ID61/62 Series Panel - Operating Manual
Operator
Actions at Panel
24
997-458-000-8, Issue 8
January 2010
After a few seconds, the panel will automatically return
to Test Mode and the device LED will be turned off. The
panel is then ready to test the next device.
Note:
Up to one minute must be allowed for smoke
sensors to clear.
If a fire alarm signal is received from a zone other than
those being tested, all sounder output and relay output
circuits will activate as configured for a zone in alarm. The
sounders will continue to ring until silenced from the panel.
4.9.4 Auto High Test - User Option
The Auto High Test, if configured during commissioning,
automatically polls and tests all devices on the loop at a
specified time of day. This operation takes about 70-80
seconds to complete. To run the test manually:
1
From the Test Menu, using the numeric keypad press
the ‘
4
’ button to select the Auto High Test.
2
When the LCD displays the start Auto High Test
message, press the ‘
5
’ button to start the test.
3
Each sensor is tested individually. The device under
test is displayed on line 2 of the LCD in the format
shown below, then re-displays the Test Menu.
4
After each device test the pass or fail message is
displayed, as in the examples below:
5
If a fault occurs while the Auto High Test is active the
LCD displays a fault message (example given below):
Press the ‘
6
’ button to display additional zonal and
device text information. Press the ‘
4
’ button to return
to the Test menu. Clear the fault and repeat the test.
[U0 Test] 1:LEDs
2:LCD
3:Zones
4:Auto High Test
5:Outputs
¦
: More
Manually start automatic high test ?
Press
to confirm
<:Cancel
4
5
Test started ! !
[Sensor nn in test]
<:Cancel
Sensor nn passed
Total failed:nn
[Sensor nn in test]
<:Cancel
Sensor nn failed
Total failed:nn
[Sensor nn in test]
<:Cancel
FAULT
01 / 03 Z01 M12 MCP
14:55
DEVICE FAILED AUTO HIGH TEST
>