background image

3

4

8

9

10

5

6

7

2. SAFETY

3. MECHANICAL ASSEMBLY

Ensure that you read and understand these instructions 

BEFORE

 

handling or operating the equipment. Please pay particular attention to 

the Safety Warnings.

WARNINGS

  1.   The Searchline Excel gas detector is certified for and intended for use in potentially 

   

hazardous areas. Install and use the Searchline Excel gas detector in accordance with  

   

the latest regulations.

 2.

 

For installations in the UK, the Code of Practice SELECTION, INSTALLATION AND 

   

MAINTENANCE OF ELECTRICAL APPARATUS FOR USE IN POTENTIALLY  

   

EXPLOSIVE ATMOSPHERES should be strictly observed. General recommendations are 

   

given in BS EN 60079-14 & IEC 60079-14. Refer to BS EN 60079-29-2  

   

& IEC 60079-29-2 in the UK or the appropriate local or national regulations.

  3.  For installations in North America, the national Electrical Code (NFPA 70) or later 

   

issues should be strictly observed.

  4.  Elsewhere, the appropriate local or national regulations should be used.
  5.  The Searchline Excel gas detector must be properly earthed to protect against electrical 

   

shock and minimise electrical interference. For electrical installation design  

   

considerations refer to Section 3.

  6.  Operators must be fully aware of the action to be taken if the gas concentration exceeds 

   

an alarm level.

  7.  Dismantling or repair of equipment should be carried out in the safe area only.
  8.  Test gases may be toxic and/or combustible. Refer to Material Safety Sheets for 

   

appropriate warnings.

  9.  Do not drill holes in any housing as this will invalidate the explosion protection.
  10. In order to maintain electrical safety, the unit must not be operated in atmospheres with 

    

more than 21% oxygen.

  11.  Ensure that the bolts which secure flameproof enclosures are fully tightened. The  

   

securing bolts used are made from a special certified grade of steel. Only bolts supplied 

   

by Honeywell Analytics should be fitted for this purpose.

  12. Do not open the enclosure in the presence of an explosive atmosphere.
  13. The transmitter unit contains high voltages when operational. These are discharged when 

   

the unit is removed from its enclosure.

  14. The conduit and cable glands fitted to Searchline Excel should not be modified. If, 

   

however, it becomes necessary to make modifications they must comply with the  

   

relevant national Codes of Practice.

  15. The irradiance and power emitted by the Searchline Excel transmitters is less than  

   

5 mW/mm

2

 and 15 mW/mm

2

 respectively.

 

Honeywell Analytics Limited reserve the right to change or revise the 

information supplied in this document without notice and without 

obligation to notify any person or organisation of such revision or 

change. If further details are required that do not appear in this 

document, contact Honeywell Analytics Limited or one of their agents.

4. INSTALLATION

INSTALLATION

4.1 GENERAL

Searchline Excel is designed to allow installation to be performed by a 

single operator.
The installation procedure is split into mechanical installation and 

electrical installation. Each unit needs to mounted to a supporting 

structure before making the electrical connections. The diagrams show 

different ways of orientation for the mountings.

4.2 MECHANICAL INSTALLATION

This mechanical installation procedure applies to both the receiver and 

the transmitter.

1.  Ensure that the equipment to be 

installed is correct for the type 

of installation required (i.e. short/

medium/long range).

2.  Fit the mounting bracket to the 

mounting plate for the unit, as 

shown.

3.  Fit the mounting plate to the 

supporting structure in one of the 

following ways:

 

•  by through bolts directly to a flat surface.

 

•  by U-bolts (2 off)  to a single 150mm diameter pipe/pole.

 

•  by U-bolts (4 off)  to two 55mm diameter pipes/poles,  

166mm apart.

Identify the mounting holes using the following diagram and the 

accompanying table. The subsequent diagrams show the different 

types of mountings.

3.1 GENERAL

This section details the mechanical assembly information and important 
dimensions necessary for installing the system units. Adjustable parts which form 
part of the mounting assemblies are also shown.

 

NOTE: FOR DNV VERSIONS, REFER TO THE SEARCHLINE EXCEL TECHNICAL 

HANDBOOK FOR SPECIAL INSTRUCTIONS ON THE INSTALLATION, ALIGNMENT AND 

COMMISSIONING USING THE MARITIME BRACKET AND HARDWARE

 

 

3.2 TRANSMITTER

MECHANICAL ASSEMBLY

INSTALLATION

7.  Fit an adjustment clamp to the unit’s pivot block mounting stud 

so that it sits on the stud’s shoulder with the correct orientation as 

shown in the diagram.

INSTALLATION

INSTALLATION

4.3 ELECTRICAL INSTALLATION

4.3.1 

Electrical Connections

All ranges of Searchline Excel comply with the EMC requirements 

EN50270. In order to maintain compliance with these standards it is 

essential that the electrical installation of Excel is engineered correctly.

Electrical installation standards vary for different countries, companies 

and applications and it is the responsibility of the installation design 

authority to determine the applicable standards and ensure compliance 

with them. When designing electrical installations for Excel,  

Honeywell Analytics Limited recommend that the installation design 

authority considers the following:

a.  The unit cases should not, if possible, be connected to electrically 

 

noisy (dirty) metalwork or conductors. Preferably, the case 

   (internally connected to the green/yellow GND wire) should be 

   connected to a low noise instrument (clean) earth.  See also para e. 

