Q7002A,B,C INTERFACE MODULES

63-2551

5

Fig. 2. Q7002A wiring.

24 VAC

ECONO

1

3

4

2

5

2K

ECONOMIZER LOGIC MODULE

1K

1S

1S1

1

1

W7100 or W973

Q7002A

POWER SUPPLY. PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

M13267

L1
(HOT)

L2

AT72 (40 VA)
TRANSFORMER

SIGNAL

INPUT

24V

PWR

COM

1

L1
(HOT)

L2

GND
TR
TR

W
R
B
Y

TR

TR1

Fig. 3. Q7002B wiring with voltage or current input.

Fig. 4. Q7002B wiring with 3-wire potentiometer input.

Fig. 5. Q7002B wiring with 2-wire variable resistance

input.

Q7002B

M13268

SIG OUT

0-18 Vdc

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
THE POWER SUPPLY CAN BE 24 VAC (AS SHOWN) OR 24 VDC.

0-20 mA

24V PWR

COM

REF OUT

SIG IN

L1

(HOT)

L2

1

2

1

2

0-20 Vdc or
4-20 mA
signal

OR

Q7002B

M13269 

SIG OUT

0-18 Vdc

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
THE POWER SUPPLY CAN BE 24 VAC (AS SHOWN) OR 24 VDC.

0-20 mA

24V PWR

COM

REF OUT

SIG IN

L1

(HOT)

L2

1

2

1

2

3-WIRE
POTENTIO-
METER

OR

Q7002B

M13270

SIG OUT

0-18 Vdc

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
THE POWER SUPPLY CAN BE 24 VAC (AS SHOWN) OR 24 VDC.

0-20 mA

24V PWR

COM

REF OUT

SIG IN

L1

(HOT)

L2

1

2

1

2

2-WIRE
VARIABLE
RESISTANCE

OR

Summary of Contents for Q7002A

Page 1: ...a voltage or current output for an actuator Inputs and outputs are jumper selectable and include adjustable zero and span Output is jumper selectable direct or reverse acting Includes reference voltage and current to power an input device or sensor Q7002C Pulse to Analog Interface Module Accepts a pulse width modulation PWM signal User selectable PWM time base Positive or negative input reference ...

Page 2: ... with enclosure Q7002A1019 with track mount Universal Analog Interface Modules Q7002B1009 with enclosure Q7002B1017 with track mount Pulse to Analog Interface Modules Q7002C1007 with enclosure Q7002C1015 with track mount Dimensions See Fig 1 Approval Ratings Enclosure Models NEMA 1 Q7002A Economizer Interface Module Electrical Ratings Supply Voltage 24 Vac 10 24 Vdc 10 Input Impedance 10K ohm Outp...

Page 3: ...umidity Range 5 to 95 RH noncondensing Weight Maximum 13 oz 0 36 kg Table 1 Acceptable Q7002B Inputs NOTE All Q7002B inputs have adjustable zero and span Signal Minimum Input Reference Jumper Positions Type Range Spana Impedance Output Input Ref Voltage b 0 1 09 Vdc 55 mV 165K N Ab 10 10V Vb 10b 0 10 9 Vdc 550 mV ohms X1 10V 0 2 Vdc 100 mV 301K 10 20V 0 20 Vdc b 1Vb ohmsb X1b 20Vb Current 0 4 mA 0...

Page 4: ...ng Wire the device using Fig 2 through 7 IMPORTANT Comply with national and local codes when wiring the device PWM Time Base Dip Switch Settings in seconds Switch 3 Switch 4 Switch 5 0 1 2 65 Off Off Off 0 1 5 2 a Off a Off a On a 0 1 12 85 Off On Off 0 1 25 6 Off On On 0 59 2 93 On Off Off a Factory default setting INSTALLATION When Installing this Product 1 Read these instructions carefully Fail...

Page 5: ...input Q7002B M13268 SIG OUT 0 18 Vdc PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THE POWER SUPPLY CAN BE 24 VAC AS SHOWN OR 24 VDC 0 20 mA 24V PWR COM REF OUT SIG IN L1 HOT L2 1 2 1 2 0 20 Vdc or 4 20 mA signal OR Q7002B M13269 SIG OUT 0 18 Vdc PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THE POWER SUPPLY CAN BE 24 VAC AS SHOWN OR 24 VDC 0 20 mA 24V PWR COM REF OUT...

Page 6: ...ired value cannot be achieved remove Z2 jumper and repeat step 11 NOTE If the desired value remains unachievable place the Z2 jumper in the HI position and repeat step 11 13 Apply the maximum input signal 14 Trim the SPAN potentiometer to the maximum output value 15 If the desired value cannot be reached move the SPN jumper from LO to HI 16 Return to step 10 and repeat steps until both the minimum...

Page 7: ...dules alerting them that a control pulse can follow The attention pulse is one second longer than the existing time base Q7002C MA OUT VOLTS OUT 1 5 Vdc 4 20 mA COM 24V PWR SIG IN SIG IN L1 HOT L2 1 3 BAS CONTROL PWM CONTACT 1 1 2 3 2 2 M13285 THE POWER SUPPLY CAN BE 24 VAC AS SHOWN OR 24 VDC PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A MAXIMUM OF EIGHT Q7002C INTERFACE MODULES C...

Page 8: ...s Switch 6 Switch 7 Switch 8 2 65 second Time Base a 5 2 second Time Base 12 85 second Time Base 25 6 second Time Base 1b Off Off Off 0 2 0 4 0 9 1 6 2 Off Off On 0 6 1 0 2 5 4 8 3 Off On Off 0 9 1 7 4 1 8 0 4 Off On On 1 2 2 3 5 7 11 2 5 On Off Off 1 5 3 0 7 3 14 4 6 On Off On 1 9 3 6 8 9 17 6 7 On On Off 2 2 4 3 10 5 20 9 8 On On On 2 5 4 9 12 1 24 0 a The 2 65 second time base is appropriate on...

Reviews: