Honeywell S8700 Series Installation Instructions Manual Download Page 5

S8700B,D-F,J-M DIRECT SPARK IGNITION CONTROLS

5

69-1299

Resetting S8700 After Safety Lockout

After completing the normal ignition sequence, without 
proving main flame, the S8700 models will shut off the 
spark and gas flow and go into lockout. S8700B,D,J,K 
will stay in lockout until the call for heat is removed and 
restored. S8700E,F,L,M will stay in lockout for 60 min-
utes, then another ignition sequence will start. If the call 
for heat is interrupted then restored, all S8700 models 
will start a new ignition sequence.

To reset the system at any time:

Adjust the temperature control setting to below the room 
temperature, wait five seconds, and move the tempera-
ture control setting up to call for heat or remove 24V 
power and reapply. Normal ignition should occur as 
described in the Start System section.

CHECKOUT

Start the system and observe operation through at least 
two complete cycles to make certain all controls and the 
appliance are operating safely.

Sequence of Operation

The S8700 control performs the following basic 
functions:

— Supplies power to the electronic pulse-generator 

circuit for the spark igniter. Allows up to the specified 
trial for ignition and one or three trials before system 
safety lockout occurs (see Table 1 and Table 3).

— Senses the burner flame(s) for safe lighting.
— Shuts off spark after burner is lit.
The S8700 is powered by a 24V transformer and is 
activated when the temperature control calls for heat. 
See Fig. 4 or 5, depending on model.

Operation is as follows:

When the S8700 is activated by the call for heat from 
the temperature control, the S8700 performs a safe-
start check that determines proper operation of the 
control before beginning the normal sequence of opera-
tion. This check also determines if a flame signal is 
being sensed. If flame is sensed or the control identifies 
any internal failure, the S8700 will go to lockout (LED 
steady on). Once the safe start check operation passes, 
the S8700 turns on the spark circuit and at the same 
time energizes the gas control main valves and allows 
gas to flow to the main burner.

Sparking continues until the trial for ignition ends, 
unless the main burner lights and is sensed as sufficient 
to shut off the spark and allow normal operation.

If the main burner lights, a flame sensing circuit is com-
pleted through the flame to the burner head and back to 
the S8700 GND (Burner) terminal. This current flow sets 
the trial for ignition timer to the reset (normal) condition 
and interrupts the spark ignition circuit. Should the 
current flow be interrupted, i.e., flame out condition, the 
spark will be re-initiated immediately and a normal trial 
for ignition will occur. If the main burner lights and 
proves, a normal run will occur. If the main burner does 
not light and prove, the S8700 goes into lockout.

The S8700 keeps the gas control main valve open as 
long as there is a call for heat and sufficient  flame 
current through the flame sensing circuit. If, however, 
the trial for ignition period ends before the main burner 
lights or the main flame generates enough flame  cur-
rent, the system goes into safety lockout 
(S8700B,D,J,K) or between trial purge (S8700E,F, 
L or M).

When the system goes into safety lockout, power to the 
spark generator is interrupted, the power to the gas 
valve is interrupted, the alarm circuit is completed and 
the LED is steady on. The system stays locked out until 
it is reset by moving the temperature control setpoint to 
below the room temperature, no call for heat, for five 
seconds. The system can be re-energized by moving 
the temperature control setpoint 5

°

F (3

°

C) above the 

room temperature or removing 24V power to the control 
then reapplying.

Note: 

S8700E,F, L, M models automatically reset 
from lockout after one hour if the call for heat is 
still present. A normal ignition sequence will be 
initiated.

SERVICE

WARNING

High Voltage Hazard.
 Shock can cause personal injury.
To prevent electric shock, do not allow fingers to 
touch the stripped end of the jumper or the 
spark terminal. 

IMPORTANT
— Only persons trained and experienced in DSI 

systems should service this equipment.

— Always de-energize the system for at least five 

seconds before recycling for further tests.

— Always turn off the gas supply before performing 

ignition checks.

— S8700 control cannot be repaired. If the 

troubleshooting procedure indicates a malfunction in 
the S8700, it must be replaced.

— The following service procedures are for the S8700 

and basic DSI systems. On all installations, refer to 
the appliance manufacturer’s service instructions.

Preliminary Check

The following checks should be made before trouble-
shooting the system:

— Check for power to the heating appliance and the 

S8700. Voltage to the control should be between 
20.5 and 28.5 Vac, when in run mode.

— Make certain that the manual shut-off valve in the 

supply line and the gas cock knob on the 
combination gas control valve are open. 

