Honeywell Notifier FCM-1-REL Installation And Maintenance Instructions Download Page 1

Wiring

NOTE:  All  wiring  must  conform  to  applicable  local  codes,  ordinances,  and 
regulations. 

1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.  Set the address on the module per job drawings.
3.   Secure  module  to  electrical  box  (supplied  by  installer),  as  shown  in 

Figure 2.

IMPORTANT:  When  using  the  FCM-1-REL  for  Class  B  applications,  remove 
Jumper  (J1)  and  discard.  The  Jumper  is  located  on  the  back  as  shown  in 
Figure 1B.

Figure 2. Module Mounting:

C1060-00

NO-460-002 

I56-2992-004

FCM-1-rel releasing Control Module 

BeFore installing

This information is included as a quick reference installation guide. Refer to 
the control panel installation manual for detailed system information. If the 
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.

general desCription

FCM-1-REL Releasing Control Modules are intended for use in intelligent, two-
wire systems, where the individual address of each module is selected using 
the built-in rotary switches. This module is used to switch an external power 
supply, which can be a DC power supply to a solenoid. It also supervises the 
wiring to the connected load and reports the status to the panel as NORMAL, 
OPEN, or SHORT CIRCUIT. The FCM-1-REL has two pairs of output termination 
points available for fault-tolerant wiring and a panel-controlled LED indicator. 

CoMpatiBility requireMents

To ensure proper operation, this module shall be connected to a compatible 
Notifier system control panels only (list available from Notifier). In addition, 
please refer to Notifier Device Compatibility document number 15378 for the 
list of compatible solenoids.

Mounting

The FCM-1-REL mounts directly to 4-inch square electrical boxes (see Figure 
2). The box must have a minimum depth of 2

1

/

8

 inches. Surface mounted elec-

trical boxes (SMB500) are available (for indoor dry applications only).

Figure 1a. Controls and 

Figure 1B. JuMper loCation: 

indiCators:

J1

 

C1059-00 

C0910-00

I56-2992-004

speCiFiCations

SLC

 

  Normal Operating Voltage: 

15 to 32 VDC Nominal

  Average Operating Current: 

700µA (LED flashing)

  Maximum Activation Current: 

9.0 mA (red LED on)

External Supply

  Normal Operating Voltage: 

24 VDC Nominal

  Maximum Line Loss: 

2.3 VDC (total allowable loss from power supply to module and from module to solenoid)

  Minimum Operating Voltage to Activate Solenoid: 

18 VDC (at solenoid) 

  Standby Current: 

6.4 mA

  Activation Current: 

10 mA

  Maximum Activation Current: 

2 A

Solenoid

  Supervisory Loop Voltage: 

3.3 V

  Supervisory Loop Current (Normal): 

30 mA

  Maximum Activation Current: 

2 A

Temperature Range: 

14°F to 140°F (-10°C to 60°C)

Humidity: 

10% to 95% RH Non-condensing

Dimensions: 

4

1

/

2

˝ H × 4˝ W × 1

1

/

4

˝ D; (106 mm H × 108 mm W × 31 mm D)

Accessories: 

Wall cover plate (included); SMB500 Surface Mount Electrical Box (for indoor dry applications only)