background image

-- 5 --

462 06 1211 00

3/17/06

Typical Gas Valve Honeywell

SV9501

INLET

OUTLET

Pilot

Adjustment

Pilot

Outlet

Wiring Terminals

Outlet Pressure Tap

Connect manometer here to

check outlet pressure. Must be

adjusted per

Table 1.

Inlet Pressure

Tap (Hidden)

25--22--25

Figure 8

Typical Gas Valve Honeywell

VR8205S

Figure 9

V

T

25--24--98a

HONEYWELL

ON

OFF

Regulator Adjustment

Under Cap

Inlet

Pressure

Tap

1

/

8

NPT

INLET

OUTLET

Outlet

Pressure

Tap

1

/

8

NPT

Typical Honeywell

Regulator Assembly

PRESSURE

REGULATOR

HOUSING

Cap Screw

Black

Silver

Pressure

White

White

Regulator

Adjusting

Screw

Stainless

Spring

Red

Steel

LP

Gas

Natural

Gas

Figure 10

4. Install the pressure regulator adjusting screw. This will set

the manifold pressure close to required setting for normal

operation.

5. Replace the regulator cap screw.
6. Attach gas valve conversion label (found in Honeywell con-

version kit) to gas valve.

Reassembly

Reassemble all parts in reverse order as removed. Attach Natural
Gas Conversion Label next to the unit rating plate. Fill out and
attach the Field conversion Label to the front exterior of the
furnace.

D

Manifold Assembly

-- Be sure to engage the main burner

orifices in the proper openings in the burners.

D

Testing for leaks

-- After reassembly, turn the gas on and

check all joints for gas leaks using a soapy solution. All

leaks must be repaired immediately.

Start--up and Check--out

1. Remove the plug from the Inlet Pressure Tap on gas valve

and install a manometer.

(

See

Figures 7, 8, 9, & 10)

2. Open manual gas line valve to unit. Check for gas leaks and

correct as necessary. Check supply pressure. Refer to

Table 2

for proper supply pressure values. If not within

these limitations DO NOT OPERATE UNIT, contact gas

supplier.

3. Close manual gas line valve to unit, remove manometer and

replace inlet pressure tap plug.

Gas Valve Adjustment

4. With the gas valve knob in the OFF position, remove the

pressure tap plug from the outlet end of the valve, and con-

nect a “U” tube manometer to the pressure port.

(

See

Fig-

ure 7, 8, 9 & 10)

.

5. Turn the gas valve knob to the ON position and restore elec-

trical power to unit. Cycle the main burner on and off several

times to stabilize the pressure regulator diaphragm. This

MUST be done before an accurate pressure reading can be

obtained.

6. With the main burner on, read the pressure gauge. Manifold

pressure should be adjusted to values from

Table 2.

Turn

pressure regulator adjusting screw clockwise to increase or

counterclockwise to decrease manifold pressure. Burner

Input must not exceed nameplate rating.

Refer to Section

“Checking Input Rate”

.

7. Turn gas valve to OFF. Remove the pressure gauge and re-

place the pressure tap plug and pressure regulator cap

screw.

8. With gas valve on, observe furnace through two or more

complete cycles to be sure all controls are operating.

Summary of Contents for PGF3

Page 1: ...ied Model Number Orifice Drill Kit Number Orifice Drill Field Supplied PGC K060F GPCM K060 PGC K080F GPCM K080 PGC K100F GPCM K100 PGC K120F GPCM K120 Natural Gas Orifice Kits and Sizes Table 1 PGF K140F GPFM K140 PGAA PGMD All Sizes PGAD PGME All Sizes PGC K040F GPCM K040 Orifice Drill Field Supplied 0 to 2000 ft Elevation Above Sea Level PGF K080F GPFM K080 Parts List Kit 1173865 Description Par...

Page 2: ...arting installation EXPLOSION HAZARD Failure to follow this warning could result in personal injury death and or property damage If unit is still running allow 2 5 minutes after gas shut off before turning off power Shut Off electric power at unit disconnect and service panel D Disconnect electric power supply to the furnace before starting installation D Check for gas leaks after installation of ...

Page 3: ...erting from Propane Gas to Natural Gas in the state of California NOx baffles must be installed to comply with California law NOx baffles can be ordered from Fast Parts Remove the two 2 screws holding the burner assembly in place Install the correct NOx baffle for the unit if required and replace the Burner Assembly using the original two screws Figure 2 Installing NOx Baffles Figure 2 or Changing...

Page 4: ...erting from Propane Gas to Natural Gas Conversion of Honeywell VR8200 SV9500 SV9501 and VR8204M Gas Valves using Natural Gas Conversion Kit 396222 1 Remove the regulator cap screw and pressure regulator ad justing screw See Figure 10 2 Remove the existing regulator spring from the regulator housing 3 Insert the replacement spring stainless steel contained in this kit into regulator housing Typical...

Page 5: ...a soapy solution All leaks must be repaired immediately Start up and Check out 1 Remove the plug from the Inlet Pressure Tap on gas valve and install a manometer See Figures 7 8 9 10 2 Open manual gas line valve to unit Check for gas leaks and correct as necessary Check supply pressure Refer to Table 2 for proper supply pressure values If not within these limitations DO NOT OPERATE UNIT contact ga...

Page 6: ... complete 1 revolution 2 3600 38 94 7 3 94 7 x 1 94 7 4 94 7 x 1020 96 632 Btu hr For this example the nameplate input is 100 000 Btu hr so only a minor change in manifold pressure is required In no case should the final manifold pressure vary more than 3 water column from the values in Table 2 Never exceed the required input rate Table 3 Table 3 0 2000 2001 3000 3001 4000 4001 5000 5001 6000 6001...

Page 7: ...crease clockwise to decrease 3 Replace the cap on the pilot adjusting screw Pilot Burner HSP 10 11 65 Sensor Tip Proper Flame Adjustment Hot Surface Igniter Figure 11 Main Burner Flame Check Check for the following D Stable and blue flames See Figure 12 Dust may cause orange tips or wisps of yellow but flames MUST NOT have solid yellow tips D Flames extending directly from burner into heat exchang...