Honeywell Perfect Window HR150B Quick Start Manual Download Page 10

HR150B, HR200B PERFECT WINDOW™ FRESH AIR VENTILATION SYSTEMS

68-0285

10

Airflow Balancing

Volume-balanced airflow in the ventilator is required. Volume of 

outside air brought in must equal the volume of air the unit 

exhausts. If airflow is not correctly balanced:

• unit does not operate at its maximum efficiency.

• negative or positive air pressure can occur in the house.

• unit will not defrost properly.

• warranty can be voided.

Excessive positive pressure

 can drive moist indoor air into 

building external walls where it can condense (in cold weather) 

and degrade structural components. Moist indoor air can also 

cause keyholes to freeze.

Excessive negative pressure

 can have several undesirable 

side effects; in some geographic locations, soil gases such as 

methane and radon can be drawn into the home through 

basement/ground contact areas. Excessive negative pressure 

can also cause back drafting of vented combustion equipment 

when adequate combustion air supply is not provided.

Balancing Procedure

Six-inch (150 mm) diameter flow collars connected to inclined 

or digital manometer, or magnehelic, with range of 0 to.25 in. 

(0 to 62.5 Pa) of water are recommended for accurate airflow 

measurements. To avoid airflow turbulence and incorrect 

readings, flow stations should be located at a distant point of at 

least five duct diameters; for example, 6 in. (150 mm) duct 

requires five diameters x 6 in. (150 mm) = 30 in. (76 cm) from 

nearest valve or flow restriction. This requirement applies to 

both stale air to exchanger duct and fresh air to house duct.

Before balancing, make sure:

• all sealing of the ductwork system is completed.

• all of the ventilator system components are in place and 

functioning properly.

• balancing dampers are fully open.

• unit is on High speed.

• airflows in branch lines to specific areas of house are 

adjusted before balancing the unit. (A smoke pencil used at 

the grilles is a good indicator of relative airflow for each 

branch line.)

After taking readings in stale air and fresh air ducts, duct with 

lower cfm (L/s) velocity reading should remain as is, while duct 

with higher reading should be dampered back to match lower 

reading. See Fig. 10.

Return unit to appropriate fan speed for normal operation.

STARTUP AND CHECKOUT

After installation is complete, check to be sure system is 

working correctly. Turn speed-selection knob to desired 

position to set continuous background ventilation rate. Activate 

two-wire control devices in system to make sure devices switch 

ventilator to High speed. For operating instructions, see 

instructions packed with digital fan timer. Leave instructions 

with homeowner.

Fig. 10. Balancing airflow.

SERVICE 

CAUTION

Electrical shock hazard. 

Can cause personal injury or equipment damage.

Disconnect power to unit before starting maintenance.

For maximum efficiency, the Fresh Air Ventilation System must 

be maintained on a regular basis. Honeywell recom-mends 

checking and cleaning at least twice a year, preferably at the 

beginning of each heating and cooling season.

Cleaning Filters and Core

Remove the room air filter, fresh air filter and heat transfer core 

from the ventilator as a unit. 

1.

Open ventilator door by loosening draw latches on top of 

unit and swinging door open. For easier access, remove 

door by moving it right to disengage hinges.

2.

Carefully grip ends of core, (be careful not to damage 

aluminum fins); then pull evenly outward. Core fits tightly, 

but slides out of channels.

3.

Once core is removed, filters can be removed by remov-

ing clips holding them in place. Note clip installation for 

reassembly.

4.

Wash the filters and the core in warm soapy water. Do 

not wash them in a dishwasher.

5.

Place the clean filter (wet or dry) over the core and 

secure it in place with the clips.

6.

Reinstall core by sliding it into the four corner channels. 

(Water cannot damage gasket and label on core ends, 

so it is not necessary to remove them from the core.)

Inspecting Exterior Hoods

Inspect exterior hoods at least monthly. Be sure exhaust and 

fresh air supply hoods are not blocked or restricted by leaves, 

grass or snow. In winter, be sure snow does not block hoods 

and frost does not accumulate on wire mesh bird screen.

IMPORTANT

Blocked hoods can cause house/building pressure 

change that can lead to possible combustion product 

spillage from heating appliances.

PUSH AND TURN WITH 
SLOTTED SCREWDRIVER.
DAMPER AUTOMATICALLY
LOCKS WHEN PRESSURE
IS RELEASED.

M13462

Summary of Contents for Perfect Window HR150B

Page 1: ...es ventilation that helps contractors meet ASHRAE 62 89 4 speed fan control Automatic economical built in frost control for operation to design temperatures of 40 F 40 C Easy to clean aluminum cross flow core Includes vibration isolation hardware and duct collars Insulated cabinet made of rugged steel Permanent washable prefilters Quiet operation Digital fan timer option on all models Contents App...

Page 2: ...not include normal manufacturing tolerances Therefore this unit might not exactly match the listed specifica tions Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Color White Electrical Ratings Power Rating 220 Vac 50 Hz Consumption 0 8A at maximum speed Mounting Mount in condit...

Page 3: ...gh the ventilator to the outdoors Heat is transferred from one airstream to the other as the air passes through the opposite sides of the heat transfer core See Fig 2 Fig 2 Duct connections and airflow 14 3 4 375 33 5 8 854 19 483 SERVICE CLEARANCE 25 635 19 483 HR CONTROLS ALL DUCT CONNECTIONS ARE 6 150 DRAIN SPOUTS MOUNTING STRAP 4 M22700 WEIGHT 70 lb 32 kg SHIPPING WEIGHT 72 lb 33 kg Fresh Air ...

Page 4: ...l connections to and from the ventilator Separate outside intake and exhaust vents by at least 6 ft 2m NOTES Do not locate the fresh air vent where it blows directly onto occupants or the thermostat Do not locate the fresh air intake close to known sources of pollutants such as automobile exhaust a dryer vent or chimney smoke Ducting the supply outlet and or the exhaust inlet of the ventilator to ...

Page 5: ...ECTRICALLY LOW VOLTAGE USING OPTIONAL 32003248 001 BLOWER INTERFACE KIT NO SEPARATION REQUIREMENTS ARE NECESSARY BETWEEN DIRECT CONNECTION POINT AND FURNACE WEATHER HOOD ARRANGEMENT IS FOR DRAWING ONLY 6 FT 2m MINIMUM SEPARATION REQUIRED 18 IN 0 46m ABOVE GRADE MINIMUM 40 IN 1m MINIMUM COLD AIR RETURN FORCED AIR FURNACE COMBUSTION OR ELECTRIC M22723 RETURN AIR OUTDOORS NOTES 1 2 3 4 FURNACE BLOWER...

Page 6: ... can also be high levels of formaldehyde and other chemicals that were used in the building materials Running the ventilation system on high speed provides optimum indoor air pollutant reduction High speed also provides maximum moisture removal when the outside air contains less moisture than the inside air Typically during cold weather conditions Operating Damper Frost Control Some models have an...

Page 7: ...ts is recommended NOTE Removing door and core reduces the weight of the ventilator making it easier to lift into place Floor Mounting The mounting hardware included is not needed for floor mounting 1 Use 2 x 4 in wood pieces to build a frame to support the ventilator along the bottom edge The frame must hold the ventilator at least 10 in up from the floor to allow clearance for the drain line 2 Se...

Page 8: ...nnect the hot line to the interlock switch See Fig 9 To confirm correct polarity use voltmeter or test lamp to verify there is no power after the switch when the door is open Check between that point and ground on cabinet This process must be used because occasionally some dwellings are incorrectly wired Connect line voltage to the ventilator according to Fig 9 Honeywell recommends that a licensed...

Page 9: ...LTAGE M22720 SEE DEFROST DETAIL 1 FIELD INSTALLED HIGH VOLTAGE FIELD INSTALLED 12V LOW VOLTAGE RED 1 INSTALL 1 4 in FEMALE QUICK DISCONNECT TERMINAL TO HOT WIRE AND ASSEMBLE TO INTERLOCK SWITCH INSTALL 1 4 in FEMALE QUICK DISCONNECT TERMINAL TO NEUTRAL WIRE AND ASSEMBLE TO T11 TERMINAL INSTALL RING TERMINAL TO THE GROUND LEAD AND ASSEMBLE SECURELY TO THREADED STUD IN WIRING COMPARTMENT 2 3 2 T1 T2...

Page 10: ...e dampered back to match lower reading See Fig 10 Return unit to appropriate fan speed for normal operation STARTUP AND CHECKOUT After installation is complete check to be sure system is working correctly Turn speed selection knob to desired position to set continuous background ventilation rate Activate two wire control devices in system to make sure devices switch ventilator to High speed For op...

Page 11: ...gh conden sation appears on windows Dehumidistat is set too high Set dehumidistat lower Undersized ventilator hot tub indoor pool etc Cover pools and hot tubs when not in use Lifestyle of occupants Avoid hanging clothes to dry storing wood and venting clothes dryer inside Consider moving wood outside Moisture coming into home from crawl space not vented or heated Vent crawl space and place vapor b...

Page 12: ...ly installed Make sure water drains correctly from pan Table 3 Troubleshooting Guide Continued Symptom Cause Solution Item Number Fig 11 Description 1 Heat Transfer Core Aluminum with Plastic Frame 2 Blower Housing Kit 3 Condensate Pan Left or Right 4 Foam Prefilter Set of 2 5 Clip for Foam Prefilter 6 Drain Spout 7 Duct Collar Red 8 Duct Collar Blue 9 H Channel 13 1 4 in 10 Door Hinge Complete 11...

Page 13: ...HR150B HR200B PERFECT WINDOW FRESH AIR VENTILATION SYSTEMS 13 68 0285 Fig 11 Exploded view M22702 1 16 3 5 6 7 8 15 14 9 10 11 12 13 17 18 4 5 2 ...

Page 14: ...68 0285 14 ...

Page 15: ...15 68 0285 ...

Page 16: ...International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 68 0285 G H 02 05 ...

Reviews: