43-TV-33-88 iss.2 GLO Nov 06 UK
6
Re-fit the case and back panel assembly
Fit the case by carefully sliding it on from the rear of the recorder. Ensure the case is orientated correctly, with the
power supply cooling slots on the top of the recorder.
Slide the case/back panel fully forward ensuring that no internal cables get trapped between the case and front bezel.
The case should sit flat on the back of the front bezel.
Re-fit the four screws that secure the case.
Screw should be tightened to a torque of 120cNm.
Touch Screen Calibration
Calibration of the touch screen may not be required.
Test the touch screen calibration by using the “Touch Test” option on the recorder. This allows you to touch the screen
and check a cursor moves to the correct position. This can be accessed by entering the “Main Menu”, then “Screen”,
then “Touch Test”.
If the touch screen needs recalibrating:
Exit the touch test screen with the “finish” button the press “Calibrate”. This will take you to the calibration screen.
Using the stylus touch the screen at the centre of the cursor. Hold the stylus there until the cursor moves. Continue
touching and holding on the cursor until calibration is complete.
Once calibration is complete, touch the screen once more to exit calibration.
The new calibration can be tested again with “Touch test” if required.
More information on touch screen calibration can be found in the product user manual.
Copyrighted Materials. For more information please contact your supplier.