 12 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
MODULE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
SILENT KNIGHT CONTROL PANELS ONLY
TO NEXT
DEVICE
C0805-01
C0804-01
C0806-01
Figure 5. Typical 2-wire initiating circuit configuration for security systems (with alarm versus short capability):
NOTE:
For UL Listed security installations, the IDP-Monitor must be mounted within the control panel enclosure.
Figure 4. Typical 4-wire fault tolerant initiating circuit configuration, NFPA Style D:
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:
K200-08-00
2
I56-2724-002
7550 Meridian Circle
Maple Grove, MN 55369-4927
763-493-6455; 800-328-0103
Fax: 763-493-6475
http://www.silentknight.com
© 2006 Silent Knight
8/05