82
Notifier FirstCommand Series Manual —
P/N LS10001-001NF-E:H 1/8/2018
Appendix B: Wiring Requirements
Connecting external system accessories to the NFC-50/100 main circuits must be carefully considered to ensure proper operation. It is
important to use the correct type of wire, wire gauge and wire run length per each circuit. Refer to the following table to specify wire
requirements and limitations.
NOTE:
If an SLC loop is to be run in conduit with NFC-50/100 Notification Appliance Circuits, the risk of encountering problems can be
greatly reduced by using twisted, shielded cable on the SLC and NACs.
Circuit Type
Wire Type & Limitations
Maximum Distance (feet)
Wire Gauge
(terminals support)
CMD1-CMD2
TB4, TB5: polarity reversal
untwisted/unshielded,
twisted/shielded, see note
1
1 Refer to NEC Standards.
depends on trigger circuit,
9-32 VDC, 1.6 mA
12-18 AWG
CMD1-CMD2
TB4, TB5: contact closure
untwisted/unshielded,
twisted/shielded, see note
max loop impedance 200 ohms
12-18 AWG
CMD3-CMD8
TB6-TB8: contact closure
untwisted/unshielded,
twisted/shielded, see note
max loop impedance 200 ohms
12-18 AWG
speaker circuits
TB20, TB21
untwisted/unshielded,
twisted/shielded, see note
2
2 Twisted, shielded wire is recommended for maximum protection against EMI and AFI emissions and susceptibility.
determine using Lite-Calcs utility
see note
3
3 Must also meet NFPA 72 Standards for minimum and maximum sound levels.
12-18 AWG
ECC-CE6 speaker circuits
TB1 - TB6
untwisted/unshielded,
twisted/shielded, see note
determine using Lite-Calcs utility
see note
12-18 AWG
external data bus: TB12
twisted/shielded
max loop impedance 13.2 ohms
12-18 AWG
external audio riser: TB22
twisted/shielded
max loop impedance 13.2 ohms
12-18 AWG
external operator interface power:
TB24
untwisted/unshielded,
twisted/unshielded
max loop impedance 13.2 ohms
12-18 AWG
NAC output: TB19
untwisted/unshielded,
twisted/unshielded
refer to Section 2.6.3 , max loop
impedance 120 ohms
12-18 AWG
speaker volume control override:
TB23
untwisted/unshielded,
twisted/unshielded
max loop impedance 120 ohms
12-18 AWG
night ring input: TB16
untwisted/unshielded,
twisted/unshielded
max impedance 30 K ohms
12-18 AWG
external audio input
TB5 (on display board)
twisted/shielded
max loop impedance 100 ohms
12-18 AWG
MNS active, AC loss, and trouble
output relays: TB1 - TB3
untwisted/unshielded,
twisted/shielded, see note
depends on the panel monitoring
these outputs
12-18 AWG
auxiliary power: TB17
untwisted/unshielded, see note
distance set by 4 VDC max line
drop
12-18 AWG
Table B.1 Wiring Requirements
NOTE:
Wire to wire short circuit trouble = zero ohms.
Open circuit trouble = infinite ohms.
Ground fault trouble = zero ohms to ground.
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...