 

below.  In order to facilitate electrical isolation of the Searchline 

 

Excel from a noisy earth an isolation kit is supplied. This kit should 

 

be fitted as standard unless local regulations forbid this.

b.  The entire length of the field cabling connected to each unit should

 

 

be fully shielded. This should be connected to a low noise (clean) 

 earth.
c.  The low noise instrument (clean) earth system should only be 

 

connected to safety earth (usually dirty) at a single point on the 

 

entire site/installation. This connection should be made in such a 

 

manner that it does not introduce noise onto the low noise 

 

instrument earth. Star earthing arrangements minimise earth current 

 crosstalk.

d.  The shields of the field cabling should not be connected such that

 

 

earth loops are produced, or in a manner that will result in the    

 

shields carrying large currents from heavy plant or equipment.

e.  Ideally, the field cable shield should be connected to the unit’s

 

 

green/yellow GND wire, providing a single, continuous earth shield. 

   This connection must not be allowed to complete an earth loop.

160mm (SR) 

211mm  

(MR/LR)

291 (SR) 353 (MR/LR)

Approximately 300mm

417 (SR) 

433 (MR/LR)

160mm

291mm

Approximately 300mm

3.3 RECEIVER

417mm

3.4 ADJUSTABLE MOUNTINGS

Adjustment Clamp 

lock screw (2 off)

Mounting Bracket 

adjusting screws (2 off)

Clamp Nut

Adjustment Clamp
lock screw  (2 off)

Pivot Block 

adjusting screw  (2 off)

Clamp Nut

Notes: 1. 

Drawing is 

not to scale. 

 

2.  Mounting plate fixing holes are clear. Searchline Excel system 

component mounting holes are threaded.

 

3.  The mounting plate fixings are not supplied.

4.  Fit an adjustment clamp to the unit’s pivot block mounting stud 

so that it sits on the stud’s shoulder with the correct orientation as 

shown in the diagram.

5.  Tighten the adjustment clamp’s 

grubscrews until they just grip the 

unthreaded part of the mounting stud.

6.  Fit the pivot block to the mounting bracket 

using a clamp nut and spring washer (M12 

or M16) with the correct orientation as 

shown in the diagram. Do not fully tighten 

the nut.

 

Ensure that the adjustment clamp’s 

stub lever is positioned approximately 

centrally between the mounting bracket’s 

grubscrews. Adjust the screws if required.

Pivot

Block

Mounting Stud

Adjustment

Clamp

Mounting

Bracket

Clamp Nut 

and Spring 

Washer

Mounting 

Bracket 

Grubscrew

Mounting 

Stud

Adjustment 

Clamp

Stub Lever

8.  Tighten the adjustment clamp’s 

grubscrews until they just grip 

the unthreaded part of the unit’s 

mounting stud.

9.  Fit the unit to the pivot block using 

a self-locking clamp nut and washer 

(M12 or M16).  

 

Do not fully tighten the nut.

 

Ensure that the adjustment clamp’s 

stub lever is approximately centrally 

positioned between the pivot block’s 

grub screws.  Adjust the screws if 

required.

10. Fit a suitable junction box, e.g. OELD, 

DX100(M) or other suitable type of 

junction box, to the mounting plate

Note:  For information about alternative 

types of junction box see Section 

4.3 Electrical Installation.

11. Measure the distance (in metres) 

between the transmitter and receiver 

units. 

 

This distance is required by the 

system commissioning personnel.

Surface Mounting

Single Pipe/Pole

Dual Pipes/Poles

Identity

Quan-
tity

Size

Used For

A

8

ø7.5mm

Dual 2’’ pipe or pole mounting, flat 

 

surface mounting

B

8

ø9.5mm

Single 6’’ pole, flat surface mounting, 

Dual 2.5’’ ID pipe

C

4

M6 tapped

00780-A-0100 junction box mounting

D

3

M6 tapped

DVC100(M) junction box mounting.

D1

2

M6 tapped

DVC100(M) MK2 junction box (used in 
conjunction with bottom two D holes)

E

4

M10 tapped

DX100(M) junction box mounting

F

2

M6 tapped

Killark/Akron junction box mounting

G

4

M6 tapped

Sun/heat shade mounting

H

3

M8 tapped

Short range Transmitter and all Receiver 
brackets.

J

3

M10 tapped

Medium/Long range Transmitter  
mounting bracket.

K

2

M10 tapped

 XNX Universal Transmitter

Always mount 
plate this  
way up

60x45° 2 POSNS

6mm thick  
stainless steel  
plate

A

D1

D

D1

D

E

C

C

F

F

D

G

G

G

G

C

C

E

E

E

K

K

J

J

J

H

H

H

A

B

B

B

B

B

B

B

B

A

A

A

A

A

A

224

15

15

49
83

133.2

181
215
249

299.2

380

209

Mounting 

Bracket

Mounting Plate

Isolation 

Kit

NOTE: FOR DNV VERSIONS, REFER TO THE SEARCHLINE 

EXCEL TECHNICAL HANDBOOK FOR SPECIAL 

INSTRUCTIONS ON THE INSTALLATION, ALIGNMENT 

AND COMMISSIONING USING THE MARITIME BRACKET 

AND HARDWARE

Reviews: