ID61/62 Series Panel - Operating Manual
Operator
Actions at Panel
18
997-458-000-8, Issue 8
January 2010
4.7 Numeric Keys
When using any numeric key, each operation is confirmed
by a sharp audible bleep.
At Access Level 1, the numeric buttons have NO function
until an alarm condition occurs. The alarm condition
enables the ‘
2
’ and ‘
8
’ buttons, allowing the user to
view each alarm in turn.
At Access Level 2 the ‘
2
/
8
’ function remains identical
to the Level 1 function. The ‘
4
’ (cancel), ‘
5
’ (confirm),
‘
6
’ (go to next option) pushbuttons are enabled.
Numeric entry (used in conjunction with the ‘
0..9
’ [shift]
button) is also enabled.
a. Use the ‘
2
’ and ‘
8
’ buttons to scroll through fire
alarms, fault conditions, and warning conditions or to
view the ‘More’ menu list when available.
b. Press the ‘
5
’ button to confirm an option.
c. Press the ‘
0..9
’ (Shift) button to enable number entry.
Following the input of a number (approx. 1 second
later) a second audible bleep indicates that number
entry is no longer enabled.
d. When an internal printer is fitted, press the un-shifted
‘
0
’ button to feed the printer paper - one press of
the ‘
0
’ button advances the paper by one line.
4.7.1 Cancellation/Termination Button
To cancel or terminate configuration data entry, press the
‘
4
’ button. The LCD returns to the previous menu.
To cancel access rights, press the ‘
4
’ button until the
‘Status: NORMAL’ message is displayed.
4.7.2 Level 2 Options Menu Button
Operating the ‘
’ button enables the Level 2 menu and
prompts for the entry of an appropriate access code, as
described in
Section 4.1.3 Access Codes
.
Pressing the menu button toggles between the panel
status and user menus.
Press and hold the ‘
0..9
’
(Shift) pushbutton while
entering numbers.
0..9