PAGE - 2
Manuale di installazione
AM-8000
NOTIFIER ITALIA
Doc. 160.1-AM8000-ITA Rev A.3
AM8000_manu-inst
EN 54 : Informations
EN54
This fire detection control unit is in accordance with the requirements of rule
EN54-2/4
.
In addition to the basic EN 54 requirements, the control unit is in conformity with the
following optional operation requirements
Optional Functions
EN 54.2 reference
Output to fire alarm devices
Output to fire protection equipment
Fault monitoring of fire protection equipment
Delays to outputs
Dependencies on more than one alarm signal
Fault signals from point
Total loss of power supply
Disablement of addressable points
Test Condition
Indication of the test condition
Indication of zones in the test state
7.8
7.10
7.10
7.11
7.12 ( type A )
8.3
8.4
9.5
10
10.2
10.3
EN54
The power supply section of the AM-8000 control unit is in conformity with the
following EN54-4 requirements.
Function
EN 54.4 reference
Power supply from main source
Power supply from battery source in standby
Re-charging and check of the battery source
Power supply fault detection and signalling
5.1
5.2
5.3
5.4
EN54
!
EN54-2 13.7
Max 512
Sensors / Manual
Call Points per
microprocessor.
The AM-8000 control unit has a maximum capacity of : 636 sensors
and 636 addressable modules .
If this function is not appropriately used, it can contravene the EN54
requirements.
This limit includes the possible conventional sensors and buttons
connected to the system with zone modules.
Therefore, check the number of installed devices and ensure their types
are in conformity with the rule
.
1293
Notifier Italia S.r.l. Via Grandi, 22 -20097 San Donato
Milanese (MI), Italy
12
1293 – CPD - 0316
EN 54-2, EN 54-4
Analog Addressable Fire Detection Panel AM-8000
type: BB-8000 with terminal LCD-8000-F or LCD-8000-L
Option with requirements:
EN-54-2
: 7.8, 7.10, 7.10, 7.11,
7.12 ( type A ), 8.3, 8.4, 9.5, 10, 10.2, 10.3