AM_8000
Programming Manual
PAGINA - 9
AM8000_manu-prog-ENG
Doc. M-160.2-AM-8000-ENG Rev A1
NOTIFIER ITALIA
P
P
R
R
O
O
G
G
R
R
A
A
M
M
M
M
I
I
N
N
G
G
M
M
E
E
N
N
U
U
RECOMMENDED SEQUENCE TO PERFORM THE CONTROL UNIT PROGRAMMING
The following operation sequence is recommended to perform the initial programming of the control unit, to
prevent mistakes and consequent loss of time.
The details of each operation are pointed out in the following pages.
- Perform the wiring of the control unit lines and perform the appropriate tests as described in the
installation manual before powering the control unit.
- Make some photo-copies of the programming sheet that can be found at the end of this manual and
record on these sheets the necessary information for ALL sensors, modules, software zones, CBE and
groups.
From
the
Programming
menu select the
“System”
menu.
Select the “
Line”
item and program the type of connection
which has been performed on the installed
lines ( open line or closed loop ).
From
the
Programming
menu select
Point Programming
Select
the
Auto-Learn
item, and press the enter key
and subsequently enter the number of lines for
which the procedure must be started.
Through this operation all the devices installed on the lines are recognized and loaded in the control unit
memory according to their
Hardware TYPE ID
and
with the default data
.
At the end of the procedure
check that the devices detected by the control unit during the Auto-
Learn are those really installed
, and confirm.
This will
record all data in the Panel memory
.
In any case user can edit and modify the recorded data in case it needs.
From
the
Point Programming
menu select
“Detectors”
Associate the detector with the appropriate zone
Program the detector CBE
( Control by Event action).
From
the
Point Programming
menu select the
“Modules”
item
Program
the
Software Type-ID
(if it is different from the default value assigned )
Associate the module with the appropriate zone
Program the module CBE
( Control by Event action).
At the end of this programming steps the control unit is ready to manage the Alarm system
Additional details can be added to the mentioned, as for example a text description for each
detector, module or zone.
For further information or specific parameters description see the following paragraphs.