Honeywell NOTIFIER AM-8200 Installation Manual Download Page 34

AM-8200 

Installation Manual

 

PAGE - 31 

AM8200_manu-inst 

 Doc. M-162.2-AM8200-ENG Rev A.2 

NOTIFIER ITALIA 

16 Loops Network max 500 m Node-to-Node 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

 
 
 
 
 

 

 

Network with AM82-2S2C board installed on the AM-8200 control panel

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

AM82-2S2C

 

 

AM82-2S2C

 

 

 

500 m Node-Node 

 

 

500 m Node-Node 

 

 

500 m Node-Node 

 

 

500 m Node-Node 

 

 

AM-8200

 

CAN-BUS

 

CAN-BUS

 

CAN-BUS

 

CAN-BUS

 

AM-8200

 

AM-8200-BB

 

max 500 m

 

max 500 m

 

max 500 m

 

max 500 m

 

PRINTER

 

AM82-2S2C

 

 

 

AM82-BST-C

 

 

 

HLPPS25

 

 

 

Summary of Contents for NOTIFIER AM-8200

Page 1: ...AM 8200 Installation MANUAL Rev A 01 Fire Detection System ...

Page 2: ...supply AM 8200BB 10 Power Supply 10 Battery Charger section 10 Batteries 10 Power supply and battery operation 11 Mains and Batteries connection 12 Current consumption from Power Supply 13 Current consumption from battery 13 SYSTEM COMPONENT 14 BOARDS AND INTERCONNECTION AM8200 15 BOARDS ASSEMBLY AM8200 15 LIB 8200 Assembly 16 AM 8200 KLCD AM 8200 CPU Board 16 AM 82 MB Terminal Board 17 CN1 Termin...

Page 3: ...AM82 BST C AMPLIFIER BOARD CAN BUS 29 Board Assembly AM82 BST C 30 AM 8200 NETWORK 31 System Wiring Example 31 16 Loop Network 31 Network with AM82 2S2C board installed on AM 8200 control panel 31 Network with AM82 BST C board installed on HLSPS25 EN54 4 32 Can Bus wiring CABLES 32 Communication lines with Detectors Modules 33 Modules and Detectors connection 34 Test procedure for detection lines ...

Page 4: ...which is guaranteed by NOTIFIER and is compatible with its own control units Please consult NOTIFIER Technical Service for any doubt This system like all solid state components may be damaged by induced electrostatic voltages handles the boards keeping them among the edges and avoid to touch the electronic components An appropriate earthing connection ensures in any case a sensitivity reduction to...

Page 5: ...M 8200 control unit is in conformity with the following EN54 4 requirements Function EN 54 4 reference Power supply from main source Power supply from battery source in standby Re charging and check of the battery source Power supply fault detection and signalling 5 1 5 2 5 3 5 4 This device must be installed and must operate in accordance with these instructions and to the rules in force in the i...

Page 6: ... output 28Vdc 3 18 3 5A on board to power external loads such as sirens bells etc OUTPUTS o 1 Supervised Sounder Output o 1 General Alarm Output with contacts free from voltage supervised Output EOL 47KΩ o 1 General Fault Output with contacts free from voltage supervised Output EOL 47KΩ Mechanics The control unit mechanics is suitable for wall installations For cabinet sizes refer to the below dra...

Page 7: ...PAGE 4 INSTALLATION MANUAL AM 8200 NOTIFIER ITALIA Doc M 162 2 AM8200 ENG Rev A 2 AM8200_manu inst AM 8200 dimensions Top view Back view Botton view BACK view ...

Page 8: ...AM 8200 Installation Manual PAGE 5 AM8200_manu inst Doc M 162 2 AM8200 ENG Rev A 2 NOTIFIER ITALIA AM 8200 and AM 8200 BB Installation Sequence for wall mounting ...

Page 9: ... NOTIFIER ITALIA Doc M 162 2 AM8200 ENG Rev A 2 AM8200_manu inst AM 8200 front panel Warning Drill into the lower part of the panel of the AM 8200 with a 10mm diameter drill bit for the passage of the 230Vac power cable of the AM 8200BB ...

Page 10: ...opening of the front panel The control unit is designed to be installed to the wall through self blocking cleats masonry walls or self tapping screws pre fabricated panels It is recommended not to install the panel near heat sources radiators etc Use screws of max 5 mm The control unit must be installed to the wall so as to allow a clear view of the display and easy access by the operator For exam...

Page 11: ... M 162 2 AM8200 ENG Rev A 2 AM8200_manu inst Extractable labels on the front panel AM 8200 EU control panel is provided with extractable labels to indicate the functions Status via LED A set of some different languages labels are provided in each EU panel ...

Page 12: ...netic sources ex repeaters radio relays motors etc Power supply The internal power supply has the following output 28 8Vdc 29 0Vdc 3 5 A ripple max 500mVpp Power supply for control unit user output external load power supply User Output 28 5Vdc 28 9Vdc 2A with 2 A resettable fuse Battery charger section Output voltage 26 5 Vcc 28 5Vcc temperature compensation Output current 1A 500mVpp max Number o...

Page 13: ... Output voltage 26 5 Vdc 28 5 Vdc 500mA Vpp max temperature compensation Output current 1A 500mVpp max Number of batteries that can be connected 2 x 12 V min 7Ah max 18Ah max The battery charger section has the following signaling thresholds Exhausted battery threshold 21 5 Vdc Re charge Fault threshold 3 4 Vdc voltage difference between the two batteries Battery release threshold 19 5 Vdc Thresho...

Page 14: ...rates through AC mains the main microprocessor controls the battery charger output and the presence of them To perform this test the output battery charger is temporarily switched off and the battery voltage is read signaling of missing batteries 15 0V When the control unit operates as a battery in the absence of the AC mains Low Battery breakdown will be indicated when their voltage is 21 5V and ...

Page 15: ...act separation 3 mm min The sectioning device must be omni polar or must disconnect the line phase Power Supply connection must be done following this procedure Refer to Base Board 1 Turn off the main power switch of the 230 Vac mains 2 Disconnect the CN1 terminal block from the control unit 3 Connect the mains cable 4 Re connect the CN1 terminal block 5 Turn on the mains switch 6 Install and conn...

Page 16: ...mA AM82 BST C AMPLIFIER BOARD CAN BUS at nominal voltage 29Vdc 39mA Current consumption from battery Current from battery in Normal Condition in the absence of mains voltage 230Vac AM 8200 KLCD CPU AM 8200 Board at nominal voltage 24Vdc 113mA AM 82 BBMB CPU AM 8200BB Board Card at nominal voltage 24Vdc 95mA LIB 8200 LIB at nominal voltage 24Vdc 53mA AM82 2S2C INTERFACE RS232 485 CAN BUS at nominal...

Page 17: ...2 ADV detection loops Each ADV Loop line can connect up to 159 detector and 159 Modules in Advanced protocol One amplifier board CAN BUS AM82 BST C One optional interface RS232 485 CAN BUS AM82 2S2C BOARDS AND INTERCONNECTION AM 8200 SIB 8200 LIB 8200 AM82 2S2C AM 8200 KLCD AM 8200 LIB 8200 loop expansion board line 3 line 4 AM82 MB terminals line 1 line 2 AM82 2S2C INTERFACE RS232 485 CAN BUS POW...

Page 18: ...00_manu inst Doc M 162 2 AM8200 ENG Rev A 2 NOTIFIER ITALIA Boards Assembly AM82 2S2C Assembly Flat cable 3 x screw AM82 2S2C B 2 x screw AM82 2S2C A 2 x spacer 3 x spacer AM 8200 KLCD AM 82 MB back front AM 8200 KLCD AM82 2S2C A AM82 2S2C B ...

Page 19: ...PAGE 16 INSTALLATION MANUAL AM 8200 NOTIFIER ITALIA Doc M 162 2 AM8200 ENG Rev A 2 AM8200_manu inst AM 8200 KLCD AM 8200 CPU Board LIB 8200 Assembly 2 x spacer 1 x screw LIB 8200 AM 82 MB ...

Page 20: ...Negative in non alarm 1 A resettable fuse this is a polarity inversion output EOL resistor 47KΩ 17 Sounder positive in non alarm 16 User 2 Relay N C N O Max 30V 2A Select N O N C with JUSR2 Jumper or supervised output resettable fuse 0 3A with EOL resistor 47KΩ 15 User 2 Relay Common 14 User 1 Relay N C N O Max 30V 2A Select N O N C with JUSR1 Jumper or supervised output resettable fuse 0 3A with ...

Page 21: ... Vdc NO NC or supervised output 0 3A Fused selectable through Jumper JUSR2 refer to basic board topography Max 2A resistive 30 Vdc NO NC or supervised output 0 3A Fused selectable through Jumper JUSR1 refer to basic board topography Max 2A resistive 30 Vdc NO NC or supervised output 0 3A Fused selectable through Jumper JALL refer to basic board topography Max 2A resistive 30 Vdc NO NC or supervise...

Page 22: ...n free voltage contacts or as supervised output Contact range max 30 VAC DC 2A Non inductive loads CNU COM NO NC 11 12 Polarized devices electronic sirens etc 47 K W 12 11 Non polarized devices Bells relays etc 47 K W 2 x 1N 4004 12 11 Main Alarm output Supervised output resettable fuse 0 3A with EOL resistor 47KΩ Setting of the general Alarm output with N O contact Jumper JALL Setting of the gene...

Page 23: ...ve loads Selection of type of contact Normally open Normally closed or supervised outputs see page 15 NOTE To program the activation of these outputs refer to AM 8200 Programming Manual USR1 Output Supervised output resettable fuse 0 3A with EOL resistor 47KΩ Polarized devices electronic sirens etc 47 K W 14 13 Non polarized devices Bells relays etc 47 K W 2 x 1N 4004 14 13 CNU USR1 COM NO NC 13 1...

Page 24: ...ated condition at idle condition they are inverted USR2 Output Supervised output resettable fuse 0 3A with EOL resistor 47KΩ Polarized devices electronic sirens etc 47 K W 16 15 Non polarized devices Bells relays etc 47 K W 2 x 1N 4004 16 15 Setting of the USR2 output with N O contact Jumper JALL Setting of the USR2 output with N C contact Jumper JALL Setting of the USR2 output as supervised outpu...

Page 25: ...displayed are in Alarm condition at idle condition they are inverted Sounder connection controlled output Polarized devices electronic sirens etc 47 K W 17 18 Non polarized devices Bells relays etc 47 K W 2 x 1N 4004 17 18 Thresholds for supervised outputs CNU 18 17 Sounder output connections refer to basic board topography 1A resettable fuse NORMAL STATUS OPEN CIRCUT SHORTCIRCUIT 21K 61K ...

Page 26: ...necessary to set the address n 4 Detection Lines connection on AM 8200 N Description Characteristics Note 8 Line 2 B Detection LINE 4 if the board is mounted on AM 8200 Detection LINE 8 if the board is mounted on AM 8200 BB 7 Line 2 B 6 Line 2 A 5 Line 2 A 4 Line 1 B Detection LINE 3 if the board is mounted on AM 8200 Detection LINE 7 if the board is mounted on AM 8200 BB 3 Line 1 B 2 Line 1 A 1 L...

Page 27: ...op Interface cards LIB 8200 Each LIB card can drive up to 2 ADV loop Each ADV Loop line can connect up to 159 detector and 159 Modules in Advanced protocol BOARDS AND INTERCONNECTION AM 8200BB Boards Assembly AM8200BB LIB 8200 AM 82 BBMB POWER SUPPLY AM 82 BBMB CPU BOARD line 5 line 6 LIB 8200 loop expansion board line 7 line 8 LIB 8200 Flat Cable AM 82 BBMB 2 x spacer 1 x screw 1 x spacer ...

Page 28: ...IA AM 82 BB MB AM 8200BB CPU Board User terminal block Fault led Alarm led Earth dispersion led Dip switch SW1 Battery connections Mains power terminal Connector for interconnections with LIB 8200 Flat cables for interconnections with AM 82 MB USB connector LIB 8200 3 x spacer 3 x screw AM 82 BBMB ...

Page 29: ... on CPU Board Dip switch Note 1 2 3 4 ON ON OFF OFF necessary to set the address N 3 on board AM 82 BBMB Detection Lines connection on AM 8200 BB N Description Characteristics Note 10 GND USR 2 A Resettable fuse 9 24V USR 8 Line 2 B Detection LINE 5 7 Line 2 B 6 Line 2 A 5 Line 2 A 4 Line 1 B Detection LINE 6 3 Line 1 B 2 Line 1 A 1 Line 1 A ...

Page 30: ...LIN N Description Characteristics Note 01 CDAHA Communication line side A for CAN BUS NETWORK optically isolated with 120 ohm termination resistor installed on board 02 GNDISA 03 CDALA 04 CDAHB Communication line side B for CAN BUS NETWORK optically isolated with 120 ohm termination resistor installed on board 05 GNDISB 06 CDALB Can Bus Terminal block RS232 RS485 Terminal block Rx RS232 Led Tx RS2...

Page 31: ...PAGE 28 INSTALLATION MANUAL AM 8200 NOTIFIER ITALIA Doc M 162 2 AM8200 ENG Rev A 2 AM8200_manu inst Summary of all Cards Connection ...

Page 32: ...F OFF OFF Address n 6 ON ON ON OFF OFF OFF Address n 7 OFF OFF OFF ON OFF OFF Address n 8 N Description Characteristics Note 01 24V Power input 02 GND 03 IN GST NO Digital input to signalize the power supply fault potential free contact 04 IN GST C GND N Description Characteristics Note 01 CDAHRA Communication line side A for CAN BUS NETWORK opticaly isolated with 120 ohm termination resistor inst...

Page 33: ...LIA Doc M 162 2 AM8200 ENG Rev A 2 AM8200_manu inst Board Assembly AM82 BST C AM 8200 NETWORK System Wiring Example 2 x screw AM82 BST C 2 x spacer 3 x spacer HLSPS25 AM 8200 AM 8200BB AM 8200 AM82 BST C inside the HLSPS25 PSU AM 8200 2S2C AM82 BST C ...

Page 34: ...ork max 500 m Node to Node Network with AM82 2S2C board installed on the AM 8200 control panel AM82 2S2C AM82 2S2C 500 m Node Node 500 m Node Node 500 m Node Node 500 m Node Node AM 8200 CAN BUS CAN BUS CAN BUS CAN BUS AM 8200 AM 8200 BB max 500 m max 500 m max 500 m max 500 m PRINTER AM82 2S2C AM82 BST C HLPPS25 ...

Page 35: ...rain Tinned copper 7x0 20 Can Bus Typology Similar to all RS 485 communication line the CAN Bus is a Point to Point sequential connection The wire must have a 120 Ohm resistor at each end on board on all boards The typology used is a Class A closed Loop Note that it s not necessary to follow the sequential series on the peripherals addresses T taps are not permitted Cable must be wired in conduits...

Page 36: ...of detection line connection cables Type of cable 2 conductors for their section refer to the table below Twisted narrow pitch 5 10 cm Shielded pair cable Max admitted capacity 0 5 uF Cable section The sections are referred to the total length of the line in case of STYLE 6 loop and therefore when the loop is closed it is considered the loop length which however must not be longer than 3000 meters...

Page 37: ...ction For the specific field device connections please refer to Analogue system device installation manual document M 199 1 SCH ITA or M 199 1 SCH ENG by Notifier Italia Example of closed line style 6 Loop The total length of the loop from the Panel Loop output and input SHALL NOT exceed 3 000 mt A SIDE LIB 8200 B SIDE LIB 8200 ...

Page 38: ...e Place a test prod of the tester on the line cable screen and the other test prod on the positive cable of the same line The resistance measured must be higher than 15 20 MOhm better if infinitive Perform the same operation between the line screen and negative cable Check that also in this case the resistance is higher than 15 20 MOhm Earthing lines insulation Place a test prod of the tester on t...

Page 39: ...ing connection is compulsory and must be fixed to the cabinet by means of a cable fixing device so that it cannot be accidentally stripped off The power supply connection must be performed through the following phases refer to basic board topography Turn off the main switch of the 230 Vca mains which powers the control unit Disconnect the CN1 terminal block from the control unit Connect the 230 Vc...

Page 40: ...ff General Fault relay deactivated 3 Disconnect both batteries wait not more than 2 3 minutes for the control unit to signal The indication of BATTERIES NOT CONNECTED on the display Yellow led FAULTS flashing Yellow led POWER OK on Yellow led MAINS on General Fault relay active Re connect the batteries and press the SILENCE ALARM FAULT key and check No breakdown signalling on the display Yellow le...

Page 41: ...stem operation Table 1 NORMAL condition ALARM condition A B Item Q Current each Total Current dev x Q Current each Total Current dev x Q AM 8200 AM 8200 CPU AM8200 KLCD 179 mA 345 mA LIB 8200 50 mA 92 mA AM82 2S2C 28 mA 28 mA AM82 BST C 39 mA 39 mA SIB 8200 62 mA 62 mA Devices connected to Sounder Output 1 0 0 _________ _________ Loops 2 Current Refer to Table 3 Loop 1 _________ _________ Loop 2 _...

Page 42: ...t request for the stand by or alarm conditions cannot in any case exceed the power supply capacity If the calculated current exceeds the value of 3 5 Ampere available at the power supply the exceeding current necessary during the Alarm condition is drawn from the batteries 5 The sum of currents obtained must be multiplied by a 1 2 factor to take account of the battery manufacturing tolerances NORM...

Page 43: ...700 Double Modules serie 700 Modules serie MA MMX 10ME CMX 10RME MCX 55ME Isolation modules Addressable Sounders Power from loop Other devices N B Total must be less than 0 75 A Total loop N 2 Total loop N 2 Detectors serie NFX Detectors serie 700 MCP Single Modules serie 700 Double Modules serie 700 Modules serie MA MMX 10ME CMX 10RME MCX 55ME Isolation modules Addressable Sounders Power from loo...

Page 44: ... M710 CZ 288 μA 8 8mA External Power M710 CZ 1 5 mA 8 8mA Loop Power M710 CZR 500 μA 8 8 mA External Power M710 CZR 6 5 mA 8 8 mA Loop Power M720 340 μA 5 mA M721 340 μA 5 mA M700X CMA 11E 340 μA 6 mA CMA22 700 μA 7 mA MCX 55ME 2 7 mA 30mA MMX 10ME 2 7 mA 30mA CMX 10RE 4mA 30mA M700KACI SG 660 uA 6 mA M700WCP R I SG 660 uA 6 mA P700 390 μA 5 mA NFXI WSF WC 450 uA 9 09 mA Maximum Volume NFXI WSF RR...

Page 45: ...PB 700 400 2 mA 8 5mA Loop Power LPB 700T 2 mA 8 5mA 24 Vcc external MMX 102E 100 μA 5 mA ZMX 1E 200 μA 9 mA External Power MCX 3 450 μA 5 mA MCX 3 IMX 1 200 μA 4 mA M500KA 200 μA 5 mA NBG 12LX 100 μA 5 mA M700K 260 μA 5 mA AWS32 R I 220μA 6 5mA Maximum Volume AWS32 R RD I 220μA 9 7mA Maximum Volume AWB RD I 220μA 2 2 mA ABS32 PW I 220μA 6 5 mA ABSB32 PW RD I 220μA 9 8 mA AWS32 R I 220μA 6 5mA Max...

Page 46: ...7 M Tel Fax 055 289177 00118 Roma Via Del Casale Santarelli 51 Tel 06 7988021 Fax 06 79880250 E mail notifier roma notifier it 80143 Napoli Palazzo Prof Studi Centro Direzionale Isola E2 Scala B Piano 5 Tel 081 19493111 Fax 081 7879159 E mail notifier napoli notifier it 70125 Bari Via Delia Costituente 29 Tel 080 6180700 Fax 080 5648114 E mail notifier bari notifier it 95128 Catania Viale Alcide D...

Reviews: