Honeywell RA890F Protectorelay Primary Control Quick Manual Download Page 8

60-2034—7

8

RA890F

C H E C K O U T

Checkout

IF A STEADY READING OF AT LEAST MINIMUM

STRENGTH CANNOT BE OBTAINED, ONE OR MORE
OF THE FOLLOWING CONDITIONS CAN EXIST:

• Improper supply voltage.
• Defective flame detector wiring including:

— Open circuits.
—Short circuits.
— High resistance shorts caused by moisture, accu-

mulated dirt, or improper choice of detector leadwire
for the particular installation.

• Improper sighting, improper viewing window, or dirty

viewing window for optical detectors.

• Improper application of a flame rod including:

— Insufficient ground area.
— Poor location of flame rod in flame.
— Excessive heat on flame rod insulator (greater than

600

°

F (316

°

C).

— Ignition interference.

• Improper application of a vacuum photocell, including:

— Temperature over 165

°

F (74

°

C) at photocell.

— Dirty photocell envelope.

• Defective sensor.

Fig. 8—Connecting meter to read flame
current.

CAUTION

Use extreme care while testing the RA890F; line
voltage can be present on most terminals when
power is on.

PRELIMINARY CHECKS

Before placing the system in operation, complete the

following preliminary checks:

1. Check through wiring. Use a meter to check the conti-

nuity of all circuits. See Fig. 8.

2. Check flame detector installation.
3. Check burner adjustments.
4. Thoroughly purge gas piping.
5. Reset the safety switch by pushing in and then releas-

ing the green safety switch button.

6. If the system has a standing pilot, make sure the pilot

link (Fig. 7) is removed and the pilot is lit.

CHECKOUT REQUIRED

Before the installation is complete, satisfactorily perform

all checkout tests indicated below.

Flame Current Check (all installations).
Pilot Turndown Test (all installations that require proof of

pilot before main fuel valve is opened).

Safe Shutdown Checks—Flame failure, power failure,

limit action (all installations).

Hot Refractory Hold-In (photocell applications only).

FLAME CURRENT CHECK

The flame current check is the best indicator of proper

flame detector application. Perform the check at the time of
installation, at any time service is done on the system, and at
least once a month or more often while the system is in
operation. This prevents shutdowns due to poor flame signal.

Perform test by connecting a W136 (or equivalent)

microammeter in series with the flame detector and reading
the flame signal while the burner is operating.

Insert a 196146 Meter Connector Plug, wired color-to-

color to the W136A leadwires, into the test jack on the
RA890F. This automatically puts the microammeter in se-
ries with the flame detector.

If a meter connector plug is not available, disconnect the

flame detector lead from the F terminal; then connect this
lead to the Black lead of the microammeter, and connect the
Red lead of the microammeter to the F terminal.

When reading the flame current, assure the following

criteria are met:

1. The flame current is steady; meter does not vary more

than a needle width.

2. The flame current is at least two microamperes for a

rectification type detector like used with the RA890F. The
normal operating range is 2 to 5 microamperes.

M8755

BLACK

BLACK

BLACK

RED

RED

FLAME
CURRENT
TEST JACK

RA890

IF 196146  METER CONNECTOR PLUG IS NOT AVALIABLE —

FLAME 
DETECTOR

F LEAD

G LEAD

RED

F

G

W136

RA890

-

+

W136

196146  METER 
CONNECTOR 
PLUG (SUPPLIED 
WITH W136)

Summary of Contents for RA890F Protectorelay Primary Control

Page 1: ... required during Off cycle no tube to warm up before starting Push to reset safety switch in dust resistant enclosure Built inprotectionagainstignitioncrossoverinflame rod systems Does not start if flame simulating failure occurs in flame detector circuit Automatic safety shutdown if flame fails on start or if flame not re established after flame failure Flame signal current is directly measurable...

Page 2: ...r 1 0A at 120 Vac in suitable wiring enclosure Low Voltage Control Circuit T T 0 3A Ordering Information When purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor refer to the TRADELINE catalog or price sheets for complete ordering number or specify 1 Order number standard or TRADELINE 2 Voltage and frequency 3 Flame response time 4 Safety switch tim...

Page 3: ...TE All devices meeting UL components recognition have the following symbol Replacement exchange controls that meet current UL requirements are identified with the term REMFR D following the listing or component recognition mark Canadian Standards Association Certified 120V models only File No LR1620 Factory Mutual Approved Report No 17678 19417 and 19784 American Gas Association Design Certified f...

Page 4: ...nt temperature is within the specified rating Mount the subbase so the top and bottom are horizontal and the back is vertical The subbase can lean backward as much as 45 degrees when necessary See Fig 1 Fig 1 Mounting subbase in in mm M8681 HORIZONTAL VERTICAL 2 7 8 73 0 4 1 8 104 8 KNOCKOUTS 9 FOR 1 2 IN 13 CONDUIT 45 DEGREES MAXIMUM LEAN WIRE SUBBASE 1 Disconnect power supply see Fig 2 before ma...

Page 5: ... ALARM TERMINALS ARE ENERGIZED THROUGH RA890 SAFETY SWITCH ALARM WILL NOT SOUND UNTIL SAFETY SWITCH TRIPS OUT POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR RA890E REPLACEMENT LEAVE POWER CONNECTED TO TERMINAL 1 SUBBASE WIRING CHANGES ARE NOT REQUIRED SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT OR OPERATING CONTACTS IN SERIES WITH THE MAIN F...

Page 6: ...ON AS REQUIRED RA890F IS POWERED AT TERMINAL 6 ONLY WHEN REPLACING ANOTHER MODEL LEAVE HOT LINE L1 CONNECTED TO TERMINAL 1 EVEN THROUGH IT IS NOT NECESSARY FOR OPERATION MAY USE LINE OR LOW VOLTAGE CONTROLLER IF LINE VOLTAGE CONTROLLER IS USED CONNECT IT BETWEEN THE LIMIT CONTROLLER AND TERMINAL 6 JUMPER T T FOR INTERMITTENT IGNITION CONNECT TO TERMINAL 3 OPENING OF A LIMIT CONTROL OR LINE VOLTAGE...

Page 7: ...SET PUSHBUTTON LOAD RELAY 1K Q270A SUBBASE M8766 FLAME RELAY 2K CAPTIVE MOUNTING SCREWS 10 ARC GAP PROTECTOR OPTIONAL ALARM CONTACT 3 PILOT LINK JUMPER WIRE 0N BASE ALONGSIDE TEST JACK TEST JACK PILOT LINK ARC GAP PROTECTOR M8767 Operation NORMAL OPERATION SUMMARY Normal control operation is summarized below Refer to Fig 5 for the internal schematic of the control 1 Call for heat Load relay pulls ...

Page 8: ...m all checkout tests indicated below Flame Current Check all installations PilotTurndownTest allinstallationsthatrequireproofof pilot before main fuel valve is opened Safe Shutdown Checks Flame failure power failure limit action all installations Hot Refractory Hold In photocell applications only FLAME CURRENT CHECK The flame current check is the best indicator of proper flame detector application...

Page 9: ... on the axis of a pilot flame or b Adjusting a flame rod detector so that a larger mini mum pilot is required CAUTION If the pilot needs to be adjusted and rechecked allow five minutes for the purge of unburned gases in the firebox before proceeding to the next step 10 Repeat the entire turndown test until the flame is established promptly in step 7 11 Turn up the pilot to full flame at the comple...

Page 10: ...ners tested were found to leave deposits on the contact surfaces or to attack RA890 chassis parts Troubleshooting Whentroubleoccursintheheatingsystemanditscauseis not immediately apparent the service technician can apply the following step by step checkout to locate the cause of most problems Refer to Fig 3 and 4 for terminal locations and to Fig 6 for location of component parts CAUTION Use extre...

Page 11: ... PROBLEMS Relay Chatter Load relay chatter can result from extreme low voltage notifypowercompany orfromalooseconnection tighten Flame relay chatter may result from improper combus tion adjust burner or soot or carbon on flame detector clean and correct the cause Difficulty Resetting Safety Switch 30 Second Safety Switch Models _ Ambienttemperaturemaybebelow 10 F 12 C Prob lem is corrected by warm...

Page 12: ...rol Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: