VEA Product Guide —

 P/N LS10215-000NF-E:A 07/24/2018

References

Introduction

The VEA-040-Axx-NTF models have implemented an interface to the FACP over the SLC loop. An interface module mounted to the inside of the 
VEA door provides the SLC interface for the detector. 

The SLC detector does not have VESDAnet capability as the networking is provided by the SLC loop. 

Specifications specific to SLC detectors

• Power drawn from the SLC loop: 30mA
• Event reporting is achieved via event logs

NOTE:

This model doesn’t support the expansion STAX

Ordering Information

VESDA-E VEA-040-Axx Detector capable of interfacing to NOTIFIER panels: 

• VEA-040-A00-NTF: NOTIFIER Intelligent VESDA-E VEA-40 point with LEDs
• VEA-040-A10-NTF: NOTIFIER Intelligent VESDA-E VEA-40 point with 3.5" Display

Compatibility with FACP

VEA-040-Axx-NTF is compatible with the following NOTIFIER FACPs:

• NFS2-3030
• NFS2-640
• NFS-320

Installation

VEA is an addressable Aspirating Smoke Detector (ASD) with 40 addressable microbore tubes. VEA is configured as an ASD in a 5-address space 
providing the Alert and Action pre-alarms; and the Fire-1 and Fire-2 alarm conditions. Each of the 40 microbore tube air sampling points are to be 
configured as a photo detector on the SLC loop. Each VEA will occupy 45 consecutive addresses on the SLC loop.

Document Id

Description

27034

VESDA-E VEA-040-A00 Product Guide

27035

VESDA-E VEA-040-A10 Product Guide

!

CAUTION: DO NOT CONNECT ANY OTHER DEVICE TO THE SPARE VESDANET PORT ON THE VEA-040-Axx-NTF.

Summary of Contents for Notifier VESDA-E VEA Series

Page 1: ...nd electri cal connections This document contains generic product information and some sections may not comply with all local codes and standards In these cases the local codes and standards take precedence The information below was correct at the time of printing and may be out of date check with your local codes standards and listings for current restriction FCC Compliance Statement This equipme...

Page 2: ...F NOTIFIER Intelligent VESDA E VEA 40 point with LEDs VEA 040 A10 NTF NOTIFIER Intelligent VESDA E VEA 40 point with 3 5 Display Compatibility with FACP VEA 040 Axx NTF is compatible with the following NOTIFIER FACPs NFS2 3030 NFS2 640 NFS 320 Installation VEA is an addressable Aspirating Smoke Detector ASD with 40 addressable microbore tubes VEA is configured as an ASD in a 5 address space provid...

Page 3: ...respective terminals on the SLC terminal block as shown in figure below Refer to the diagram below to wire the SLC detector to the FACP Communication ports All of the standard ports of VEA 040 Axx are available except for VESDAnet VESDAnet is not available to the user in these models of the detec tors However Gateway function is still applicable to this detector model to connect to Xtralis VSC SLC...

Page 4: ...aded with Xtralis VSC software is directly connected to the detector using the USB port for initial configuration of the detector FACP Programing For FACP programing use the FlashScan ID FAASTX and Type Code ASPIRATION or ASPIR SUP Do not use ASPIR PRE ASPIR NON and ASPIR REF For the 40 addressable tubes use the FlashScan ID PHOTO and Type Code Smoke Photo SLC Address Assignment The SLC addressing...

Page 5: ...air flow normalization process for the selected detector The normalization process determines the reference flow rate Normalization should be performed after changing pipe or monitoring pump settings The process takes approximately 30 minutes The detector must have been powered up for 5 minutes before the Normalization process can be initiated The detector can be in normal or disabled mode The pum...

Page 6: ...cal Smoke Test command to complete the test Stop Local Smoke Test End an in progress local smoke test Fault 826 will cleared Start Leak Test Test for air leaks within the detector Test is performed automatically every 24 hours at a specified time Can be manually initiated from within the Xtralis VSC software Generates Fault 829 if leaks are detected Stop Leak Test End an in progress leak test Samp...

Page 7: ...mulate full scale smoke level and initiates all alarm activity Alarm relays will energize unless the detector is disabled Procedure 1 Initiate the Start Alarm Test command from the Device menu 2 Select the tubes to be tested by editing the check boxes in the Enable column 3 Set the test duration default 30 seconds 4 Select Start 5 End the test early by selecting Stop Start Air Flow Fault Test Test...

Page 8: ... Axx product guide can be set using the VSC software Follow the VEA 040 Axx product guide for information on setting up the remaining parameters GPIs and Relays General purpose inputs are not available to be configured via VSC Relay options are not available to be configured via VSC The following screen shot shows relay assignments for the SLC instance Tube Flow Scan The Tube Flow Scan function al...

Page 9: ...mapped to the following categories at the FACP Use the Xtralis VSC software to further investigate the following faults Sensor fault Aspirator fault Communication fault Configuration fault Low flow fault High flow fault Filter fault clogged Low voltage fault Refer to the troubleshooting section of VEA 040 Axx product guide for additional fault information Commissioning Forms Customer Name Site Add...

Page 10: ...o the client obtain the relevant signatures and ensure that all required documents are included VEA 040 Axx Detector Configuration Record Use the Xtralis VSC application to print a record of the detector s configuration Select the detector on the Xtralis VSC tree view at the left and choose the Print command on the File menu Hand Over Documents Copy of this form Configuration printout or record if...

Reviews: