SETTINGS AND ADJUSTMENTS

Calibration

IMPORTANT

The Q7002A is not field-adjustable.

Q7002B

Calibrate the device as follows:

1. Set the output (OUT) jumper to voltage (V) or current

(MA) to match desired output.

2. Set the INPUT and REF jumpers according to Table 1.
3. Verify ACT jumper is set to direct (D) or reverse (R).

The device is shipped with the ACT jumper set to D.

4. Verify span jumper (SPN) is set to LO. The device is

shipped with the SPN jumper set to LO.

5. Turn SPAN potentiometer clockwise            25 turns.
6. Remove and set aside both Z1 jumpers.

NOTE:

The input signal does not affect the ZERO1
potentiometer adjustment.

Q7002C

M13271

MA OUT

VOLTS OUT

1-5 Vdc

4-20 mA

COM

24V PWR

SIG IN +

SIG IN - 

L1

(HOT)

L2

L1

(HOT)

L2

PWM
CONTACT

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
THE POWER SUPPLY CAN BE 24 VAC (AS SHOWN) OR 24 VDC.

1

2

1

2

Q7002C

M13272

MA OUT

VOLTS OUT

1-5 Vdc

4-20 mA

COM

24V PWR

SIG IN +

SIG IN - 

L1

(HOT)

L2

PWM
CONTACT

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
THE POWER SUPPLY CAN BE 24 VAC (AS SHOWN) OR 24 VDC.

1

2

2

1

7. Trim ZERO1 potentiometer to minimum desired output

value.

8. Reinstall both Z1 jumpers.
9. Set Z2 jumper to LO. The device is shipped with the Z2

jumper set to LO.

10. Apply the minimum input signal.
11. Trim the ZERO2 potentiometer to the same value used

in step 7.

12. If the desired value cannot be achieved, remove Z2

jumper and repeat step 11.

NOTE:

If the desired value remains unachievable,
place the Z2 jumper in the HI position and
repeat step 11.

13. Apply the maximum input signal.
14. Trim the SPAN potentiometer to the maximum output

value.

15. If the desired value cannot be reached, move the SPN

jumper from LO to HI.

16. Return to step 10 and repeat steps until both the

minimum and maximum output values are correct.

NOTE:

Typically one repetition of steps 10 through 15
is sufficient.

17. Apply an input signal at the midpoint of the input span.
18. Verify that the output is at the midpoint of the output

range.

Q7002C

Voltage Only Output
Calibrate the device as follows:

1. Determine the minimum and maximum voltage output

required.

2. Determine the minimum mA calibration output with the

following formula:

Minimum Output (mA) = 20 mA x (Desired Minimum

Volts) / (Desired Maximum Volts)

3. Apply minimum input pulse signal.
4. Set MA ZERO potentiometer to the value determined in

step 2.

5. Using a signal generator, apply maximum input pulse

signal.

6. Set MA SPAN potentiometer to 20 mA.
7. Set the VOLT ADJ potentiometer to the desired

maximum voltage.

NOTE:

The device calibrates the minimum voltage
automatically according to the ratio of mA
output extremes.

EXAMPLE: 4-20 mA signal produces a ratio of 5 to 1.

As a result, with maximum voltage set to
10V, the device sets the minimum to 2V.

Current and Voltage Output or Current Only Output
Calibrate the device as follows:

1. Apply minimum input pulse signal.
2. Set MA ZERO potentiometer to the desired minimum

mA output.

3. Apply maximum input pulse signal.
4. Set MA SPAN potentiometer to the desired maximum

mA output.

Summary of Contents for Q7002A

Page 1: ...a voltage or current output for an actuator Inputs and outputs are jumper selectable and include adjustable zero and span Output is jumper selectable direct or reverse acting Includes reference voltage and current to power an input device or sensor Q7002C Pulse to Analog Interface Module Accepts a pulse width modulation PWM signal User selectable PWM time base Positive or negative input reference ...

Page 2: ... with enclosure Q7002A1019 with track mount Universal Analog Interface Modules Q7002B1009 with enclosure Q7002B1017 with track mount Pulse to Analog Interface Modules Q7002C1007 with enclosure Q7002C1015 with track mount Dimensions See Fig 1 Approval Ratings Enclosure Models NEMA 1 Q7002A Economizer Interface Module Electrical Ratings Supply Voltage 24 Vac 10 24 Vdc 10 Input Impedance 10K ohm Outp...

Page 3: ...umidity Range 5 to 95 RH noncondensing Weight Maximum 13 oz 0 36 kg Table 1 Acceptable Q7002B Inputs NOTE All Q7002B inputs have adjustable zero and span Signal Minimum Input Reference Jumper Positions Type Range Spana Impedance Output Input Ref Voltage b 0 1 09 Vdc 55 mV 165K N Ab 10 10V Vb 10b 0 10 9 Vdc 550 mV ohms X1 10V 0 2 Vdc 100 mV 301K 10 20V 0 20 Vdc b 1Vb ohmsb X1b 20Vb Current 0 4 mA 0...

Page 4: ...ng Wire the device using Fig 2 through 7 IMPORTANT Comply with national and local codes when wiring the device PWM Time Base Dip Switch Settings in seconds Switch 3 Switch 4 Switch 5 0 1 2 65 Off Off Off 0 1 5 2 a Off a Off a On a 0 1 12 85 Off On Off 0 1 25 6 Off On On 0 59 2 93 On Off Off a Factory default setting INSTALLATION When Installing this Product 1 Read these instructions carefully Fail...

Page 5: ...input Q7002B M13268 SIG OUT 0 18 Vdc PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THE POWER SUPPLY CAN BE 24 VAC AS SHOWN OR 24 VDC 0 20 mA 24V PWR COM REF OUT SIG IN L1 HOT L2 1 2 1 2 0 20 Vdc or 4 20 mA signal OR Q7002B M13269 SIG OUT 0 18 Vdc PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THE POWER SUPPLY CAN BE 24 VAC AS SHOWN OR 24 VDC 0 20 mA 24V PWR COM REF OUT...

Page 6: ...ired value cannot be achieved remove Z2 jumper and repeat step 11 NOTE If the desired value remains unachievable place the Z2 jumper in the HI position and repeat step 11 13 Apply the maximum input signal 14 Trim the SPAN potentiometer to the maximum output value 15 If the desired value cannot be reached move the SPN jumper from LO to HI 16 Return to step 10 and repeat steps until both the minimum...

Page 7: ...dules alerting them that a control pulse can follow The attention pulse is one second longer than the existing time base Q7002C MA OUT VOLTS OUT 1 5 Vdc 4 20 mA COM 24V PWR SIG IN SIG IN L1 HOT L2 1 3 BAS CONTROL PWM CONTACT 1 1 2 3 2 2 M13285 THE POWER SUPPLY CAN BE 24 VAC AS SHOWN OR 24 VDC PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A MAXIMUM OF EIGHT Q7002C INTERFACE MODULES C...

Page 8: ...s Switch 6 Switch 7 Switch 8 2 65 second Time Base a 5 2 second Time Base 12 85 second Time Base 25 6 second Time Base 1b Off Off Off 0 2 0 4 0 9 1 6 2 Off Off On 0 6 1 0 2 5 4 8 3 Off On Off 0 9 1 7 4 1 8 0 4 Off On On 1 2 2 3 5 7 11 2 5 On Off Off 1 5 3 0 7 3 14 4 6 On Off On 1 9 3 6 8 9 17 6 7 On On Off 2 2 4 3 10 5 20 9 8 On On On 2 5 4 9 12 1 24 0 a The 2 65 second time base is appropriate on...

Reviews: