Honeywell Silent Knight IDP-Monitor Installation And Maintenance Instructions Download Page 1

C0218-01

C0156-00

C0157-00

Figure 1. Controls and Indicators:

Specifications

Normal Operating Voltage:  15 to 32 VDC
Maximum Current Draw: 

5.0 mA (LED on)

Average Operating Current:  375µA (LED flashing)
EOL Resistance: 

47K Ohms

Maximum IDC 
wiring resistance: 

1,500 Ohms

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10% to 93% Non-condensing

Dimensions: 

4

1

2

˝ H x 4˝ W x 1

1

4

˝ D  

 

(Mounts to a 4˝ square by  

 

2

1

8

˝ deep box.)

Accessories: 

SMB500 Electrical Box

Figure 2B: 

Figure 2A. Module mounting:

NOTE:

 For UL Listed security installations, the IDP-Monitor 

must be mounted within the control panel enclosure.

Before Installing

This information is included as a quick reference installa-
tion guide. Refer to the control panel installation manual 
for detailed system information. If the modules will be 
installed in an existing operational system, inform the 
operator and local authority that the system will be tem-
porarily out of service. Disconnect power to the control 
panel before installing the modules.

NOTICE: 

This manual should be left with the owner/

user of this equipment.

General Description

The IDP-Monitor Module is intended for use in intel-
ligent, two-wire systems, where the individual address of 
each module is selected using the built-in rotary switches. 
It provides either a Class A or Class B fault tolerant initi-
ating device circuit (IDC) for normally open contact fire 
alarm and supervisory devices, or either normally open or 
normally closed security devices. The module has a panel 
controlled LED indicator.

Compatibility Requirements

To ensure proper operation, this module shall be con-
nected to a compatible Silent Knight system control panel 
(list available from Silent Knight).

INSTALLATION AND MAINTENANCE 

INSTRUCTIONS

K200-08-00 

 

I56-2724-002

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

1

2

3

4

8

7

6

5

9

ON

ES

AD

DR

ES

S

TE

NS

1 0

2

3

4

5

6

7

8 9

1 0

2

3

4

5

6

7

8 9

9
8
7
6
5

4

3

2

1

0

0

1

2

3

4

5 6

7 8 9

TENS

ONES

ADDRESS

LOOP

10

7 8

6

5

4

3

2

9

IDP-Monitor Module

Mounting

The IDP-Monitor mounts directly to 4˝ square electri-
cal boxes (see Figure 2A). The box must have a mini-
mum depth of 2

1

8

˝.  Surface mounted electrical boxes 

(SMB500) are available from Silent Knight.

Wiring

NOTE: 

All wiring must conform to applicable local 

codes, ordinances, and regulations. This module is in-
tended for power limited wiring only.
1.  Install module wiring in accordance with the job draw-

ings and appropriate wiring diagrams.

2.  Set the address on the module per job drawings.
3.  Secure module to electrical box (supplied by installer), 

as shown in Figure 2A.