Honeywell NetAXS-123 Installation Manual Download Page 46

38

www.honeywell.com

Installing the NetAXS-123 Panels

Installation

Note:  

Address 0 is not a valid setting.

b. Both DIP Switch 8 and DIP Switch 9 need to be either ON or OFF to be properly 

configured.

Table 9:  

NetAXS-123 SW2 DIP Switch Settings

S1

a

S2

a

Selection

OFF

OFF

RS-485_2 termination (EOL) DISABLED

ON

ON

RS-485_2 termination (EOL) ENABLED (FUTURE) (Default)

a. Both DIP Switch 1 and DIP Switch 2 need to be either ON or OFF to be properly 

configured.

Note

: When you use the DIP switches to reset a panel to the original factory default 

values, the Event History is lost and any customized databases are removed, so the 
panel is reset with the original factory default database. This does not affect the 
Ethernet IP address.
You can also use this ASCII command:

_I=pn_R

 

This command resets the panel to the original factory default values, but it only 
removes the customized databases and restores the original factory default 
database. The Event History is retained.

To reset the panel to the factory default values:

1. Make a note of the existing settings on SW1 DIP switches.

2. While the panel is powered up, turn all DIP switches to the OFF position.

3. Power down, then power the panel back up.

4. Wait for the panel to come up. The RUN LED should flicker fast.

5. Set the DIP switches back to their original positions.

6. Power down, then power the panel back up. 

7. After the the panel comes up, the RUN LED should flash normal.

The panel is now reset to the original factory default values.

Summary of Contents for NetAXS-123

Page 1: ...May 2010 2010 Honeywell All rights reserved 800 05779 Revision A NetAXS 123 Access Control Unit Installation Guide ...

Page 2: ...es of America Honeywell reserves the right to change any information in this document at any time without prior notice Ordering Information Please contact your local Honeywell representative or visit us on the web at www honeywellaccess com for information about ordering Feedback Honeywell appreciates your comments about this manual Please visit us on the web at www honeywellaccess com to post you...

Page 3: ...5 Suppressors 10 3 0 Installation 11 3 1 Installing the Compact Enclosure Panel 11 Installing on a Wall 11 Installing over a Gang Box 15 Installing on a Flat Surface 16 3 2 Installing the Standard Enclosure Panel 17 3 3 Installing the Add On Board 26 3 4 Wiring the Readers 29 3 5 Wiring Door Strikes 33 3 6 Setting DIP Switches and Jumpers 35 Controller Board DIP Switch and Jumper Settings 35 Add O...

Page 4: ...etAXS 123 Access Controller Panel Connection Detail 57 4 10 NetAXS 123 NetAXS 123 Access Controller Panel Connection Detail 58 4 11 Mixed Loops 59 5 0 Hardware Specifications 60 5 1 Relay Contacts 60 5 2 Reader Interface 60 5 3 Maximum Output Loading 60 5 4 PoE Power Limitations 60 5 5 Mechanical 61 5 6 Environment 62 5 7 Cable 62 6 0 Basic Standalone Operation 63 6 1 Card Read Door Lock Operation...

Page 5: ...tion via N 485 PCI 3 45 Figure 10 RS 485 Configuration via NetAXS 123 Gateway 46 Figure 11 Ethernet TCP IP Configuration 47 Figure 12 Ethernet Connection 48 Figure 13 NetAXS 123 USB Connection 49 Figure 14 RS 485 Connection via PCI 3 50 Figure 15 RS 485 Connection via NetAXS 123 51 Figure 16 RS 485 Connection via NetAXS 123 with Multidrop Panels at Both Ends 52 Figure 17 RS 485 Connection via PCI ...

Page 6: ...vi www honeywell com ...

Page 7: ... Output Options 7 Table 4 Readers Supported by NetAXS 123 8 Table 5 Factory Default Configuration Settings for Door 1 30 Table 6 Factory Default Configuration Settings for Door 2 31 Table 7 Factory Default Configuration Settings for Door 3 32 Table 8 NetAXS 123 SW1 DIP Switch Settings 36 Table 9 NetAXS 123 SW2 DIP Switch Settings 38 Table 10 Reader Wiring 62 Table 11 Troubleshooting Problems and S...

Page 8: ...viii www honeywell com ...

Page 9: ...ocument 800 05779 Revision A 1 Installing the NetAXS 123 Panels In this chapter Introduction 2 Panel Components and Descriptions 3 Installation 11 System Configuration 48 Hardware Specifications 60 Maintenance 64 Troubleshooting 65 Technical Support 66 ...

