AM_8000
Programming Manual
PAGINA - 31
AM8000_manu-prog-ENG
Doc. M-160.2-AM-8000-ENG Rev A1
NOTIFIER ITALIA
Example:
G301 = TIM (
18.00 08.30)
CBE of the high sensitivity group
G302 = TIM (
08.30 18.00)
CBE of the low sensitivity group
For the Detector to which this function is to be coupled the parameter
“Daytime/Night = YES ”(refer to
Detectors programming)
must be programmed. In this way the system automatically associates the high and
low sensitivity groups, so that the following two time bands are obtained:
Daytime band (low sensitivity) from 8.30 to 18.
(the sensitivity values assumed by the detector are those
programmed in the “
Sens-Low”
item
in the option folder).
Night band (high sensitivity) from 18. to 8.30.
(the sensitivity values assumed by the detector are those
programmed in the “
Sens-High”
item
in the option folder).
Zone Menu
By selecting the
“Zones”
sub-menu you can enter a descriptive text to be associated with the selected zone.
The control unit locates by default on the first zone.
Day / Night : YES/NO
Setting “YES” this Zone will use the programmed HI-LOW sensitivity Groups ( refer to HIGH AND LOW
SENSITIVITY GROUPS above) to switch to LOW sensitivity during DAY and to HIGH sensitivity during
the Night .
Name:
Programmable text for the ZONE
max. 32 characters
To enter the Text press the enter
key
to enter
the editing function
Through the alphanumerical
keyboard enter the zone name
at the end press the enter key
to
store the datum.