background image

D - 1

126247-04

PEHA_M_960-3_PSB (Rev05_130319)

GB - 1

PEHA Elektro GmbH & Co. KG

Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: [email protected] • Internet: www.peha.de

 

DescrIPTIOn

The PHC switching box has 8 inputs (Input 8-15) that can be switched against ground 

(0V) using push buttons. The inputs can be used to control the outputs of the PHC 

output modules or of the PHC system boxes. The 6 outputs (Out 0-5) of the PHC 

switching box are used to switch various consumers, such as light bulbs, HV halogen 

lamps, electronic ballasts and inductive loads. They are supplied by a 3 pole through 

line carrying with a voltage of 230 V~/50-60 Hz.

notes:

–  Detailed expert knowledge for programming a PHC system

  are required.

–  The PHC-functions for the PHC system are to be programmed

  with the PHC system software (see PHC manual).

–  Read through the operating instructions carefully before putting

  the device into service.

sAFeTy

cAuTIOn! Danger of electrical shock! 

The housing contains current-carrying components. contact  can lead 

to personal injury! All work on the mains network and the device may 

only be done by an authorised electrician.

•  Disconnect power supply from the device prior to performing any work on it.

•  Secure the device against being powered on again.

•  Check that the device is powered off.

•  Close the housing securely before applying power.

The following must be observed:

•  Prevailing statutes, standards and regulations.

•  State-of-the-art technology at the time of installation.

•  The PHC manual and operating instructions of the PHC modules.

•  Operating instructions can only cite general stipulations. These are to

  be viewed in the context of a specific system.

The following systems may not be switched:

•  Safety switches such as EMERGENCY OFF

•  Emergency power supplies

•  Fire alarm systems

•  Emergency lighting systems

This  device  is  only  intended  to  be  used  for  its  stated  application.  Unauthorised 

conversions, modifications or changes are not permissible! 

This device may not be used in conjunction with other devices whose operation could 

present a hazard to persons, animals or property.

TechnIcAL sPecIFIcATIOns

general data

Power supply

230 VAC /50-60 Hz (L, N, PE)

Maximal load of the system box

4000 W (250 VAC / 16 A)

Own consumption

10-60 mA

relay service life

ca. 40.000 applications at max. load

Protection

Circuit breaker (max. 16 A)

coding

8 pole dip switch for module address

Ambient temperature

0 to + 50 °C

storage temperature 

– 40 to + 85 °C

connections

8 Push button inputs (INPUT 8-15)

  3 switches max. allowed!

1 PHC bus input (BUS-IN)

6 Outputs (OUT 0-5)

2 PHC bus output (BUS-OUT)

Test specifications

EN 60669-2-1

certifications

CE ; KEMA/KEUR

Protection type

IP20

Dimensions

L 180 mm x W 205 mm x H 48 mm

Load specifications per output (Out 0-5)

Incandescent lamps

 (Ω)

2300 W (9 A)

hV-halogen lamps

1250 W (5 A)

Inductive

600 VA (2,4 A)

electronic ballast

5 items

note: 

To calculate the current consumption for the power supply, you should assume 

a consumption of 60 mA. The power consumption increases to 150 mA for about 1s 

when switching on the relays.

InsTALLATIOn

Installation and commissioning may only be done by an authorised electrician. Mains 

power to electrical equipment must be switched off during installation. Applicable 

laws and standards of the country in which the device is operated must be observed! 
The PHC switching box can be mounted in any location using the included screws and 

plugs (e.g. onto a smooth wall or inserted ceiling ). The base of the PHC switching 

box is used as a template for the drill holes.
•  Carry out installation and switch on electrical system (supply line).

•  The input and output functions of the PHC switching box have to be programmed 

  in the PHC software (see PHC manual).

•  Carry out program transfer with PHC software.

DATA cOnnecTIOn

Usually, a JY(ST)Y 2x 2x 0,8 mm Ø cable is used as a data line. The cable is connected 

to the 4 pole connectors (included). The data

 connection

 to the PHC switching box 

is carried out at the „BUS-IN“ input. A data connection for further PHC system boxes 

or PHC modules is carried out at the „BUS-OUT“ output.

notes:

– Switch off power supply before connecting or disconnecting bus line.

– The module can be positioned anywhere in the data line.

– The module is supplied with voltage by the bus line.

cODIng sWITch

The coding switch sets the module address. The setting is presented in the 

PHC software under menu item „

Components

 

 

Modules

“.

notes:

– Do not set the same module addresses for PHC switching boxes.

– Before setting the module address, the PHC module needs to be

  switched off and it must be secured against electrical discharge.

Turn-On cOnDITIOns

You can select the switching states of the outputs (OFF, Memory and ON) on voltage 

switch-on or recovery in the PHC software under the menu item „

Components 

 

Turn-on conditions

“:

The  turn-on  conditions  are  pre-set  to  „OFF“. The  „Memory“  switching  condition  is 

selected, e.g. , to get the previous switching state for the switching box from the control 

module after a voltage interruption (> 50 ms).

TrOubLeshOOTIng & reMeDIes (eLecTrIcIAn OnLy)

new system or existing system

•  Check circuit breaker and power supply

•  Check connected electrical loads and connection cables

•  Check module address (coding switch).

•  Check PHC programming and transfer again (see PHC manual).

contact

Telephone: ...................+49 (0)2351 185-0

Fax:..............................+49 (0)2351 27666

Internet: .......................www.peha.de

E-mail: [email protected]

WArrAnTy cOnDITIOns

These operating instructions are an integral part of both the device and our terms of 

warranty. They must be handed over to the user. The technical design of the appliance 

is  subject  to  change  without  prior  notification. 

PEHA

 products are manufactured 

and quality-checked with the latest technology according to applicable national and 

international regulations. Nevertheless, if a product should exhibit a defect, 

PEHA

 

warrants to make remedy as follows (regardless of any claims against the dealer to 

which the end user may be entitled as a result of the sales transaction):

In the event of a justified and properly established claim, 

PEHA

 shall exercise its 

prerogative to either repair or replace the defective device. Further claims or liability 

for consequential damage are explicitly excluded. A justifiable deficiency is deemed to 

exist if the device exhibits a structural, manufacturing, or material defect that makes it 

unusable or substantially impairs its utility at the time it is turned over to the end user. 

The warranty does not apply to natural wear, improper usage, incorrect connection, 

device tampering or the effects of external influences. The warranty period is 24 months 

from the date of purchase by the end user from a dealer and ends not later than 36 

months after the device’s date of manufacture. German law shall be applicable for the 

settlement of warranty claims.

DIsPOsAL OF The DeVIce

Do not dispose of old devices in the household waste! The device must be 

disposed of in compliance with the laws and standards of the country in which it 

is operated! The device contains electrical components that must be disposed of 

as electronics waste. The enclosure is made from recyclable plastic.

InsTALLATIOn AnD OPerATIng InsTrucTIOn
Phc switching system box

960/3 Psb

GB

Vorsicht! Erhöhte
Strahlung

Vorsicht! Kontamination

Vorsicht! Kontamination

Vorsicht, Gefahr durch
Abquetschen

Vorsicht, Gefahr durch
Abschneiden

Vorsicht, Gefahr durch
Abstürzen

Vorsicht, Gefahr durch
ätzende Stoffe

Vorsicht, Gefahr durch
elektrischen Strom

Vorsicht, Gefahr durch
elektrischen Strom

Vorsicht, Gefahr durch
elektromagnetische
Strahlung

Vorsicht, Gefahr durch
explosionsgefährliche
Stoffe

Vorsicht, Gefahr durch
feuergefährliche Stoffe

Vorsicht, Gefahr durch
giftige Stoffe

Vorsicht, Gefahr durch
heiße Oberfläche

Vorsicht, Gefahr durch
Laserstrahlung

Vorsicht, Gefahr durch
Radioaktivität

Vorsicht, Gefahr durch
Rutschen

Vorsicht, Gefahr durch
Stolpern

Vorsicht, Gefahr durch
Verwickeln

Vorsicht, Warnung vor
einer Gefahrstelle

Vorsichtig verschieben!
- veraltet -

Während der
Schweißarbeiten,
Arbeitsstelle beobachten

Wandbrände nicht von
oben löschen

Wandbrände von unten
nach oben löschen

Wandhydrant

Wandhydrant (2.
Vorschlag)

