COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Notifier system control panel.  

COMPONENTS

Following are descriptions of the XP10-M mounting frameworks.  There are 
two mounting options for   XP10-M modules:

•  Up to six XP10-M modules can be installed on a CHS-6 in a CAB-3 Series 

cabinet, CAB-4 Series cabinet or BB-25 cabinet.

•  One or two XP10-M modules can be installed in a BB-XP cabinet.

Chassis 

The CHS-6 chassis is used to mount XP10-M modules in a BB-25, CAB-3 or 
CAB-4 Series cabinet. It accommodates up to six XP10-M modules in a single 
cabinet row three modules wide and two modules deep.

FIGURE 1. CHS-6 CHASSIS:

The BB-XP cabinet has a built-in chassis that will accommodate one or two 
XP10-M modules.

FIGURE 2. BB-XP CABINET:

N500-77-00  1 I56-1803-010 

XP10-M Ten Input Monitor Module

SPECIFICATIONS

Normal Operating Voltage: 

15-32 VDC

Stand-By Current: 

3.75 mA @ 24V

Alarm Current: 

55 mA (assumes all ten LEDs solid on)

Temperature Range: 

32°F to 120°F (0°C to 49°C) 

 

Humidity: 

10 to 85% Noncondensing 

 

Dimensions: 

6.8˝H x 5.8˝W x 1.25˝D 

Accessories: 

CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-3 Series Cabinet; CAB-4 Series Cabinet 

Wire Gauge: 

12-18 AWG

Maximum SLC Wiring Resistance: 

40 Ohms

Maximum IDC Wiring Resistance: 

1500 Ohms

Maximum IDC Voltage: 

10.2 VDC

Maximum IDC Current: 

240µA (each circuit)

C0202-00

C0236-01

BEFORE INSTALLING

If the modules will be installed in an existing operational system, inform the 
operator and local authority that the system will be temporarily out of service. 
Disconnect the power to the control panel before installing the modules. This 
system contains static sensitive components. Always ground yourself with a 
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably 
grounded.

NOTICE: 

This manual should be left with the owner/user of this equipment.  

GENERAL DESCRIPTION

The XP10-M Ten Input Monitor Module is intended for use in an intelligent 
alarm system. Each monitor module is intended to interface between a control 
panel and normally open contact devices, such as pull stations. A common 
SLC input is used for all modules, and the initiating device loops share a 
common supervisory supply and ground. Otherwise, each monitor operates 
independently from the others. Each module has its own unique address.

A pair of rotary code switches is used to set the address of the first module 
from 01 to 150. The remaining modules are automatically assigned to the next 
nine higher addresses. Provisions are included for disabling a maximum of 
two unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled green LED indicators. The panel can cause the 
LEDs to blink, latch on, or latch off.

Included: 

 

(6) 1 x 4 Terminal Blocks    (2) 1

1

/

4

 (32mm) Stand offs

 

  

(4) Machine Screws     (3) Shunts      (10) 47k Ohm 
 

 

    End of Line Resistors

(2) Nuts

Shipped on Board:

(1) Shunt in Class A/B position

     (Shipped in Class B position, remove shunt for Class A)

I56-180

3-0
10

INSTALLATION AND MAINTENANCE INSTRUCTIONS

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

0 1

2 3 4 5 6

78

9

0

78

65

4

3

21

910

11

1213

14

15

BA

SE

 AD

DR

ES

S

AD

DR

ES

S

DIS

AB

LE

NO

NE

ON

E

TW

O

THR

EE

0 1

2 3 4 5 6

78

9

0

78

65

4

3

21

910

11

1213

14

15

BA

SE

 ADDRE
SS

ADD

RE

SS

DI

SA

BL

E

NONE

ON

E

TW

O

THR

EE

C0234-00

MOUNT WITH

SELF-THREADING SCREWS 

TO BACK OF CABINET

Summary of Contents for NOTIFIER XP10-M

Page 1: ...ules This system contains static sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re moved from the body The housing cabinet should be metallic and suitably grounded NOTICE This manual should be left with the owner user of this equipment GENERAL DESCRIPTION The XP10 M Ten Input Monitor Module is intended for use in an int...

Page 2: ... will be installed in the chassis position in front of it Refer to Figures 6a and 6b for method two All necessary screws and standoffs are supplied with the modules FIGURE 5 INSTALLATION OF REAR MODULE ONLY METHOD ONE Step 1 Insert the bottom of the XP10 M module down into a rear slot on the chassis Step 2 Carefully swing the upper edge of the board back towards the back of the chassis until it to...

Page 3: ...at may cause undesired operation NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordanc...

Page 4: ...lation instructions NOTE Any number of UL listed contact closure devices may be used DO NOT mix fire alarm initiating and supervisory devices on the same initiating device circuit Install contact closure devices per manufacturer s installation instructions BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS IDC ADDRESS 0 1 2 3 4 5 6 7 8 9 IDC ADDRESS IDC ADDRESS IDC ADDRESS IDC ADDRESS SLC FROM PANEL OR...

Reviews: