GB - 2
PEHA_M_Installation_952JRM (Rev01-130308)
FunCTIon TabLe
Input assignment
Input
(I=Input)
Input function
output function
output
(O=Output)
output assignment / room
I0
Button local UP
Motor M0 UP
O1
I1
Button local DOWN
Motor M0 DOWN
O0
I2
Button local UP
Motor M1 UP
O3
I3
Button local DOWN
Motor M1 DOWN
O2
I4
Button local UP
Motor M2 UP
O5
I5
Button local DOWN
Motor M2 DOWN
O4
I6
Button local UP
Motor M3 UP
O7
I7
Button local DOWN
Motor M3 DOWN
O6
I8
Button local UP
Motor M4 UP
O9
I9
Button local DOWN
Motor M4 DOWN
O8
I10
Button local UP
Motor M5 UP
O11
I11
Button local DOWN
Motor M5 DOWN
O10
I12
Button local UP
Motor M6 UP
O13
I13
Button local DOWN
Motor M6 DOWN
O12
I14
Button local UP
Motor M7 UP
O15
I15
Button local DOWN
Motor M7 DOWN
O14
I16
Button local UP
Motor M8 UP
O17
I17
Button local DOWN
Motor M8 DOWN
O16
I18
Button local UP
Motor M9 UP
O19
I19
Button local DOWN
Motor M9 DOWN
O18
I20
Button local UP
Motor M10 UP
O21
I21
Button local DOWN
Motor M10 DOWN
O20
I22
Button local UP
Motor M11 UP
O23
I23
Button local DOWN
Motor M11 DOWN
O22
I24
Button central UP
Central UP
o
auF
I25
Button central DOWN
Central DOWN
o
AB
I26
Button group 0 UP
Group 0 UP
o
g0
I27
Button group 0 DOWN
Group 0 DOWN
I28
Button group 1 UP
Group 1 UP
o
g1
I29
Button group 1 DOWN
Group 1 DOWN
I30
(1)
Button group 2 UP
Group 2 UP
o
g2
I31
(1)
Button group 2 DOWN
Group 2 DOWN
I30
(2)
Sun sensor S2 On/Off
Motor DOWN
/ UP
(Sun sensor S2 / S3)
o
ss
I31
(2)
Sun sensor S3 On/Off
I32
(3)
Automatic switch
On/Off
Automatic (timer, Sun sensor,
Twilight sensor)
o
u
,
o
ss
,
o
ds
I33
Twilight sensor
On/Off
Motor DOWN
/ UP
(Twilight sensor)
o
ds
I34
Sun sensor S1
On/Off
Motor DOWN
/ UP
(Sun sensor S1)
o
ss
I35
Wind-/ rain sensor
On/Off
Motor UP
(Wind-/ rain sensor)
o
Ws
(1)
Standard function of Group 2 (Group 2 mode “Standard”)
(2)
Sun sensor S2/S3 when Group 2 set to “Sensors” mode (see CONFIGURING GROUP 2 instructions).
(3)
Auto mode (timer, sun sensor, twilight sensor) for all assigned outputs (see AUTO MODE instructions).
o
auF
All outputs UP
o
u
Outputs with programmed timers
o
AB
All outputs DOWN
o
ds
Outputs with assigned twilight sensor
o
g0
Group 0 outputs
o
ss
Outputs with assigned sun sensor
o
g1
Group 1 outputs
o
Ws
Outputs with assigned wind-/ rain sensor
o
g2
Group 2 outputs
ConneCTIng sensoRs
Sensors connected to the JRM can be assigned singly to every output
(motor) (see AUTO MODE and SENSORS instructions). The outputs (mo-
tors) can therefore be controlled depending on the daylight and weather.
WInD sensoR 940 Ws
The 940 WS wind sensor with the 940 WS-AE plotting unit is used to
protect electric motor operated blinds and awnings in combination with
the JRM Module. The plotting unit requires an operating voltage of 24V
DC. Output 15 of the plotting unit can be connected to the I35 24V input
of the JRM Module:
A2
18
15
16
S2
S1
B2
B1
EIN
STÖRUNG
WINDSTÄRKE
9
10
3
4
5
6
7
8
18
15
S1
S2
16
24V
0V
940 WS-AE
0V
Compact 952 JRM
Input I35
Compact 952 JRM
sensor connection 24V
Attention!
The operating instructions for the wind sensor must be observed!
RaIn sensoR 940 Rs
The 940 RS rain sensor has a relay contact (COM u. N. O) to operate an
input signal up to a maximum 50V DC / 0.5A. The device is provided with
a heater for faster drying and snow recognition. The rain sensor requires
an operating voltage of 24V DC and is particularly suitable for connecting
to the JRM.
You can connect the rain sensor parallel to a wind sensor (e.g. 940 WS)
using the I35 24V input:
N.O
COM
N.C
VCC
GND
24V
0V
940 RS
Compact 952 JRM
sensor connection 24V
0V
Input I35
Compact 952 JRM
Attention!
The operating instructions for the rain sensor must be observed!
TWILIghT / sun sensoR 941 LuX
The 941 LUX twilight/sun sensor consists of the 941 LUX-LF light sensor
and the 941 LUX-REG evaluation unit.
A10
A11
twilight sensor
Switching off threshold
Hysterisis
Switching on threshold
B
rightness
941 LuX-Reg
The twilight sensor is connected to the
24V input I33 on the JRM.
A10
A11
sonnensensor
Ausschaltschwelle
Hysterese
Einschaltschwelle
B
eleuchtungs-
stärk
e
941 LuX-LF
The S1 sun sensor is connected to the 24V input I34 on the JRM. When
Group 2 has been set to “Sensors”, a sun sensor (S2/S3) can optionally
be connected to the inputs I30 and I31.
This allows the level of brightness
(sun from the east, south and west) to be captured correctly.
941 LUX-REG
S2
S1
S3
B2
B1
A10
A11
0V
24V
Light sensor
941 LUX-LF
Parallel connection of
several 941 LUX-REG
Compact 952 JRM
sensor connection 24V
952 JRM
Input I 34
952 JRM
Input I 33
Attention!
The operating instructions for the twilight/sun sensor
must be observed!