32
FCPS-24S Series Instruction Manual —
P/N 51977:J2 7/11/2014
Applications
Split Temporal Mode of Operation
5.3 Split Temporal Mode of Operation
In this application, the power supply has been set as a master with two synchronized and two non-
synchronized outputs as determined by the Split Temporal mode feature. Control Input #1 (TB4,
Terminals 3 & 4) is connected to an addressable control module which will cause the synchronized
power supply output circuits 1 & 2 to turn on. Control Input #2 (TB4, Terminals 7 & 8) is con-
nected to an FACP Notification Appliance Circuit which is used to activate the power supply’s tem-
poral output circuits 3 & 4.
TB
4
JP
3
J3
TB
5
TB
2
JP1
JP
2
OUT4
-NAC4
+
OUT4
-N
AC4+
OU
T4
-NAC
4+
OUT3
-NA
C
3
+
OUT2
-NAC
2
+
OU
T
1
-NA
C1+
AU
X
-
IN
2-
IN
2+
OUT
1
-
OUT1
+
IN1-
IN1
+
SYNC
IN
-
SYN
C
I
N
+
AU
X
+
NO
N
C
AUX
T
B
L
CO
M
1 2 3 4 5 6 7 8 9 10
8
7
6
5
4
3
2
1
8
7
8
7
TB2
TB2
3
2
1
+
+
+
+
+
+
+
+
+
-
-
-
-
-
-
-
-
-
T1
T11
T2
T10
T3
T9
T4
T8
T5
T7
T6
Figure 5.3 Split Temporal Mode Application
Style Z (Class A)
Style Y (Class B)
Temporal Bell Circuit 4
Temporal Bell Circuit 3
Horn/Strobe Circuit 2
Horn/Strobe Circuit 1
Use listed ELR
(4.7K
:
) to
terminate Style Y
(Class B) NAC
ELR not required for
Style Z (Class A) NAC
Note: All NACs are supervised and power-limited (Class 2)
ZNAC-4
Option Module
SW1 Switch Settings
1 & 2 = sync (any setting but
OFF/OFF)
3 = OFF (master)
4 = OFF (no AC Fail reporting delay)
5 = ON
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Internal Trouble Contact
Split Temporal
FACP
Control Module*
End-of-Line
Resistor supplied
with Control Module
FACP NAC
End-of-Line
Resistor
Bells
Bells
SLC
2
4
fsa
pp5
tp
H
2
.wmf
*If the SLC device does not match the one in this figure, refer to the SLC manual
wiring conversion charts for legacy and newer versions of the modules.
T11
T10
T9
T8
T7
T6
T1
T2
T3
T4
T5
FCPS-24S
NAC
(steady,
no sync)