5. Set Egress (20*).
Setting egress allows the connection of a push button mounted inside a building to grant passage
when exiting. When set, this option will disable the external Night Lock control which uses the
same I/O 2 input. Egress is low active, i.e. access is granted when I/O 2 is connected to GND for a
short while.
The default option is 20*0*, meaning that this function is disabled. If you want to use the default
value, skip this step and proceed with the next.
To use a setting other than the default one, perform the steps indicated in Figure 7.
1. Enter Program mode by
presenting the Installer
Remote Programmer.
2. Enter Egress option.
3. Normal operation of the
NS1 is resumed.
Figure 7
Setting Egress Option
6. Set NS1 from Installer level to User level.
To prevent tamper alarms, make sure the NS1 cover is in place. If for any reason you
need to go back to the installer level, just present the Installer Remote Programmer in
the RF field of the NS1 and enter 0*1*.
To set the User level, perform the steps indicated in Figure 8.
1. Enter Program mode by
presenting the Installer
Remote Programmer.
2. Press 0*0*.
3. The NS1 goes to User
Sleep mode. Switch the
power OFF.
Figure 8
Set User Level