Page 10: ...nd access privileges An access control system consists of hardware and software usually configured in a network environment over a standard network protocol Access control units readers door strikes and video and other devices for example are configured to control and monitor the access to a company site 1 2 NetAXS 123 Overview A NetAXS 123 access control is a full featured one door web based acce...

Page 11: ...ot cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation The NetAXS 123 panel consists of a web browser enabled controller a one or two door add on board that supports additional inputs and outputs a power over Ethernet PoE power supply NetAXS 123 Compact only and a battery NetAXS 123 Standard only The following...

Page 12: ...igure 2 NetAXS 123 Standard Enclosure Panel Wiring and Components Note Maintain at least a 25 inch distance between the non power limited wiring 115 VAC 60 Hz input wiring power line filter wiring and battery backup charger wiring and all other wiring which is power limited Class 2 wiring ...

Page 13: ...5 Figure 3 NetAXS 123 Add On Board Wiring and Components 2 1 Supervised Input Wiring The supervised inputs are located on the following terminal blocks Table 1 Supervised Input Terminal Blocks Board Configuration Terminal Block 1 Door Controller Board C TB2 C TB10 1 Door Add On Board IO TB2 2 Door Add On Board IO TB2 as 1 door Add On Board IO TB6 ...

Page 14: ...am The figure above shows standard 2 200 ohm resistors The NetAXS 123 panel accepts 1 000 2 200 4 700 or 10 000 ohm values Note that both resistors must have the same value In addition the Reader tampers can be supervised and capable of being used as additional inputs if the default functionality is not needed The wire used for the inputs should be shielded and cannot exceed 30 ohms over the entir...

Page 15: ...ate supervision Normal Alarm Short and Cut One input is used for request to exit on each door and one input is used for door status on each door Supervised inputs for External Power Fail and Reader Tampers are supplied as well and they can be used as additional inputs when not required for their default purpose 2 2 1 NetAXS 123 Add On Board The NetAXS 123 Add On Board enables you to expand from on...

Page 16: ...umber OmniProx OP 10 OP10GENE OP10HONE OP 30 OP30GENE OP30HONE OP 40 OP40GENE OP40HONE OP 45 OP45GENE OP45HONE HID ProxPoint Plus 6005B MiniProx HU 5365EGP00 Thinline II HU 5395CB100 HU 5395CG100 HU 5395CK100 ProxPro HU 5355AGN00 ProxPro II HU 5455BGN00 ProxPro K HU 5355AGK00 EntryProx 4045CGNU0 MaxiProx HU 5375AGN00 Omni Class OM40 OM40BHONB OM40GHONB OM41 OM41BHONB OM41GHONB OM55 OM55BHONB OM55G...

Page 17: ...on current limits using PoE The Standard Enclosure uses a 12VDC 4A power supply with an international input of 100VAC to 240VAC The supply also charges and monitors the condition of the battery Wire the unswitched electrical power to the supply per the National Electrical Code as well as any local electrical codes including the safety ground wire An input power indicator is supplied and it is illu...

Page 18: ...tandby backup power depending upon system configuration and activity When AC is lost the power supply automatically switches to the backup battery for continuous 12VDC power Replace the battery every 2 to 2 5 years or more often if the system has a high rate of backup use 2 5 Suppressors Two suppressors HAS number S 4 are required for each door lock One suppressor is installed on the panel control...

Page 19: ...he panel to ensure protection from Electrostatic Discharge ESD 3 1 1 Installing on a Wall 1 Review the panel layout cable runs and power needs 2 Mount the enclosure s back at the proper location on the wall a Drill the screw holes in the wall using the panel s back as a template and then pull the power and all I O wires to the enclosure and through the knockout holes and properly mark each wire fo...

Page 20: ... honeywell com Installing the NetAXS 123 Panels Installation 3 Mount the board onto the back of the panel 4 Choose the tamper type standard or off the wall tamper and wire the tamper Wiring a standard tamper ...

Page 21: ... Installation NetAXS 123 Access Control Unit Installation Guide Document 800 05779 Revision A 13 Wiring an off the wall tamper 5 Set the tamper using pliers at the four locations indicated below Warning Do not apply power at this time ...

Page 22: ...dress communication termination and biasing See DIP Switch Settings page 36 8 Check all wiring at this time Caution Improper wiring can cause damage to the NetAXS 123 at power up and result in a loss of warranty 9 Apply power to the panel 10 Check for the Run LED for a successful power up If the LED is blinking green the panel is powered up successfully 11 Close the cover ...

Page 23: ... over a Gang Box 1 Review the panel layout cable runs and power needs 2 Mount the back of the panel on the gang box 3 Pull the wires from the gang box through the knockout holes in the base of the enclosure 4 Perform steps 3 through 10 in the preceding section Installing on a Wall page 11 to complete the installation of the panel over a gang box ...

Page 24: ...ayout cable runs and power needs 2 Mount the back of the enclosure on the surface either with drywall screes or threaded wall anchors 3 Break off the appropriate plastic wiring tabs using pliers 4 Perform steps 3 through 10 in Installing on a Wall page 11 to complete the installation of the panel over a horizontal surface ...

Page 25: ... 2 Installing the Standard Enclosure Panel Perform the following steps to install the NetAXS 123 Standard Enclosure panel Warning Use a static strap whenever touching the panel to ensure protection from Electrostatic Discharge ESD 1 Optional Remove the green ground wire and the door 2 Partially install the four power supply screws ...

Page 26: ...s Installation 3 Install the power supply a Fit the power supply screws through the key holes in the left side of the cabinet and seat the power supply by pulling down b From the outside of the cabinet tighten the screws to lock the power supply in place ...

Page 27: ...ol Unit Installation Guide Document 800 05779 Revision A 19 c Inside the cabinet screw in the two self tapping screws supplied in the product box at the top and bottom of the power supply Warning These screws must be installed to ground the power supply to the enclosure ...

Page 28: ...20 www honeywell com Installing the NetAXS 123 Panels Installation d Plug the connector that is attached to the blue and brown wires into the power supply ...

Page 29: ...e sure the power cable is disconnected from the external power source before following this step Through the bottom conduit knockout which directly connects AC power to the terminal block Through the side conduit knockout which also directly connects AC power to the terminal block Through the optional AC input receptacle Note the brown and blue wires must be twisted together from the point of entr...

Page 30: ...22 www honeywell com Installing the NetAXS 123 Panels Installation 5 Use a pencil to mark the location of the holes on the wall 6 Screw the NetAXS 123 Controller Board with the four captive screws ...

Page 31: ...Revision A 23 7 Hold the Add On Board over the Controller Board and seat the board to board connector into the Controller Board Secure the Add On Board onto the Controller Board with the four captive finger screws For more explanation of the Add On Board installation see the next section Installing the Add On Board ...

Page 32: ...anels Installation 8 Connect the wiring harness as shown Warning DO NOT CONNECT the AC power or the battery wires yet 9 Power up the NetAXS 123 Controller Board and configure the system Refer to the NetAXS 123 Startup Guide 800 05780 for instructions ...

Page 33: ...S 123 Panels Installation NetAXS 123 Access Control Unit Installation Guide Document 800 05779 Revision A 25 10 Connect the battery 11 Attach the door to the cabinet 12 Re connect the green ground wire to the cabinet door ...

Page 34: ... Add On Board Warning To prevent damage to the NXC1 Controller Board remove power from the NetAXS 123 panel before installing or removing a NetAXS 123 Add On Board 1 On the NetAXS 123 Controller Board locate the four posts called out in the image shown below NetAXS 123 Controller Board ...

Page 35: ...Revision A 27 2 Pick up the Add On Board and notice the four posts on the bottom 3 Seat the Add On Board posts into the four posts on the NetAXS 123 Controller Board aligning the terminal block edge of the Add On Board with the terminal block edge of the Controller Board 4 With your fingers tighten the posts screws ...

Page 36: ...Use the following figure to locate the jumpers b See Add On Board DIP Switch and Jumper Settings page 40 to set the power source 12VDC power or external power and the relay contact position Normally Open or Normally Closed 6 Wire the door strikes See Wiring Door Strikes page 33 for instructions ...

Page 37: ...h can be disruptive The maximum recommended length of wiring is 500 feet per reader Figure 5 shows a one door panel with the readers wired to terminal blocks C TB3 and C TB4 on the Controller Board and to terminal blocks IO TB3 IO TB4 IO TB7 and IO TB8 on the Add On Board The wires are color coded to their labeled terminals If this were a two door panel the two additional readers would be wired to...

Page 38: ...nput 1 Door 1 Egress C TB2 IN1 REX Input 1a Input 1a Door Status Input 2 Door 1 Status C TB2 IN2 STS Input 2a Input 2a Reader Tamper Input 3 Door TMPR A C TB3 TMPR A Input 3 Reader Tamper Input 4 Door TMPR B C TB4 TMPR B Input 4 General Input 5 GENERAL PURPOSE C TB10 IN5 Input 5 Power General Input 6 POWER C TB10 IN6 PWR FAIL Input 6 Panel Tamper PANEL TAMPER ALTER_T MPR Input 20 Output Lock Relay...

Page 39: ...used for the readers inputs and outputs when either a 1 or 2 door Add On Board is attached to the board to board connector on the Controller Board Table 6 Factory Default Configuration Settings for Door 2 a Readers A and B share the same connection Type Purpose Web Default Name Terminal Block Label Reader A Reader B Other Input Egress Request to Exit REX Input 9 Door 2 Egress IO TB2 IN9 REX Input ...

Page 40: ...associated reader LEDs Incorrect wiring of the reader to the panel can cause the panel to abnormally stop operating or to operate erratically Type Purpose Web Default Name Terminal Block Label Reader A Reader B Other Input Egress Request to Exit REX Input 9 Door 2 Egress IO TB2 IN9 REX Input 9a Input 9a Door Status Input 10 Door 2 Status IO TB2 IN10 STS Input 10a Input 10a Reader Tamper Input 11 D...

Page 41: ...for two seconds after a valid card read Although readers operate similarly LED control can vary depending on the manufacturer Therefore your readers may require some testing to identify the right LED wire when the reader uses Dual LED wires If you are using Dual Line LED control it s recommended that you try the ORANGE colored wire for a GREEN LED The Reader Buzzer feature is not currently support...

Page 42: ...l for the On Board option should not be connected Similarly on the External Power Supply side the Return terminal should not be connected The On Board option is used when jumpers are set for 12VDC The External Power Supply options is used when the jumpers are set to External Power see Jumper Settings page 39 for details Return Dry C NO NC Locking Device Return Dry C NO NC Locking Device DC OR On B...

Page 43: ...ation Guide Document 800 05779 Revision A 35 3 6 Setting DIP Switches and Jumpers 3 6 1 Controller Board DIP Switch and Jumper Settings Figure 6 locates the NetAXS 123 DIP switch panel and the output 1 and output 3 relay jumpers Figure 6 Controller Board DIP Switch and Jumper Location ...

Page 44: ...OFF Address 3 OFF OFF ON OFF OFF Address 4 ON OFF ON OFF OFF Address 5 OFF ON ON OFF OFF Address 6 ON ON ON OFF OFF Address 7 OFF OFF OFF ON OFF Address 8 ON OFF OFF ON OFF Address 9 OFF ON OFF ON OFF Address 10 ON ON OFF ON OFF Address 11 OFF OFF ON ON OFF Address 12 ON OFF ON ON OFF Address 13 OFF ON ON ON OFF Address 14 ON ON ON ON OFF Address 15 OFF OFF OFF OFF ON Address 16 ON OFF OFF OFF ON ...

Page 45: ...ss 29 OFF ON ON ON ON Address 30 ON ON ON ON ON Address 31 OFF Downstream Panel ON Gateway Panel Default OFF Uses the User Provided Ethernet IP address Default ON Uses the Default Ethernet IP Address 192 168 1 150 OFF OFF RS 485_1 termination EOL DISABLED Default ON ON RS 485_1 termination EOL ENABLED Default OFF Future Use Default ON Future Use a DIP Switch 7 does NOT require a panel reboot to ta...

Page 46: ...he original factory default database This does not affect the Ethernet IP address You can also use this ASCII command _I pn_R This command resets the panel to the original factory default values but it only removes the customized databases and restores the original factory default database The Event History is retained To reset the panel to the factory default values 1 Make a note of the existing ...

Page 47: ...d on board 12V power to be applied to the relay contact load The other jumper is used to select Normally Open NO or Normally Closed NC relay contacts There is a total of four 3 pin jumpers two per relay on the Controller Board Figure 7 NetAXS 123 Controller Board Jumpers Each relay is associated with two jumpers As shown below a relay s left jumper configures the relay s load source 12VDC or Exter...

Page 48: ...r Location Note The figure above shows a one door Add On Board configuration If you are instead using a two door Add On Board you will see an additional two relays and their corresponding jumper sets to the right of the relays shown The additional relays and jumpers will configure output 11 and output 13 and all of the jumpers are configured in the same manner The NetAXS 123 Controller Board provi...

