Honeywell RA890F Protectorelay Primary Control Quick Manual Download Page 10

60-2034—7

10

RA890F

SERVICE • TROUBLESHOOTING

Service

GENERAL SERVICE

1. Only qualified personnel should attempt to service

heating equipment or controls.

2. Perform all checks required in the Checkout section

when replacing the RA890, or when relighting or restoring
power to the system after shutdown.

3. The captive mounting screws carry current; always

disconnect power before loosening or tightening the mount-
ing screws.

4. On each service call, check the controller for the ap-

proximately correct calibration and differential; assure that it
is mounted securely. (See controller instructions.)

5. Never use oil on any part of the RA890F.
6. When cleaning the burner, clean the flame detector.
7. Do not manually push in the RA890 relays. This may

damage the relays and it is an unsafe practice because it
overrides the protective features of the relay. Clean relay
contacts only as instructed below.

PERIODIC MAINTENANCE

The specific maintenance schedule setup depends on

several factors including type of equipment being controlled,
operating conditions (dirt and heat especially), cost of a

nuisance shutdown, etc. The following should be included in
any program:

1. Replace the vacuum tubes in the C7012 Flame Detec-

tor (when used) annually.

2. Perform a flame failure check and pilot turndown test

whenever the burner is serviced, and at least annually.

3. Inspect and clean the detector and any viewing win-

dows as often as required by soot accumulation and heat
conditions at the detector.

4. Perform a flame current check at least monthly and

more often when a shutdown may be costly.

5. Clean contacts only when required by failure to oper-

ate properly.

CONTACT CLEANING

Clean the relay contacts on the RA890 only when re-

quired and then only with Honeywell part no. 132569 Con-
tact Cleaner. The contact cleaner comes in pressurized spray
cans; directions for its use are printed on the can. Do not use
other commercial contact cleaners. Most cleaners tested
were found to leave deposits on the contact surfaces or to
attack RA890 chassis parts.

Troubleshooting

When trouble occurs in the heating system and its cause is

not immediately apparent, the service technician can apply
the following step-by-step checkout to locate the cause of
most problems. Refer to Fig. 3 and 4 for terminal locations,
and to Fig. 6 for location of component parts.

CAUTION

Use extreme care troubleshooting the RA890F;
line voltage can be present on most terminals when
power is on.

TEST STANDBY OPERATION

1. Set controller not to call for heat.
2. Reset the safety switch by pushing in and then releas-

ing the green safety switch reset button.

3. Close the line switch.
4. Check for line voltage at terminals 2 and 6. (Voltage

will be zero when a line voltage controller is used; check for
line voltage when controller is set to call for heat.)

a. Voltage must be 10 to -15 percent of the rated

voltage.

b. When voltage is zero (with low voltage controller), be

sure limit switch contacts are closed and check power
supply. Check for blown fuses, open circuit, or open
disconnect switch.

5. Check position of flame relay. (When a line voltage

controller is used, observe the action of the flame relay on a
call for heat.)

a. If the flame relay is out, proceed to step 6.
b. If the flame relay is pulled in, check for a flame simulat-

ing condition.

(1) Insert flame simulator plug or part no. 196146

Cable Plug into the test jack; do not ground the
other end.

(2) If flame relay holds in, replace the RA890.
(3) If flame relay drops out, trouble is in the flame

detector or external circuit. Check for light reach-
ing the photocell, hot refractory hold-in, or defec-
tive wiring.

TEST STARTING OPERATION

6. Set controller to call for heat . (If control uses a line

voltage controller, go back to steps 4 and 5.)

7. Observe load relay for pull-in.
a. Load relay pulls in to light pilot and start burner—

proceed to step 11.

b. Load relay does not pull in—proceed to step 8.
c. Load relay pulls in but does not light or burner does

not start—proceed to step 10.

8. Check line voltage controller, if used, and the limit; if

the load relay does not pull in, check again for power at

Summary of Contents for RA890F Protectorelay Primary Control

Page 1: ... required during Off cycle no tube to warm up before starting Push to reset safety switch in dust resistant enclosure Built inprotectionagainstignitioncrossoverinflame rod systems Does not start if flame simulating failure occurs in flame detector circuit Automatic safety shutdown if flame fails on start or if flame not re established after flame failure Flame signal current is directly measurable...

Page 2: ...r 1 0A at 120 Vac in suitable wiring enclosure Low Voltage Control Circuit T T 0 3A Ordering Information When purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor refer to the TRADELINE catalog or price sheets for complete ordering number or specify 1 Order number standard or TRADELINE 2 Voltage and frequency 3 Flame response time 4 Safety switch tim...

Page 3: ...TE All devices meeting UL components recognition have the following symbol Replacement exchange controls that meet current UL requirements are identified with the term REMFR D following the listing or component recognition mark Canadian Standards Association Certified 120V models only File No LR1620 Factory Mutual Approved Report No 17678 19417 and 19784 American Gas Association Design Certified f...

Page 4: ...nt temperature is within the specified rating Mount the subbase so the top and bottom are horizontal and the back is vertical The subbase can lean backward as much as 45 degrees when necessary See Fig 1 Fig 1 Mounting subbase in in mm M8681 HORIZONTAL VERTICAL 2 7 8 73 0 4 1 8 104 8 KNOCKOUTS 9 FOR 1 2 IN 13 CONDUIT 45 DEGREES MAXIMUM LEAN WIRE SUBBASE 1 Disconnect power supply see Fig 2 before ma...

Page 5: ... ALARM TERMINALS ARE ENERGIZED THROUGH RA890 SAFETY SWITCH ALARM WILL NOT SOUND UNTIL SAFETY SWITCH TRIPS OUT POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR RA890E REPLACEMENT LEAVE POWER CONNECTED TO TERMINAL 1 SUBBASE WIRING CHANGES ARE NOT REQUIRED SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT OR OPERATING CONTACTS IN SERIES WITH THE MAIN F...

Page 6: ...ON AS REQUIRED RA890F IS POWERED AT TERMINAL 6 ONLY WHEN REPLACING ANOTHER MODEL LEAVE HOT LINE L1 CONNECTED TO TERMINAL 1 EVEN THROUGH IT IS NOT NECESSARY FOR OPERATION MAY USE LINE OR LOW VOLTAGE CONTROLLER IF LINE VOLTAGE CONTROLLER IS USED CONNECT IT BETWEEN THE LIMIT CONTROLLER AND TERMINAL 6 JUMPER T T FOR INTERMITTENT IGNITION CONNECT TO TERMINAL 3 OPENING OF A LIMIT CONTROL OR LINE VOLTAGE...

Page 7: ...SET PUSHBUTTON LOAD RELAY 1K Q270A SUBBASE M8766 FLAME RELAY 2K CAPTIVE MOUNTING SCREWS 10 ARC GAP PROTECTOR OPTIONAL ALARM CONTACT 3 PILOT LINK JUMPER WIRE 0N BASE ALONGSIDE TEST JACK TEST JACK PILOT LINK ARC GAP PROTECTOR M8767 Operation NORMAL OPERATION SUMMARY Normal control operation is summarized below Refer to Fig 5 for the internal schematic of the control 1 Call for heat Load relay pulls ...

Page 8: ...m all checkout tests indicated below Flame Current Check all installations PilotTurndownTest allinstallationsthatrequireproofof pilot before main fuel valve is opened Safe Shutdown Checks Flame failure power failure limit action all installations Hot Refractory Hold In photocell applications only FLAME CURRENT CHECK The flame current check is the best indicator of proper flame detector application...

Page 9: ... on the axis of a pilot flame or b Adjusting a flame rod detector so that a larger mini mum pilot is required CAUTION If the pilot needs to be adjusted and rechecked allow five minutes for the purge of unburned gases in the firebox before proceeding to the next step 10 Repeat the entire turndown test until the flame is established promptly in step 7 11 Turn up the pilot to full flame at the comple...

Page 10: ...ners tested were found to leave deposits on the contact surfaces or to attack RA890 chassis parts Troubleshooting Whentroubleoccursintheheatingsystemanditscauseis not immediately apparent the service technician can apply the following step by step checkout to locate the cause of most problems Refer to Fig 3 and 4 for terminal locations and to Fig 6 for location of component parts CAUTION Use extre...

Page 11: ... PROBLEMS Relay Chatter Load relay chatter can result from extreme low voltage notifypowercompany orfromalooseconnection tighten Flame relay chatter may result from improper combus tion adjust burner or soot or carbon on flame detector clean and correct the cause Difficulty Resetting Safety Switch 30 Second Safety Switch Models _ Ambienttemperaturemaybebelow 10 F 12 C Prob lem is corrected by warm...

Page 12: ...rol Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: