Honeywell S8910U Installation Instructions And Safety Information Download Page 2

69-0845—2

2

S8910U UNIVERSAL HOT SURFACE IGNITION MODULE

S8910U

Model   

Numbers

Selection

Tab

Remove   

Black

Jumper

Local (L) or

Remote (R)

Sensing   

Lockout

Time
(sec)

Ignition

Trials

PrePurge

(sec)

Igniter

Warmup

(sec)

Between

Trial Purge

(sec)

S8910U

A

Local or

4

1

32

34

NA

Specifications

B

Remote

3

96

C

7

1

NA

D

3

96

50E47-1 thru 9

A

Yes

R

4

1

0

17

NA

50E47-10 thru 19

A

Yes

R

4

1

0

45

NA

50E47-20 thru 29

A

Yes

R

4

1

30

17

NA

50E47-30 thru 39

A

Yes

R

4

1

30

45

NA

50E47-40 thru 49

B

Yes

R

4

3

30

17

90

50E47-50 thru 59

B

Yes

R

4

3

30

45

90

50E47-60 thru 69

B

Yes

R

4

3

0

17

60

50E47-70 thru 79

B

Yes

R

4

3

0

45

60

50E47-101 thru 109

C

Yes

R

7

1

0

17

NA

50E47-110 thru 119

C

Yes

R

7

1

0

45

NA

50E47-120 thru 129

C

Yes

R

7

1

30

17

NA

50E47-130 thru 139

C

Yes

R

7

1

30

45

NA

50E47-140 thru 149

D

Yes

R

7

3

30

17

90

50E47-150 thru 159

D

Yes

R

7

3

30

45

90

50E47-160 thru 169

D

Yes

R

7

3

0

17

60

50E47-170 thru 179

D

Yes

R

7

3

0

45

60

50E47-201 thru 209

A

Yes

R

4

1

0

17

NA

50E47-210 thru 219

A

Yes

R

4

1

0

45

NA

50E47-220 thru 229

A

Yes

R

4

1

30

17

NA

50E47-230 thru 239

A

Yes

R

4

1

30

45

NA

50E47-240 thru 249

B

Yes

R

4

3

30

17

90

50E47-250 thru 259

B

Yes

R

4

3

30

45

90

50E47-260 thru 269

B

Yes

R

4

3

0

17

60

Sensor:

A separate sensor is required for remote sensing applica-
tions.

Wiring:

Use the existing appliance wiring. If repair or replacement
of leadwires is required, follow the instructions on the
appliance label. Use the included quick-connect terminals
according to the instructions.

Prepurge:

32 seconds.

Igniter Warmup:

34 seconds.

Between Trial Purge:

96 seconds (three trial mode only).

Flame Failure Response Time:

1.5 seconds maximum.

Ignition Sequence:

The number of trials for ignition and trial time are deter-
mined by the selection tab. See Table 1. If a selection tab
is not installed, the module will operate at four seconds
trial time and one ignition trial.

Ambient Operating Temperature:

-40

°

F to +175

°

F (-40

°

C to +79

°

C).

Accessory Bag Assembly:

White-Rodgers adapter.

Robertshaw ground lead.

Four 1/4 in. female .032 quick-connects.

One 3/16 in. female .032 quick-connect.

Four selection tabs.

Seven wire labels.

Approval Bodies:

IAS Design Certified: Certification Report No. C2027002.

Table 1. White-Rodgers Control to Honeywell S8910U Cross Reference.

NOTES:

This list is for reference only. Honeywell reserves the right to add or delete models at any time, based on new or
updated information.

White-Rodgers product information was obtained from the 1991 White-Rodgers Product Catalog (R3700).

continued

Summary of Contents for S8910U

Page 1: ...and seven wire labels The wiring labels are included to assure proper marking of the wires attached to the existing module A complete list of the specific Honeywell and other modules that the SUPER TRADELINE S8910U is designed to replace is provided in Tables 1 through 3 NOTE The S8910U is intended to replace only defective ignition controls The service technician should make sure that the other p...

Page 2: ...59 B Yes R 4 3 30 45 90 50E47 260 thru 269 B Yes R 4 3 0 17 60 Sensor A separate sensor is required for remote sensing applica tions Wiring Use the existing appliance wiring If repair or replacement of leadwires is required follow the instructions on the appliance label Use the included quick connect terminals according to the instructions Prepurge 32 seconds Igniter Warmup 34 seconds Between Tria...

Page 3: ...hru 119 C Yes R 7 1 0 45 NA 50F47 120 thru 129 C Yes R 7 1 17 17 NA 50F47 130 thru 139 C Yes R 7 1 17 45 NA 50F47 140 thru 149 D Yes R 7 3 17 17 77 50F47 150 thru 159 D Yes R 7 3 17 45 77 50F47 160 thru 169 D Yes R 7 3 0 17 60 50F47 170 thru 179 D Yes R 7 3 0 45 60 50F47 201 thru 209 A Yes R 4 1 0 17 NA 50F47 210 thru 219 A Yes R 4 1 0 45 NA 50F47 220 thru 229 A Yes R 4 1 17 17 NA 50F47 230 thru 2...

Page 4: ... No L 4 3 0 34 34 HS780 34NL 306A D No L 6a 3 0 34 34 HS780 34NL 308A D No L 8a 3 0 34 34 HS780 34NL 312A D No L 12b 3 0 34 34 HS780 34NR 104A A Yes R 4 1 0 34 NA HS780 34NR 306A D Yes R 6a 3 0 34 34 HS780 34NR 308A D Yes R 8a 3 0 34 34 HS780 34NR 312A D Yes R 12b 3 0 34 34 HS780 34PL 308A D No L 8a 3 34 34 34 Table 2 Robertshaw Control to Honeywell S8910U Cross Reference NOTE Robertshaw product i...

Page 5: ...under a variety of input conditions to assure reliable operation REVIEW THE INSTALLATION WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Follow these warnings exactly 1 Review the installation as outlined in this section 2 Plan for frequent maintenance as described in the Maintenance section When hot surface ignition systems are used on central heating equipment i...

Page 6: ...onent and appliance operation as provided in these instructions WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH 1 If the ignition module gets wet it can malfunc tion leading to accumulation of explosive gas Never install where water can flood drip or condense on the module Never use a module that has been wet Replace it 2 Liquefied petroleum LP gas is heavier than...

Page 7: ...check out the S8910U and selection tabs Use only the selection tab specified in Tables 1 through 3 for the existing module being replaced Always remove all unused selection tabs from the job site and discard them at a remote location Improper use of the selection tabs can result in appliance malfunction Fig 2 Separating and installing selection tab Wire the Module CAUTION 1 Check the wiring diagra...

Page 8: ...s ground c Do not use the S8910U VALVE GND terminal VALVE GND and 24V GND are interconnected in the appliance wiring d Remove quick connect and replace with the included 3 16 in quick connect e Do not use this terminal if model being replaced does not have 120V neutral power supply connection f Use the black wire on the included adapter cable g Use the orange wire on the included adapter cable h O...

Page 9: ...UICK CONNECT SUPPLIED BURNER GROUND M8528B AUTO IGNITION SYSTEMS ANSI Z21 20 STATUS LED 1 Flash Ignition Lockout 2 Flash Weak Flame Signal 3 Flash Internal Error Replace Control Pulsing Heartbeat Normal Operation S8910U HOT SURFACE IGNITION INPUT VOLTAGES 120 24 VAC 60HZ HSI 120V 6 5A MAX VALVE 24V 1A MAX TOTAL 24V LOAD 0 2 VALVE LOAD 120VAC HOT 570A0056 WARNING Explosion hazard Can cause serious ...

Page 10: ... GROUND ADAPTER SUPPLIED TO CONNECT S8910U GND BURNER TO APPLIANCE CHASSIS BURNER GROUND M8529B AUTO IGNITION SYSTEMS ANSI Z21 20 STATUS LED 1 Flash Ignition Lockout 2 Flash Weak Flame Signal 3 Flash Internal Error Replace Control Pulsing Heartbeat Normal Operation S8910U HOT SURFACE IGNITION INPUT VOLTAGES 120 24 VAC 60HZ HSI 120V 6 5A MAX VALVE 24V 1A MAX TOTAL 24V LOAD 0 2 VALVE LOAD 120VAC HOT...

Page 11: ...HSI HSI SENSE STARTUPAND CHECKOUT Check out the gas control system At initial installation of the appliance As part of regular maintenance procedures At maintenance intervals determined by the application As the first step in troubleshooting Any time work is done on the system Maintenance frequency must be determined individually for each application see Maintenance section WARNING FIRE OR EXPLOSI...

Page 12: ...water solution Bubbles indicate a gas leak Tighten the joints and screws or replace component to stop a gas leak Recheck with soap and water solution e Check the burner flame condition The igniter sensor or sensor must be constantly immersed in flame Check the burner flame condition as shown in Fig 6 Do not relocate the hot surface igniter or flame rod f Turn the thermostat or controller below the...

Page 13: ...e gas control is closed Fig 7 S8910U normal operating sequence START PREPURGE IGNITER WARMUP CALL FOR HEAT 24V TERMINAL POWERED INTERNAL SAFE START CHECK BEGINS FLAME SIMULATING FAILURE SYSTEM WILL NOT START PREPURGE IGNITER WARMS UP BETWEEN TRIAL PURGE TRIAL FOR IGNITION GAS CONTROL OPENS FOR TIMED TRIAL FOR IGNITION LOCKOUT OCCURS SYSTEM MUST BE RESET GAS CONTROL CLOSES NO FLAME IGNITER OFF FLAM...

Page 14: ... initiates a between trial purge warmup and trial for ignition After the third trial during a single call for heat the module locks out The module must be manually reset following the lockout MAINTENANCE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not attempt to take apart the module or to clean it Improper assembly and cleaning can cause unreliable operati...

Page 15: ...nections to the ignition module and to the igniter or igniter sensor are clean and tight c Ignition cable provides good electrical continuity Step 2 Check the ignition system grounding Nuisance shutdowns are often caused by a poor or erratic ground a A common ground is required for the module igniter flame sensor and main burner Check for good metal to metal contact between the igniter bracket and...

Page 16: ...CE S8910U MODULE NOTE SYSTEM FAILURE DURING A RUN CYCLE HAS A LOW PROBABILITY OF BEING THE S8910U MAIN BURNER REMAINS POWERED AND LIT MAIN BURNER LIGHTS CHECK FOR 120 VAC ACROSS HOT SURFACE IGNITER TERMINALS NOTE IF S8910U GOES INTO LOCKOUT RESET SYSTEM CHECK CONTINUITY OF GROUND WIRE AND GROUND PATH FROM MAIN BURNER TO GND BURNER TERMINAL OF S8910U CONFIRM THAT 120 VAC HOT LEAD IS CONNECTED TO L1...

Reviews: