Honeywell Notifier FCM-1-REL Installation And Maintenance Instructions Download Page 2

Figure 3. typiCal Class B, solenoid ConFiguration:

(+)

(-)

(+)

(-)

(+)

(-)

(-)

(+)

24 VDC CIRCUIT

DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE 

RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

TO NEXT 

MODULE

24 VDC POWER SUPPLY

ISOLATED, REGULATED, 

POWER LIMITED PER NFPA 

70. UL 864 LISTED FOR 

RELEASING DEVICE 

SERVICE USE WITH 

BATTERY BACKUP.

POWER SUPPLY 

SUPERVISION BY 

MODULE

CONNECT MODULES TO LISTED 

COMPATIBLE NOTIFIER 

CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED 

AND POWER LIMITED

RELEASING

CONTROL 

MODULE

FROM 

PANEL OR 

PREVIOUS 

DEVICE

TO NEXT 

DEVICE

OUTPUT TO A UL LISTED FIRE 

ALARM RELEASING SOLENOID

(REFER TO PANEL MANUFACTURER'S 

INSTALLATION DOCUMENT)

C0996-00

Figure 4. typiCal Class a, solenoid ConFiguration:

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

POWER SUPPLY 

SUPERVISION BY 

MODULE

TO NEXT 

MODULE

TO NEXT 

DEVICE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO 

LISTED COMPATIBLE 

NOTIFIER CONTROL 

PANELS ONLY

FROM 

PANEL OR 

PREVIOUS 

DEVICE

24 VDC CIRCUIT

DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE 

RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

24 VDC POWER SUPPLY

ISOLATED, REGULATED, 

POWER LIMITED PER 

NFPA 70. UL 864 LISTED 

FOR RELEASING DEVICE 

SERVICE USE  WITH 

BATTERY BACKUP.

RELEASING

CONTROL 

MODULE

OUTPUT TO A UL LISTED FIRE 

ALARM RELEASING SOLENOID

(REFER TO PANEL MANUFACTURER'S 

INSTALLATION DOCUMENT)

C0997-00

NO-460-002 

I56-2992-004 

 

 

©2008 Notifier