Honeywell NOTIFIER AM-8000 Installation Manual Download Page 34

AM-8000 

Manuale di installazione 

PAGE - 31 

AM8000_manu-inst 

  Doc. 160.1-AM8000-ITA Rev A.3 

NOTIFIER ITALIA 

Summary of Current consumption of Loop devices: 

 
 

Device 

Current 

NOTE 

  

Normal 

Alarm 

  

SDX-751ME 300 

μ

A       6,5 mA 

  

SDX-751TEM 300 

μ

A       7 mA 

  

FDX-551E 300 

μ

A       7 mA 

  

FDX-551HTE 300 

μ

A       7 mA 

  

NFXI-OPT 300 

μ

A       4 mA 

  

NFXI-TDIFF 300 

μ

A       4 mA 

  

NFXI-TFIX 58/78 

300 

μ

A       4 mA 

  

NFXI-SMT2 300 

μ

A       4 mA 

  

PINNACLE 330 

μ

A       6,5 mA 

  

HPX-751 300 

μ

A       5 mA 

  

SMART 3 

200 

μ

A 7mA 

 

 

SMART 4 

200 

μ

A 7mA 

 

 

LPB-700 / 400 

2 mA 

8,5mA 

Loop Power 

LPB-700T 

2 mA 

8,5mA 

24 Vcc external 

MMX-102E 100 

μ

5 mA 

  

M710E-CZ 288 

μ

A 8.8mA  External 

Power 

M710E-CZ 

1.5 mA 

8.8mA 

Loop Power 

M710E-CZR 500 

μ

8.8 mA 

External Power 

M710E-CZR 

6,5 mA 

8,8 mA 

Loop Power 

ZMX-1E 200 

μ

9 mA 

External Power 

IMX-1 200 

μ

4 mA 

  

M710-E 310 

μ

5 mA 

  

MMA1-I 400 

μ

5 mA 

  

MCX-3 450 

μ

5 mA 

  

M701E 310 

μ

5 mA 

  

CMA1-I 410 

μ

5 mA 

  

M500KA 200 

μ

5 mA 

  

M700K 260 

μ

5 mA 

  

M700KI 360 

μ

5 mA 

  

NBG-12LX 100 

μ

5 mA 

  

P700 390 

μ

5 mA 

  

M720 340 

μ

5 mA 

  

M721 340 

μ

5 mA 

  

M701E-240 275 

μ

8,8 mA 

  

CMA-11 340 

μ

6 mA 

  

CMA22 700 

μ

A. 

7 mA 

  

MCX-55M 

2.7 mA 

30mA 

  

MMX-10M 

2,7 mA 

30mA 

  

CMX-10R 4mA 

30mA 

 

 

AWS32/R-I 220

μ

A 6.5mA  Maximum 

Volume 

AWS32/R/RD-I 220

μ

A 9.7mA  Maximum 

Volume 

AWB/RD-I 220

μ

2,2 mA 

  

ABS32/PW-I 220

μ

6,5 mA 

  

ABSB32/PW/RD-I 220

μ

9,8 mA 

  

DNRE 300 

μ

A       4 mA 

Depends from Detector installed 

WL-NTM 

20 mA 

25 mA 

  

Summary of Contents for NOTIFIER AM-8000

Page 1: ...AM 8000 Intelligent Addressable Fire detection P l Installation manual ...

Page 2: ......

Page 3: ...tputs 10 Sounder Output 11 System Components 12 Black Box 12 AM 8000 CPU card 12 CNU CNU terminal block 13 DIP SWITCH on CPU CARD 14 AM 8000 Front Panel LCD 14 DIP SWITCH on LCD CARD 16 LCD 8000 installation 16 CAN LCD 8000 card 17 System Wiring 19 System Wiring example 21 CAN Bus Wiring Cables 22 LIB 8000 card 23 LIB 8000 CNU terminal Block 23 Communication lines with Detectors Modules 24 Technic...

Page 4: ...lease consult NOTIFIER Technical Service for any doubt This system like all solid state components may be damaged by induced electrostatic voltages handles the boards keeping them among the edges and avoid to touch the electronic components An appropriate earthing connection ensures in any case a sensitivity reduction to disturbances Please consult NOTIFIER Technical Service if you cannot solve in...

Page 5: ...control unit is in conformity with the following EN54 4 requirements Function EN 54 4 reference Power supply from main source Power supply from battery source in standby Re charging and check of the battery source Power supply fault detection and signalling 5 1 5 2 5 3 5 4 EN54 EN54 2 13 7 Max 512 Sensors Manual Call Points per microprocessor The AM 8000 control unit has a maximum capacity of 636 ...

Page 6: ...rnal loads such as sirens bells etc OUTPUTS 1 Supervised Siren Output 1 General Alarm Output with contacts free from voltage 1 General Fault Output with contacts free from voltage Mechanics The control unit mechanics is suitable for wall installations Sizes 403mm L x 408mm H x 240mm P Protection grade IP 30 Operation temperature 5 C a 40 C Stockage temperature 10 C a 50 C Weight 7 5 Kg Main Functi...

Page 7: ...ats masonry walls or self tapping screws pre fabricated panels It is recommended not to install the panel near heat sources radiators etc Use screws of max 5 mm The control unit must be installed to the wall so as to allow a clear view of the display and easy access by the operator For example it allows an optimal view of the display at 1 5 m height It is recommended not to install the control uni...

Page 8: ...e PAGE 5 AM8000_manu inst Doc 160 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA Extractable labels on the front panel AM 8000 control unit is provided with extractable labels to indicate the functions Status via LED and some function buttons ...

Page 9: ... 9Vdc 4 A ripple max 500mVpp Power supply for control unit user output external load power supply Battery charger section Output voltage 27 5 Vdc 500mA Vpp max temperature compensation Output current 1 5A ca Number of batteries that can be connected 2 x 12 V min 7Ah max 27Ah max The battery charger section has the following signalling thresholds Exhausted battery threshold 21 5 Vdc Re charge Fault...

Page 10: ...tery breakdown will be indicated when their voltage is 21 5V and to prevent irreversible damages the voltage will be automatically switched off by disconnecting the batteries when the voltage is 19 5V All wirings MUST be checked BEFORE they are connected to the control unit It is recommended to perform at least the following checks Check the continuity of all cables used including the shield Ensur...

Page 11: ...ty class The mains supply conductors shall not be consolidated by means of a soft welding A sectioning device external to the control unit must be provided for the 230 Vac power cable contact separation 3 mm min The sectioning device must be omni polar or must disconnect the line phase Power Supply connection must be done following this procedure Refer to Base Board 1 Turn off the main power switc...

Page 12: ...108mA LCD not connected 1x LIB 8000 at nominal voltage 24Vdc 75mA LCD 8000 L at nominal voltage 24Vdc and full backlight 169mA if the LCD is connected to the CPU 8000 Card 218mA if LCD have remote connection by CAN LCD 8000 adaptor LCD 8000 F at nominal voltage 24Vdc and full backlight 215mA if the LCD is connected to the CPU 8000 Card 274mA if LCD have remote connection by CAN LCD 8000 adaptor ex...

Page 13: ...d USR2 The USR1 and USR2 relays are available in free voltage contacts NOTE do not connect to this output any alarm remote control such as a telephone dial EN 54 2 7 7 because the output line is not controlled Contact range max 30 VAC DC 2A Non inductive loads Selection of type of contact Normally open or Normally closed through JURS1 e JUSR2 Jumpers on board refer to basic board topography NOTE T...

Page 14: ...line ATTENTION Polarity displayed are in Alarm condition at idle condition they are inverted Sounder connection controlled output Polarized devices electronic sirens etc 47 K W 3 4 Non polarized devices Bells relays etc 47 K W 2 x 1N 4004 3 4 Sounder output operation window CNU 4 3 Siren output connections refer to basic board topography IDLE CUT SHORTCIRCUIT 21K 61K ...

Page 15: ...u inst SYSTEM COMPONENTS Black Box Each Black Box is equipped of one CPU card and can contain up to 2 Loop Interface cards LIB 8000 Each LIB card can drive up to 2 ADV loop Each ADV Loop line can connect up to 159 detector and 159 Modules in Advanced protocol or 99 99 in CLIP mode AM 8000 CPU card ...

Page 16: ...ommunication line side A for AUDIO CAN bus devices AUDIO 1 Line Can Bus with internal EOL resistor Power Supply line is protected with a 4 Fuse 19 General Fault NO NC 20 General Fault C General Fault Relay Contacts 2A 30V Normally Open or Closed selectable via JGST Jumper 21 General Alarm NO NC 22 General Alarm C General Alarm Relay Contacts 2A 30V Normally Open or Closed selectable via JALL Jumpe...

Page 17: ...ack Box n 6 ON ON ON off Black Box n 7 off off off ON off off off off Black Box n 8 Box ID proper configuration ON off off off Dip 5 ON from USB key loads configuration previously prepared by PK 8000 SW Tool Box ID proper configuration off ON off off Dip 6 ON copy the configuration in the USB memory key Box ID proper configuration off off off ON Dip 8 ON Use only by authorized Technician Note Set ...

Page 18: ...0 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA NOTE The two CPU cards of the two available LCD models LCD 800 F and LCD 8000 L differs in the component and in the software but maintain all end user Connectors and Dip Switches in the same positions and with the same pin out ...

Page 19: ...off LCD n 5 Normal Operation off ON ON off off LCD n 6 Normal Operation ON ON ON off off LCD n 7 Normal Operation off off off ON off off LCD n 8 Normal Operation ID proper configuration Off Off Off ON LCD n ID Use only under manufacturer autorization LCD 8000 L F installed in the Black Box front door To install the LCD on the Front Panel door Open the door Take off the plastic cover removing the f...

Page 20: ...PAGE 17 AM8000_manu inst Doc 160 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA LCD 8000 L F installed along the CAN Bus Network use CAN LCD 8000 CARD This card is necessary when the LCD is not installed in the same cabinet with the AM 8000 CPU ...

Page 21: ...er min 18Vcc a max 40Vcc must be provided Operating Temperature 5 C a 40 C Humidity Max 95 no condensation Stockage temperature 10 C a 50 C Current consumption LCD 8000 L backlight low 148mA in Normal condition 218mA in alarm condition 24Vcc LCD 8000 F full backlight 236mA in Normal condition 274mA in alarm condition 24Vcc CAN LCD 8000 16mA 24Vcc CAN LCD 8000 card CNFR 10 pins connector to connect...

Page 22: ...AM 8000 Manuale di installazione PAGE 19 AM8000_manu inst Doc 160 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA ...

Page 23: ...tion And also the Power supply connection MUST BE in the same configuration If this function is not appropriately followed it can contravene the EN54 requirements Here are some samples of the power supply and CAN bus wiring Note that Each LCD have TWO connections for the CAN Network Each LCD have TWO connections for the Power Supply CAN Bus IN OUT connections must be wired in separated path LCD Po...

Page 24: ...AM 8000 Manuale di installazione PAGE 21 AM8000_manu inst Doc 160 1 AM8000 ITA Rev A 3 NOTIFIER ITALIA System Wiring Example ...

Page 25: ...ngle pair for CAN Bus Belden 3105 A Twisted pair 22 AWG for Can Bus only Using this cable maximum distance from first to last equipment is 300 mt at maximum transmission speed of 31250 bit sec Power Supply Cable Power supply cable can be a twisted pair with copper section proportional to o the distance from first and last equipment o Number and current consumption of all devices along the line o m...

Page 26: ...iption Characteristics Note 12 Fault relay Common 11 Fault relay N C N O Max 30V 1A Select N O N C with JGST Jumper 10 Alarm Relay Common 9 Alarm Relay N C N O Max 30V 1A Select N O N C with JALL Jumper 8 Line 2 B 7 Line 2 B 6 Line 2 A 5 Line 2 A Detection LINE 2 4 Line 1 B 3 Line 1 B 2 Line 1 A 1 Line 1 A Detection LINE 1 DIP SWITCH SW1 1 2 3 4 LIB1 ON OFF OFF OFF LIB2 OFF ON OFF OFF ...

