Honeywell PRO3200 Installation And Configuration Manual Download Page 1

October 2013

© 2013 Honeywell. All rights reserved.

800-15494

PRO3200 

(PRO32IC)

Intelligent Controller

Installation and Configuration Guide

Summary of Contents for PRO3200

Page 1: ...October 2013 2013 Honeywell All rights reserved 800 15494 PRO3200 PRO32IC Intelligent Controller Installation and Configuration Guide ...

Page 2: ...ell reserves the right to change any information in this document at any time without prior notice WIN PAK is a trademark of Honeywell Inc Ordering Information Please contact your local Honeywell representative or visit us on the web at www honeywellaccess com for information about ordering Feedback Honeywell appreciates your comments about this manual Please visit us on the web at www honeywellac...

Page 3: ... 3 Other 8 3 Setting Up the PRO3200 Hardware 10 3 1 Setting the Jumpers 10 3 2 Setting the DIP Switches 11 3 3 Technical Specifications 13 3 4 Status LEDs 14 3 5 Supplying Power to the PRO3200 Interface 15 3 6 Communications Wiring 16 3 7 Cabinet Tamper and Power Failure Input Wiring 16 3 8 Memory and Real Time Clock Backup Battery 16 4 System Configuration via Web Interface 17 4 1 Connecting to A...

Page 4: ...iv www honeywell com This page is left blank intentionally for double sided printing ...

Page 5: ...eb Server Home Page 18 Figure 7 PRO3200 Web Server Network Settings Screen 19 Figure 8 PRO3200 Host Port Configuration Screen with IP Server Connection 20 Figure 9 PRO3200 Host Port Configuration Screen with IP Client Connection 22 Figure 10 PRO3200 Host Port Configuration with Serial RS 232 Connection 23 Figure 11 PRO3200 Web Server Device HW Info Screen 24 Figure 12 PRO3200 Web Server User Info ...

Page 6: ... 15494 vi LIST OF TABLES Table 1 PRO3200 Jumper Settings 10 Table 2 PRO3200 DIP Switch Settings 11 Table 3 PRO3200 Technical Specifications 13 Table 4 PRO3200 Status LED Combinations During Initialization 14 Table 5 PRO3200 Status LED Combinations During Run Time 15 ...

Page 7: ...3200 Installation and Configuration Guide Document 800 15494 1 PRO3200 Installation In this chapter Notices 2 Product Overview 8 Setting Up the PRO3200 Hardware 10 System Configuration via Web Interface 17 ...

Page 8: ... These fire and safety codes vary from city to city and you must get approval from local fire officials whenever using an electronic product to control a door or other barrier Use of egress buttons for example may be illegal in some cities In most applications single action exit without prior knowledge of what to do is a life safety requirement Always make certain that any required approvals are o...

Page 9: ... WITH THE COMMERCIAL CARRIER RESPONSIBLE FOR THE DAMAGE 1 3 Electro Static Discharge Caution Electro static discharge ESD can damage CMOS integrated circuits and modules To prevent damage always follow these procedures Use static shield packaging and containers to transport all electronic components including completed reader assemblies Handle all ESD sensitive components at an approved static con...

Page 10: ...fective Product or the negligence of Honeywell its agents or its employees Customer shall hold harmless and indemnify Honeywell from and against all claims demands losses and liability arising out of damage to property or injury to persons occasioned by or in connection with the acts or omissions of Customer and its agents and employees and from and against all claims demands losses and liability ...

Page 11: ...mber prior to returning any Product for service repair credit or exchange Honeywell warrants that its Products shall be free from defects in materials and workmanship for a period of two years from the date of shipment of the Product to Customer The warranty on Terminals Printers Communications Products and Upgrade kits is 90 days from the date of shipment Satisfaction of this warranty shall be li...

Page 12: ...lating to the design use and service of the Products shall remain confidential and shall constitute the proprietary rights of Honeywell and Customer agrees to treat such information as confidential Customer shall acquire no rights in the design of the Products or the related materials except to use such information solely for the purpose of and only during the time it sells the Products ...

Page 13: ...ment and thereafter unless specifically waived by Honeywell in writing 1 9 Compliance To obtain applicable EU compliance Declaration of Conformities for this product please refer to our website http www security honeywell com hsce international index html For any additional information regarding the compliance of this product to any EU specific requirements please contact Honeywell Security Commun...

Page 14: ...2 wire serial interface connections Ports 2 and 3 are for RS 485 2 wire downstream support for connecting 32 I O devices See Table 1 PRO3200 Jumper Settings on page 10 for more information on how to configure the port settings 2 3 Other An on board real time clock maintains the date and time taking into account leap year and accounting for global time zones and daylight savings time changes The da...

Page 15: ...PRO3200 Installation Product Overview PRO3200 Installation and Configuration Guide Document 800 15494 9 Figure 1 PRO3200 Connections LEDs and DIP Switches ...

Page 16: ...rs as required 3 1 Setting the Jumpers Table 1 PRO3200 Jumper Settings Jumpers Set At Description J1 N A Factory Use only J2 N A Factory Use Only J3 OFF Port 2 RS 485 EOL Terminator is OFF ON Port 2 RS 485 EOL Terminator is ON J4 OFF Port 3 RS 485 EOL Terminator is OFF ON Port 3 RS 485 EOL Terminator is ON J5 OFF Port 1 RS 485 EOL Terminator is OFF ON Port 1 RS 485 EOL Terminator is ON J6 N A Fact...

Page 17: ...OFF ON OFF OFF Use the factory default communication parameters ON ON OFF OFF Unless the network administrator reserves an IP address for the panel based on the controller board s Media Access Control MAC address the PRO3200 uses Dynamic Host Configuration Protocol DHCP to obtain an IP address from the network DHCP server When power is applied with the switches in this position there is a ten seco...

Page 18: ...e the S4 S3 S2 S1 combination to off off off on DIP switch 1 is read on the fly This sets the login to the default user ID admin and password password for Ethernet communications 4 Create users See User Configuration on page 25 for instructions 5 Set the S4 S3 S2 S1 combination to off off off off 6 Configure the host port for TCP IP and or Serial communications See Host Port on page 20 for instruc...

Page 19: ...ange of 10 to 14Vdc 300mA maximum 12Vdc 240mA 325mA with CoBox Micro nominal Memory and Clock Backup 3Volts Lithium type BR2325 BR2330 CR2330 Ports Port 0 10Base T 100Base TX Ethernet Port 1 RS 232 or 2 wire RS 485 9 600 to 115 200 bps async Port 2 3 2 wire RS 485 2 400 to 38 400 bps async Inputs 2 non supervised dedicated for cabinet tamper and power fault monitoring Cable requirements Power 1 tw...

Page 20: ...D 6 Description ON OFF OFF OFF OFF OFF Basic processor initialization ON ON OFF OFF OFF OFF Internal SRAM test ON OFF ON OFF OFF OFF External SDRAM First Chip ON ON ON OFF OFF OFF External FLASH Test ON OFF OFF ON OFF OFF External SDRAM Second ON ON OFF ON OFF OFF External SRAM Test ON OFF ON ON OFF OFF External EEPROM Test ON ON ON ON OFF OFF External RTC Test ON OFF OFF OFF ON OFF Backup Battery...

Page 21: ...O3200 Power Terminals Table 5 PRO3200 Status LED Combinations During Run Time LED Description 1 Off Line On Line and Battery Status Off Line 20 On ON Line 80 On Double Flash means the Battery is Low 2 Primary Host Communication Activity Ethernet or Port 1 3 Port 2 Communication Activity 4 Port 3 Communication Activity 5 ON Writing to Flash Memory Do NOT cut off power when this LED is ON 6 TBD SPD ...

Page 22: ...nals Inputs TMP and FLT are used for monitoring cabinet tamper and power failure with normally closed contacts These two inputs are for contact closure monitoring only do not use end of line EOL resistor s If these inputs are not used install a short piece of wire at the input to indicate a safe condition 3 8 Memory and Real Time Clock Backup Battery The event log buffer and the real time clock ar...

Page 23: ... to ACDSM for the First Time 1 Use the factory default controller IP address 192 168 0 251 2 Set the DIP switches to S4 OFF S3 OFF S2 ON S1 OFF Note S1 must be set to OFF for the factory default After the panel powers up change S1 to ON to enable the use of the default user name and password 3 Connect the computer to host the web server via Ethernet Port 0 Connection should be via crossover Ethern...

Page 24: ...nstallation System Configuration via Web Interface 4 3 Home Page The first screen after the login is the home page which displays all the available configuration links on the left navigation bar Figure 6 PRO3200 Web Server Home Page ...

Page 25: ...and reserve an IP address for the MAC address or they can select the other option button and assign a Static IP address as well Dynamic IP Configuration Method 1 Click the Dynamic IP option button to select the Dynamic Host Configuration Protocol DHCP method to obtain IP address automatically 2 Click OK Note The WIN PAK communicates with the PRO3200 panel using an IP address If you must use the Dy...

Page 26: ...dress Subnet Mask Default Gateway 2 Click OK 4 5 Host Port Click the Host Port link on the navigation bar to display the Host Connection Configuration screen where you can select the appropriate settings for the Primary Host Port and Alternate Host Port Note Some of the fields change dynamically depending on the Connection Type selected IP Server Connection Type Figure 8 PRO3200 Host Port Configur...

Page 27: ...number through which the host computer can communicate with the PRO3200 board c Select either Allow All or the Authorized IP Address Required option button Allow All as the label suggests allows all IP addresses to communicate with the PRO3200 Select this option for web page browser access If you select the Authorized IP Address Required option also enter in the Authorized IP Addresses fields all ...

Page 28: ...nstallation System Configuration via Web Interface IP Client Connection Type Figure 9 PRO3200 Host Port Configuration Screen with IP Client Connection Note The PRO3200 panel does not currently support an IP Client connection PRO3200 ...

Page 29: ...rop down list select one of the eight 0 to 7 available communication addresses for the PRO3200 board 2 For the Primary Host Port make the following selections a Connection Type From the drop down list select Serial RS232 Select one of the following as appropriate Serial RS232 Serial RS495 Serial Modem b Data Security Select one of the following values from the drop down list None Password no AES P...

Page 30: ...ion System Configuration via Web Interface 4 6 Device Information Click the Device Info link on the navigation bar to display the read only Access Control Device Hardware Information screen Figure 11 PRO3200 Web Server Device HW Info Screen ...

Page 31: ...er Info Screen Adding a User Follow these steps 1 Click New Account to display the new user account screen 2 Enter the following User name a unique character string that identifies the user Level level of privileges the user will have Level 1 grants the user read write privileges to all panel features level 2 grants the user read only privileges to the Notes Network Host Port and Device Info featu...

Page 32: ... down list and click Save Auto Save Timer to save the setting Editing a User To edit a user record click to select the user from the Username column and then click Edit Use the information provided in the previous section Adding a User to edit the record Deleting a User To delete a user record click to select the user from the Username column and then click Delete 4 8 Restore Default Screen Click ...

Page 33: ...9 Apply Setting Screen Click the Apply Setting link on the navigation bar to apply the selected configuration values Figure 14 PRO3200 Web Server Apply Setting Screen Click Apply Reboot to apply all the configured values and reboot the PRO3200 4 10 Log Out Click the Log Out link on the navigation bar to log out of the web server ...

Page 34: ...28 www honeywell com PRO3200 Installation System Configuration via Web Interface ...

Page 35: ... Forest Hill Avenue Oak Creek WI 53154 414 766 1700 414 766 1798 Fax European Office Boblingerstrasse 17 D 71101 Schonaich Germany 49 7031 637 782 49 7031 637 769 Fax www honeywell com Specifications subject to change without notice 2013 Honeywell All rights reserved 800 15494 ...