RTH600
21
69-2206EF—01
About your new thermostat
SETUP
WIRING
ASSIST
ANCE
TROUBLESHOOTING
Alternate wiring (conventional systems)
If labels do not match terminals, connect wires as
shown here (see notes, below).
Remove metal jumper connecting
R
and
Rc
only
if you must connect both
R
and
Rc
wires.
If your old thermostat had both
R
and
RH
wires,
remove metal jumper. Connect the
R
wire to the
Rc
terminal, and the
RH
wire to the
R
terminal.
If your old thermostat had only 1
C
or
C1
wire, connect it to the
C
terminal. If your old
thermostat had 2
C
or
C1
wires, wrap each
separately with electrical tape and do not
connect them.
RC
R
W
Y
G
C
Y2
W2
Rc
R
W
Y
G
C
Y2
W2
M28076
2
3
2
Wiring—conventional system
Summary of Contents for RTH7600 Series
Page 1: ...RTH7600 Series Touchscreen Programmable Thermostat 69 2206EF 01 Quick Installation Guide ...
Page 3: ... 69 2206EF 01 1 Turn Off Power to Heating Cooling System M28097 ...
Page 31: ...Série RTH7600 Thermostat programmable 69 2206EF 01 Guide d installation rapide ...
Page 33: ... 69 2206EF 01 1 Couper le courant du système de chauffage de climatisation M28097 ...