N200-504-00
I56-4420-000
Notifier by Honeywell
Pittway Tecnologica S.r.l
Via Caboto 19/3
34147 Trieste, Italy
-20°C
60°C
Fig./Abb. 2
Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ
M710E-CZ
M200E-SMB
Lift
Sollevare
Levantar
Anheben
Push down
Premere
Precionar
hacia abajo
Runterdrücken
Rotate / Ruotare
Girar /
Drehen
Rotate
Ruotare
Girar
Drehen
Clip / Agganciare
Acoplar /
Einrasten
Plug
Inserire
Conectar
Einhaken
2
3
1
1
3
2
1:2 DIN
1:1 M200E-SMB
Fig./Abb. 1
DOP-IOD100
EN 54-17: 2005, EN 54-18: 2005
0905 22
This manual is intended as a quick reference installation guide. Please refer to the
control panel manufacturers installation manual for detailed system information.
The M700 series of modules are a family of microprocessor controlled interface
devices permitting the monitoring and/or control of auxiliary devices.The M710E-CZ
provides an interface between a zone of System Sensor manufactured conventional
type fire detection devices and an intelligent signalling loop.
A single tri-colour LED indicates the status of the module. In normal conditions, the
LED can be set by command from the control panel to blink green when the module
is polled. In the case of a fire alarm on the conventional zone, the LED is switched
on constant red by panel command. If a fault is detected on the conventional zone or
the zone supply voltage drops below 18 V, or a fault with the external power supply
is signalled, the LED will blink yellow if enabled on the control panel. When a short
circuit is detected on the loop to either side of the module, the LED is switched to show
a constant yellow light.
This module does not require maintenance.
SPECIFICATIONS
Intelligent Loop
Operating Voltage Range: see S00-7100
LED Cutoff Voltage: 16.5 V
Max. Standby Current (@24 V and 25
o
C) External Supply Conventional Zone:
No Communication:
120 µA
Max. Standby Current (@24 V and 25
o
C) Conventional Zone connected to Capacitive
EOL only, Loop Powered Conventional Zone:
No Communication:
1.3 mA
LED Current (Red):
1.3 mA
LED Current (Yellow):
4.5 mA
Isolator Features: see S00-7100
Conventional Zone
Supply Voltage:
18 to 32 V (either from loop or external supply)
Maximum Standby Load Current: 3 mA for detectors
Maximum Zone Load:
17.5 mA (limited internally)
Maximum Conventional Line Resistance: 50 Ω (both legs)
End of Line Capacitor:
47μF non-polarised. M200E-EOL-C supplied
General
Humidity:
5% to 95% relative humidity (non-condensing)
Ingress protection:
IP44 (mounted in M200E-SMB)
Maximum Wire Gauge:
2.5 mm²
INSTALLATION
Note:
These modules must only be connected to Notifier control panels using
analogue addressable communication protocols for monitoring and control.
M700 series modules can be mounted in several ways (See
Figure 1
):
1:1
An M200E-SMB custom low profile surface-mounting box. The SMB Base is
affixed to mounting surface, and then the module and cover are screwed onto
the base using the two screws supplied. Box dimensions: 132 mm (H) x 137 mm
(W) x 40 mm (D)
1:2
The DIN bracket on top allows mounting onto standard 35 mm x 7.5 mm "Top Hat"
DIN rail inside a control panel or other suitable enclosure. Install and remove as
shown in Figure 1:2
Wiring to all series M700 modules is via plug in type terminals capable of supporting
conductors up to 2.5 mm²
CAUTION
Disconnect loop power before installing modules or sensors.
The module address is selected by means of rotary decade address switches (see
Figure 3
). A screwdriver should be used to rotate the wheels to select the desired
address, either from the front or the top of the module.
Note:
The number of addresses available will be dependent on panel capability,
check the panel documentation for information on this.
Short Circuit Isolators
All M700 series modules are provided with short circuit monitoring and isolators on the
intelligent loop. If required the isolators may be wired out of the loop to facilitate the
use of the modules on high current loaded loops, for example if sounders are used.
To achieve this, the loop out positive should be wired to terminal 5 rather than terminal
2. See
Figure 2
for details.
CAUTION
Electrostatic Sensitive Device
Observe precautions when handling and making connections
M710E-CZ
INSTALLATION INSTRUCTIONS - M710E-CZ
CONVENTIONAL ZONE INTERFACE MODULE
EN
M710E-CZ
Fig./Abb. 3