Wandhydrant, mit Angabe
des Anschlusses

Wareneingang -
Freigegeben

Wareneingang - Gesperrt

Wärmeabzugseinrichtung

Summary of Contents for PEHA PHC

Page 1: ...en durchgeführt werden Bei der Installation an das Versorgungs netz ist die elektrische Anlage spannungsfrei zu schalten Es sind die geltenden Gesetze und Normen des Landes einzuhalten in dem das Gerät betrieben wird Die PHC Schaltbox kann dezentral mit den mitgelieferten Schrauben und Dübeln montiert werden z B auf eine ebene Wand oder in eine Zwischendecke Das Unterteil der PHC Schaltbox wird al...

Page 2: ...en Funktionsumfang der PHC Systembox zu gewährleisten muss die 230 VAC Versorgungsspannung angeschlossen sein out 0 L N out 1 L N out 2 L N µ µ µ 16A 250V Address switch 3 out 4 N L out 3 N L OUTPUT250V N L out 5 N L µ µ µ 3 INPUT250V L N 3 INPUT max 16A 250V OUTPUT max 16A 250V INPUT 8 11 8 9 10 11 B A 24V BUS IN A B 24V BUS OUT A B 24V BUS OUT INPUT 12 15 12 13 14 15 ID M 2300W 600VA 1250W 2AX M...

Page 3: ...g box is carried out at the BUS IN input A data connection for further PHC system boxes or PHC modules is carried out at the BUS OUT output Notes Switch off power supply before connecting or disconnecting bus line The module can be positioned anywhere in the data line The module is supplied with voltage by the bus line Coding switch The coding switch sets the module address The setting is presente...

Page 4: ... BUS OUT A B 24V BUS OUT INPUT 12 15 12 13 14 15 ID M 2300W 600VA 1250W 2AX Max output per chanel 250V Art Nr 960 3 PSB System Box 1 2 3 4 5 7 8 6 out 0 L N out 1 L N out 2 L N µ µ µ 16A 250V Address switch 3 out 4 N L out 3 N L OUTPUT250V N L out 5 N L µ µ µ 3 INPUT250V L N 3 INPUT max 16A 250V OUTPUT max 16A 250V INPUT 8 11 8 9 10 11 B A 24V BUS IN A B 24V BUS OUT A B 24V BUS OUT INPUT 12 15 12 ...

Page 5: ...rd worden Bij de installatie aan het stroomverzorgingsnet dient u de installatie spanningsloos te schakelen Ook dient u de geldende wetten normen en installatievoorschriften te handhaven welke in uw land gelden De PHC schakelbox kan met de bijgeleverde schroeven en pluggen decentraal worden opgeschroefd bijv tegen een vlakke wand of in een verlaagd plafond Het onderstuk van de PHC schakelbox wordt...

Page 6: ...10 11 B A 24V BUS IN A B 24V BUS OUT A B 24V BUS OUT INPUT 12 15 12 13 14 15 ID M 2300W 600VA 1250W 2AX Max output per chanel 250V Art Nr 960 3 PSB System Box 1 2 3 4 5 7 8 6 out 0 L N out 1 L N out 2 L N µ µ µ 16A 250V Address switch 3 out 4 N L out 3 N L OUTPUT250V N L out 5 N L µ µ µ 3 INPUT250V L N 3 INPUT max 16A 250V OUTPUT max 16A 250V INPUT 8 11 8 9 10 11 B A 24V BUS IN A B 24V BUS OUT A B...