TK_S014 – Installation Manual
5
INTRODUCTION
What TK_S014 (RTU A08) is?
TK_S014 is a Temaline device acting as a single door controller.
It can manage up two third party Wiegand readers (on the two sides of the doors), the inputs / outputs used
for the management of such readers (led and buzzers) and the inputs / outputs needed for the management
of the door (door state, REX button, lock commands).
The device can be used to manage these two door scenarios:
•
Reader on one side of the door, REX button on the other
•
Readers on both the door sides
Be aware that, even if the device can manage two third party Wiegand readers, it cannot
manage two different doors. When the device manages two readers the only allowed
configuration is to have them on the two sides of the same door
The device needs to be wired by mean of a Lonwork connection to a Temaline TemaServer device that acts
as a controller.
RTU A08 together with other Temaline devices
The RTU A08 device can be used together with other Temaline devices to compose a TemaKey; there are
different TemaKey types that differ from the type of Human Machine Interface they have.
Each TemaKey consists of one or more RTU modules that must be positioned and connected to their
respective wall attachment frames (RTU-Sxx) as indicated in the table below.
Here below the list of TemaKeys can be composed using the RTU A08 device and their characteristics.
Readers
Code
Composition
Notes
TK_S014
RTU-A08 + third party Wiegand reader
Weight=0.2Kg
Power=0.9W
Current=70mA
(Excluding reader current)
RTU-A08 + 2 third party Wiegand
readers
Weight=0.2Kg
Power=0.9W
Current=70mA (Excluding readers current)
The 2 readers are on the same door one in
entry and one in exit direction
Interactive Terminals
Code
Composition
Notes
TK_D214
RTU-A08 + third party Wiegand
RTU-C02 + 2 RTU-S01
Weight=1.15Kg
Power=6.2W
Current=450mA (Excluding reader current)
RTU-A08+ 2 third party Wiegand readers
+ RTU-C02 + 2 RTU-S01
Weight=1.15Kg
Power=6.2W
Current=450mA (Excluding readers current)
The 2 readers are on the same door one in
entry and one in exit direction