— Check the ignition cable  for signs of damage or cut 

insulation, exposed wires or loose connections. 
Repair or replace as necessary.

— Make certain that all wiring connections are clean 

and tight.

Summary of Contents for S8700 Series

Page 1: ...tput is positive phase one half wave rectified 24 Vac Spark Output 14 KV minimum into 25 picofarad capacitive load Environmental Ambient Operating Temperature 40 F to 175 F 40 C to 79 C Relative Humidity 5 to 95 at 95 F 35 C noncondensing Ignition Sequence Flame Sense Prepurge See Table 1 Ignition Trials to Lockout See Table 1 Trial for Ignition Times 4 6 6 6 11 1 or 21 1 second nominal available ...

Page 2: ... to protect the control Proper insulation or shielding should be provided by the appliance manufacturer verify proper air circulation is maintained when the appliance is installed System Requirements S8700 system requirements Q347A Spark Igniter and Q354A Flame Sensor or a Q366 with separate spark igniter and flame sensor mounted on a common bracket Equivalent ignition hardware may be used Honeywe...

Page 3: ...ontrol 1 Connect the system components to the S8700 terminals as shown in the wiring diagrams Fig 2 and 3 Refer to the heating appliance manufac turer s instructions for wiring any other auxiliary controls 2 Adjust the temperature control heat anticipator if provided to match the system current draw The current draw equals the total current required for the S8700 0 15A plus the gas valve and all o...

Page 4: ...t System 1 Turn on the power and the gas supply 2 Set the temperature control to call for heat and watch for a spark at the igniter S8700B D E F models have no delay on start up S8700J K L M models have a predetermined delay on start up for prepurge Check that the system starts as follows Prepurge delay if provided spark turns on gas valve opens at once and burner ignites after gas reaches the mai...

Page 5: ...the reset normal condition and interrupts the spark ignition circuit Should the current flow be interrupted i e flame out condition the spark will be re initiated immediately and a normal trial for ignition will occur If the main burner lights and proves a normal run will occur If the main burner does not light and prove the S8700 goes into lockout The S8700 keeps the gas control main valve open a...

Page 6: ...gnition circuit do the following 1 Shut off the gas supply to the gas control 2 Be sure system power supply delivers proper volt age to the S8700 during the ignition cycle 3 Disconnect the ignition cable at the S8700 spark terminals to isolate the circuit from the spark igniter or igniter sensor Prepare a short jumper lead using heavily insulated wire such as ignition cable Fig 4 S8700B D J K one ...

Page 7: ...y even though operation is normal at time of checkout Therefore if nuisance shutdowns have been reported be sure to check ground connections Electrical ground connections at the spark igniter or igniter sensor and the S8700 must be clean and tight If leadwire is damaged or deteriorated use only a No 14 or No 18 gauge moisture resistant thermoplastic insulated wire with 221 F 105 C minimum rating a...

Page 8: ...ions as described in the following sections Fig 6 S8700D F K M dual rod flame current measurement Fig 7 S7800B E J L single rod flame current measurement Burner Flame The flame sensor must be constantly immersed in flame Check the burner flame conditions as shown in Fig 7 NOTE Note If the main burner flame is fluctuating or lifting off the main burner intermittent flame signals can be generated Ad...

Page 9: ...ce or repair the troubleshooting sequence should be repeated until normal system operation is obtained NOTE When the appliance is in the lightoff mode ignition spark and the gas control are energized only during the trial for ignition which can last from four to 21 seconds depending on the S8700 model It will be necessary to recycle the call for heat to the control while performing this troublesho...

Page 10: ...SPARK GAP IS NOT TOO SMALL OR TOO LARGE ALL OK REPAIR REPLACE AS NECESSARY REPAIR REPLACE AS NECESSARY IF S8700 GOES INTO LOCKOUT RESET SYSTEM CHECK FOR 24 VAC BETWEEN S8700 VALVE AND VALVE GND TERMINALS DURING TRIAL FOR IGNITION CHECK GAS SUPPLY GAS CONTROL AND GAS CONTROL WIRING REPAIR REPLACE AS NECESSARY IF S8700 GOES INTO LOCKOUT RESET SYSTEM CHECK ALL IGNITION CABLE BURNER GROUND WIRING AND ...

Page 11: ...11 69 1299 ...

Page 12: ...Home and Building Control Honeywell Inc Honeywell Limited Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P O Box 524 North York Ontario Minneapolis MN 55408 0524 M2H 3N7 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Reviews: