65-0120—1
50
TABLE 12—HOLD AND FAULT MESSAGE SUMMARY (Continued)
Annunciation Message
System Failure
Fault 18
*Flame Detected*
Flame sensed when shutter opened and no flame is expected during PURGE .
Fault 19
*Main Flame Ign.*
Flame was lost during MFEP or the first ten seconds of the RUN state.
Fault 20
*Low Fire Sw. Off*
Low Fire Interlock Switch failure to close during PURGE.
Fault 22
*Lockout ILK*
Lockout Interlock fault during PURGE.
Fault 24
*Call Service*
Internal fault. Flame Interlock was on when it should be off.
Fault 25
*Call Service*
Internal fault. Flame Interlock was off when it should have been on.
Fault 26
*Man-Open Sw. Off*
The MOS Switch was off when it should be on.
Fault 27
*Start Switch On*
Start Switch was on when it should be off. Possible jumpered or welded Start Switch.
Fault 28
*Pilot Flame Fail*
Pilot flame failure during Pilot Flame Establishing Period.
Fault 29
*Lockout ILK*
Lockout Interlock fault.
Fault 31
*Low Fire Sw. Off*
Low Fire Interlock failure to close during run.
Fault 33
*Preignition ILK*
Preignition Interlock fault.
Fault 35
*Call Service*
Internal fault. Safety relay was off when it should be on or internal fuse has blown.
Fault 36
*Call Service*
Internal fault. Main valve terminal was off when it should be on.
Fault 37
*Call Service*
Internal fault. Pilot (ignition) valve terminal was off when it should be on.
Fault 38
*Call Service*
Internal fault. Ignition terminal was off when it should be on.
Fault 40
*Call Service*
Internal fault. Safety relay was on when it should be off.
Fault 41
*Main Valve On*
Main valve terminal was on when it should be off.
Fault 42
*Pilot Valve On*
Pilot (ignition) valve terminal was on when it should be off.
Fault 43
*Ignition On*
Ignition terminal was on when it should be off.
Fault 45
*Low Fire Sw. Off*
Low Fire Interlock Switch failed to close or stay closed.
Fault 46
*Flame Amp Type*
Either Flame Failure Response Time or type of amplifier input from the amplifier
changed while the device was powered. Could also occur if pilot (ignition) valve
hold input terminal T16 is on and non shutter-check detector/amplifier is used.
Fault 47
*Jumpers Changed*
One or all of the configuration jumpers were changed from original configuration
after 200 hours of operation.
RM7838B
TROUBLESHOOTING
(continued)