Honeywell P7650A Series Installation Instructions Manual Download Page 3

P7650A/B/U

3

31-00138—02

INSTALLATION, WIRING & CONFIGURATION

1.

Plan the installation. Panel or duct mount?  

Fig. 2. 

NOTE:

Velocity measurement, 

shown below,

 requires the use of a pressure-velocity pick up tube, part P7650L6, 

P7650L8, P7650L10, P7650L12, or P7650L14. Length is the number after L in inches, so P7650L6 is 6 inch, 
etc. See form 31-00149 for details on installing and configuring the P7650L velocity pick up probes. 

Fig. 3. 

2.

For duct mount applications, thread the probe into 
the back of the device housing, as shown in the 
dimensional drawing.

3.

Configure the internal tubing for the selected instal-
lation method as described below.

Duct mount tubing configuration:
a. Connect the right-side tube to the rear brass 

barb marked as “-” on the underside of the device 
housing.

b. Connect the left-side tube to the probe in the 

back of the device housing.

Panel mount tubing configuration:
a. Connect the right-side tube to the rear brass 

barb marked as “-” on the underside of the device 
housing.

b. Connect the left-side tube to the front brass barb 

marked as “+” on the underside of the device 
housing.

Fig. 4. 

4.

Mount the transducer (see the screw hole diagram 
below).   

Fig. 5. 

AIR FLOW

FILTER

LOW

HIGH

STATIC PRESSURE

DIFFERENTIAL PRESSURE

PANEL

INSTALLATIONS

DUCT

INSTALLATIONS

M37265

AIR FLOW

AIR FLOW

AIR FLOW

VELOCITY WITH P7650L PROBE

AIR FL

OW

M37453

TUBING FOR DUCT MOUNT

TUBING FOR PANEL MOUNT

M37267

2-19/64 (59)

CTR-CTR

3-19/64 (83)

CTR-CTR

2-1/2 (62)

TO P/U

TUBE

1-13/32

(35)

TO P/U

TUBE

1/2

(13)

3-13/64

(81)

IN. (MM)

M37268

Summary of Contents for P7650A Series

Page 1: ...ller is responsible for conformance to all applicable codes If this product is used in a manner not specified by the manufacturer the protection provided by the product may be impaired No responsibility is assumed by the manufacturer for any consequences arising out of the use of this material PRODUCT IDENTIFICATION New Part Number Mounting Selectable w c Pressure Range Uni or Bi Directional Veloc...

Page 2: ...asured value Temperature Effect 1 250 Pa models 0 05 C 10 2 5 kPa models 0 01 C Relative to 25 C 0 to 50 C 32 to 122 F Zero Drift 1 year 1 250 Pa models 2 0 max 10 2 5 kPa models 0 5 max Zero Adjust Pushbutton auto zero and digital input 2 pos terminal block Operating Environment 0 to 60 C 32 to 140 F Altitude of Operation 0 to 3000 m Pollution Degree 2 Humidity Range 100 RH non condensing Mountin...

Page 3: ...g configuration a Connect the right side tube to the rear brass barb marked as on the underside of the device housing b Connect the left side tube to the probe in the back of the device housing Panel mount tubing configuration a Connect the right side tube to the rear brass barb marked as on the underside of the device housing b Connect the left side tube to the front brass barb marked as on the u...

Page 4: ...witch 2 Mode ON Velocity OFF Pressure DIP Switch 3 Direction ON Unidirectional OFF Bidirectional DIP Switch 4 Response ON Slow OFF Fast DIP Switch 5 Output ON 4 20 mA OFF Voltage DIP Switch 6 Volt Scale ON 0 5 Vdc OFF 0 10 Vdc DIP Switch 7 Unused DIP Switch 8 Unused 1 2 INCH NPT FEMALE THREADED COUPLER M37460 Scale Mode Direction Response ON Pascal MPS Velocity Uni Slow OFF In WC FPM Pressure Bi F...

Page 5: ...st accuracy after an initial warm up period During the first few minutes of operation readings at zero pressure and the lowest pressure ranges appear erroneous Following this initial warm up period the P7650A B U device maintains its specified accuracy and stability The LCD momentarily indicates range SET when a selection is made Pressure is normally indicated on the display Units are in inches wa...

Page 6: ...rference that may cause undesired operation IC REGULATIONS RSS GEN This device complies with Industry Canada s license exempt RSSs Operation is subject to the following two conditions 1 This device may not cause interference and 2 This device must accept any interference including interference that may cause undesired operation of the device Le présent appareil est conforme aux CNR d Industrie Can...

Page 7: ...P7650A B U 7 31 00138 02 ...

Page 8: ...05 18 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the literature ...

Reviews: