AM-1224
Installation and programming manual
PAGINA -
39
AM-1224_manu
Doc. M-124.1-AM1224-ENG Rev A.1
NOTIFIER ITALIA
TIM
Is the user that allow to programm the output activations with periodical time limits.
There are two possible formats:
FORMAT Type 1 : TIM (SU MO TU WE TR FR SA 00.MM 00.MM)
Where : 00 = hours, MM = minutes
This format give the possibility to programm weekly limits, for fixed days of the week.
FORMAT Type 2 : TIM (MM GG AA OO.MM OO.MM)
Where: MM = month, GG = day, AA =year
This format give the possibility to programm annual limits.
Example: IF
the equation of output
02
is:
TIM (SA SU 07.30 13.59)
THEN
the output
02
will be active
saturday
and
sunday
from 07.30 AM to 13:59.
NOTE:
If the day, month or year is not indicated, the value takes up the “EACH” meaning.
Introduce two signs do not specify anything “
“ see example below:
TIM
(
07.30 13.59)
The values of start time and end time, use the 24-hour format (midnight = 00.00 ... 23.59)
the “00.MM” value as end time has to be greater than the start time.
the maximum value for start time and end time is 23:59
Days of activation
(optional)
Start time
End time
Enter a space
character
Enter a space
character
Days of activation
(optional)
Start time
End time
Enter a space
character
Enter a space
character