TABLE 11—SELECTABLE MESSAGES (SEE TABLE 4).
Selectable Message/
Possible States/Range
Display
Description
(Terminals)
Comments
Flame Signal
Flame signal
0 - 5.0 Vdc
Flame relay pull-in and
strength.
Flame Amp (+
drop-out value 1.25 Vdc.
and - (Com))
Total Cycles
Total number
0 - 99,999 cycles
A cycle will be updated
of equipment
each time the main
operating cycles.
valve is energized.
Total Hours
Total number of
0 - 99,999 hours
An hour will be updated
equipment operating
each time the main valve
hours.
output is energized for
60 minutes.
Fault History
First level prompt for
(six most recent faults)
history information.
Has subset level.
Fault Cycle
H1
Cycle when
0 - 99,9999 cycles
fault occurred.
Fault Hours
H1
Run hour when the
0 - 99,9999 hours
fault occurred.
Fault Code
H1
Number that identifies
0 - 999
lockout reason.
*Fault Message*
H1
Indicates lockout cause.
Sequence Message
H1
Indicates where lockout
occurred in sequence.
(Second Line Message)
H1
Explains further
information avail-
able from RM7838B
or may be blank
if no pre-emptive
second line.
H2…H6 etc.
First level prompt for
Diagnostic Information
history information.
Has subset level.
Device
Device type
RM7838Bx
number.
Device Suffix
Device suffix
nnnn
number.
Run/Test Sw.
Position of
RUN or TEST
Run/Test Switch.
OperControl
T6
Recirculates
ON or OFF
Indicates if input is on
AFS/limits
(energized) or off
Stop Switch input.
(de-energized.)
Interlock
T7
Running/Lockout
ON or OFF
Indicates if input is on
Interlock.
(energized) or off
(de-energized.)
Pilot Valve
T8
Pilot Valve.
ON or OFF
Indicates if output term-
inal is on (energized) or
off (de-energized.)
Main Valve
T9
Main Fuel Valve.
ON or OFF
Indicates if output term-
inal is on (energized) or
off (de-energized.)
(continued)
RM7838B
TROUBLESHOOTING