Page 27: ...f analogue line connection cables Type of cable 2 conductors for their section refer to the table below Twisted narrow pitch 5 10 cm Shielded pair cable Max admitted capacity 0 5 uF Cable section The sections are referred to the total length of the line in case of STYLE 6 loop and therefore when the loop is closed it is considered the loop length which however must not be longer than 3000 meters a...

Page 28: ...the specific device connections please refer to Analogue system device installation manual document M 199 1 SCH ITA or M 199 1 SCH ENG by Notifier Italia Example of closed line style 6 or Loop The total length of the loop couple from the Panel Loop output and input SHALL NOT exceed 3 000 mt MCP M700KI A SIDE B SIDE MCP M700KI MCP M700KI ...

Page 29: ... line Place a test prod of the tester on the line cable screen and the other test prod on the positive cable of the same line The resistance measured must be higher than 15 20 MOhm better if infinitive Perform the same operation between the line screen and negative cable Check that also in this case the resistance is higher than 15 20 MOhm Earthing lines insulation Place a test prod of the tester ...

Page 30: ...ing connection is compulsory and must be fixed to the cabinet by means of a cable fixing device so that it cannot be accidentally stripped off The power supply connection must be performed through the following phases refer to basic board topography Turn off the main switch of the 230 Vca mains which powers the control unit Disconnect the CNAL terminal block from the control unit Connect the 230 V...

Page 31: ... off General Fault relay deactivated 3 Disconnect both batteries wait not more than 2 3 minutes for the control unit to signal The indication of BATTERIES NOT CONNECTED on the display Yellow led FAULTS flashing Yellow led POWER OK on Yellow led MAINS on General Fault relay active Re connect the batteries and press the SILENCE ALARM FAULT key and check No breakdown signalling on the display Yellow ...

Page 32: ..._________ Other devices _________ _________ _________ _________ Total 4 Total x24h or x72h x 0 5 h Stand by A Ah Alarm B Ah Ah Battery A B x 1 2 5 Ah 1 Check the load for each output is within admitted limits 2 Current from loops Refer to the device manufacturer data sheet for the current necessary in normal mode Calculate the total current required for each loop by using the table 2 refer to the ...

Page 33: ...e Modules serie 700 Double Modules serie 700 Modules serie MA MMX 10 N CMX 10 R Isolation modules Addressable Sounders Power from loop Other devices N B Total must be less than 0 500 A Total loop N 2 Total loop N 2 Detectors serie NFX Detectors serie 700 MCP Single Modules serie 700 Double Modules serie 700 Modules serie MA MMX 10 N CMX 10 R Isolation modules Addressable Sounders Power from loop O...

Page 34: ...CZ 288 μA 8 8mA External Power M710E CZ 1 5 mA 8 8mA Loop Power M710E CZR 500 μA 8 8 mA External Power M710E CZR 6 5 mA 8 8 mA Loop Power ZMX 1E 200 μA 9 mA External Power IMX 1 200 μA 4 mA M710 E 310 μA 5 mA MMA1 I 400 μA 5 mA MCX 3 450 μA 5 mA M701E 310 μA 5 mA CMA1 I 410 μA 5 mA M500KA 200 μA 5 mA M700K 260 μA 5 mA M700KI 360 μA 5 mA NBG 12LX 100 μA 5 mA P700 390 μA 5 mA M720 340 μA 5 mA M721 3...

Page 35: ...e Via Telesio 15 Tel 055 696706 Fax 055 6529294 00118 Roma Via Del Casale Santarelli 51 Tel 06 7988021 Fax 06 79880250 E mail notifier roma notifier it 80143 Napoli Via G Porzio 4 Centro Direzionale Isola E2 Scala B Piano 5 int 19 Tel 081 7879398 Fax 081 7879159 E mail notifier napoli notifier it 70125 Bari Via Della Costituente 29 Tel 080 5013247 Fax 080 5648114 E mail notifier bari notifier it 9...

Reviews: