Figure 3. typiCal Class B, solenoid ConFiguration:
(+)
(-)
(+)
(-)
(+)
(-)
(-)
(+)
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
TO NEXT
MODULE
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA
70. UL 864 LISTED FOR
RELEASING DEVICE
SERVICE USE WITH
BATTERY BACKUP.
POWER SUPPLY
SUPERVISION BY
MODULE
CONNECT MODULES TO LISTED
COMPATIBLE NOTIFIER
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
RELEASING
CONTROL
MODULE
FROM
PANEL OR
PREVIOUS
DEVICE
TO NEXT
DEVICE
OUTPUT TO A UL LISTED FIRE
ALARM RELEASING SOLENOID
(REFER TO PANEL MANUFACTURER'S
INSTALLATION DOCUMENT)
C0996-00
Figure 4. typiCal Class a, solenoid ConFiguration:
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
POWER SUPPLY
SUPERVISION BY
MODULE
TO NEXT
MODULE
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO
LISTED COMPATIBLE
NOTIFIER CONTROL
PANELS ONLY
FROM
PANEL OR
PREVIOUS
DEVICE
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER
NFPA 70. UL 864 LISTED
FOR RELEASING DEVICE
SERVICE USE WITH
BATTERY BACKUP.
RELEASING
CONTROL
MODULE
OUTPUT TO A UL LISTED FIRE
ALARM RELEASING SOLENOID
(REFER TO PANEL MANUFACTURER'S
INSTALLATION DOCUMENT)
C0997-00