Page 49: ...05779 Revision A 41 used to select Normally Open NO or Normally Closed NC relay contacts There is a total of four 3 pin jumpers two per relay on the controller board Setting the jumpers to configure the power source Setting the jumpers to configure the relay position 12V External Normally Open Normally Closed ...

Page 50: ...croUSB B cable that is supplied with the panel You will need to install a USB driver to support the connection Follow these steps Warning Do NOT connect the USB cable to the panel until AFTER the drivers are installed 1 Insert the NetAXS 123 Product CD into your Windows based computer The NetAXS 123 product menu opens in the web browser Note If the product menu does not open automatically in your ...

Page 51: ...ck Install USB Drivers on the product menu to start the USB driver installation wizard 3 Click Next to display the Ready to Install the Program screen Note If confirmation dialog boxes pop up before or during the installation click the appropriate boxes to allow or approve the installation 4 Click Install to initiate the installation ...

Page 52: ...ring of a Multidrop communication network of up to 4 000 feet 1200 m in length Only one host converter device per dropline is supported Note NetAXS 123 must be the Gateway panel on an existing NetAXS loop The NetAXS 123 panel cannot be placed as a Downstream panel when the Gateway is a NetAXS system DIP switch position 6 on the NetAXS 123 panel selects whether the panel is a Gateway or Downstream ...

Page 53: ...set the same Note that biasing and termination on both ends are present Use the SW1 positions 8 and 9 ON on both ends of the RS 485 network Note For more information on end of line EOL termination contact Honeywell technical support Note If an RS 485 network has a NetAXS 123 Gateway panel no N1000 II N1000 III N1000 IV or NS2 are allowed on the same network If they are added to a network with a Ne...

Page 54: ...s Installation Figure 10 RS 485 Configuration via NetAXS 123 Gateway This configuration supports a total of 31 NetAXS and NetAXS 123 panels per Multidrop line Reader 4 Reader 3 Reader 4 Reader 1 NetAXS 123 Gateway Terminal Ethernet RS 485 Multidrop Line ...

Page 55: ...XS and NetAXS 123 panels per Multidrop line Each NetAXS 123 panel has a port for an Ethernet TCP IP interface The Ethernet TCP IP interface provides 10 100 MB Ethernet support for each panel Reader 1 Reader 4 Reader 1 Reader 3 Reader 1 Reader 4 NetAXS Panel NetAXS 123 Panel NetAXS Panel Reader 1 Reader 3 NetAXS 123 Gateway Terminal Network Interface Card inside PC RS 485 Multidrop Line Ethernet Up...

Page 56: ...ons 4 1 Ethernet Connection Figure 12 Ethernet Connection Note You should ground each NetAXS 123 Standard Metal Enclosure panel individually with an Earth Ground NIC 100BaseT CAT 5 328 Ft Max EG EG EG EG DIP Switch Settings S1 S5 Panel Address S6 OFF S7 OFF S8 S9 ON 485 Termination ON DIP Switch Settings S1 S5 Panel Address S6 OFF S7 OFF S8 S9 ON 485 Termination ON NetAXS 123 Panel ...

Page 57: ...ation Guide Document 800 05779 Revision A 49 4 2 USB Connection Figure 13 NetAXS 123 USB Connection Note The USB connection is intended to be used for system maintenance and troubleshooting Note You should ground each NetAXS 123 Standard Metal Enclosure panel individually with an Earth Ground ...

Page 58: ... be wired in interior as well as in endpoint positions See Figure 16 on page 52 and Figure 17 on page 53 Figure 14 RS 485 Connection via PCI 3 Note If you use the PCI 3 connection you cannot access the web since the PCI 3 does not support the NetAXS 123 web interface Only Earth Ground EG one side of cable See RS 485 Cable note S2 ON S3 ON Terminal RS 232 50 Ft Max RS 485 4000 Ft Max EG EG EG NetAX...

Page 59: ...ment 800 05779 Revision A 51 4 4 RS 485 Connection via NetAXS 123 This connection supports a total of 31 NetAXS 123 panels including the Gateway for each drop line Figure 15 RS 485 Connection via NetAXS 123 Note You should ground each NetAXS 123 Standard Metal Enclosure panel individually with an Earth Ground ...

Page 60: ... at Both Ends of the Cable You can connect Multidrop panels at both ends of an RS 485 cable via either a NetAXS 123 panel or a PCI 3 device Figure 16 RS 485 Connection via NetAXS 123 with Multidrop Panels at Both Ends Note You should ground each NetAXS 123 Standard Metal Enclosure panel individually with an Earth Ground ...

Page 61: ...rth Ground COM Port See RS 485 Cable Note EG EG Only Earth Ground EG one side of cable RS 485 4 000 Ft RS 232 50 Ft Max EG EG Only Earth Ground EG one side of cable EG PCI3 DIP Switch Settings S1 S5 Panel Address S6 OFF S7 OFF S8 S9 OFF 485 Termination OFF DIP Switch Settings S1 S5 Panel Address S6 OFF S7 OFF S8 S9 ON 485 Termination ON DIP Switch Settings S1 S5 Panel Address S6 OFF S7 OFF S8 S9 O...

Page 62: ...arth Ground EG each NetAXS enclosure Individually Analog Phone Line Dedicated analog phone Remote DIP Switch Settings 1 3 8 ON 2 4 5 6 7 OFF DB 9 DB 25 Connectors Female Male 1 13 14 25 1 13 14 25 1 5 6 9 1 5 6 9 Female 9 Pin Male 25 Pin RX 2 3 RX TX 3 2 TX Comm 5 7 Comm Only Earth Ground EG one side of cable Terminal RS 485 Cable NetAXS 123 Panels C TB9 A C TB9 B C TB9 COM 4 000 ft 1 200 m max 24...

Page 63: ...NetAXS 123 Access Control Unit Installation Guide Document 800 05779 Revision A 55 4 7 Fiber Converter to RS 485 Connection via PCI 3 This connection supports 31 NetAXS 123 panels for each drop line Figure 19 Fiber Converter to RS 485 Connection via PCI 3 ...

Page 64: ...iber Converter to RS 485 Connection via NetAXS 123 This connection supports 31 NetAXS 123 panels for each drop line Figure 20 Fiber Converter to RS 485 Connection via NetAXS 123 Note You should ground each NetAXS 123 Standard Metal Enclosure panel individually with an Earth Ground ...

Page 65: ... Configuration NetAXS 123 Access Control Unit Installation Guide Document 800 05779 Revision A 57 4 9 N 485 PCI 3 NetAXS 123 Access Controller Panel Connection Detail Figure 21 N 485 PCI 3 NetAXS 123 Access Controller Panel Connection Detail ...

Page 66: ...485 4 000ft 1 200m max 24AWG 2twistedpairswith shield 120ohm 23pf HASpartno NCP2441 TN DIP Switch Settings S1 S5 Panel Address S6 ON GATEWAY S7 OFF S8 S9 ON 485 Termination ON DIP Switch Settings S1 S5 Panel Address S6 ON GATEWAY S7 OFF S8 S9 ON 485 Termination ON DIP Switch Settings S1 S5 Panel Address S6 OFF S7 OFF S8 S9 OFF 485 Termination OFF 485 485Com 485 DC Out A B COM 24VDC in NetAXS 123 C...

Page 67: ...nfiguration NetAXS 123 Access Control Unit Installation Guide Document 800 05779 Revision A 59 4 11 Mixed Loops This mixed loop configuration supports a combined total of 31 N1000 III N1000 IV NetAXS NetAXS 123 and NS2 panels per Multidrop line ...

Page 68: ...m current per reader port for any of the three reader outputs is 500mA Maximum current for any of the six relay outputs on the Songchuan 892N 1CH 1F V is 3A at dry contact or 0 5A at self whetted Maximum battery charge current for the battery wired in series is 250mA External power on C TB9 is limited to 1 5A 12VDC 5 4 PoE Power Limitations If you are using the NetAXS 123 Standard Enclosure and po...

Page 69: ...line losses by using either of the following methods Connecting the NetAXS 123 panel to the power injector or PoE switch with the shortest possible Ethernet cable length Using a high power 802 3at power injector or PoE switch with a voltage of 56VDC This reduces line losses and thus increases available power at the NetAXS 123 panel Note The NetAXS 123 panel will not benefit from the increased powe...

Page 70: ...5C storage Humidity 5 to 85 RHNC 5 7 Cable Use industry standard cables that meet the following specifications Table 10 Reader Wiring Cable Specifications Description AWG Maximum Distance Feet Meters Readers 6 Conductor Shielded 18 500 153 Alarm Input Twisted Pair Shielded 18 2 000 610 Relay Outputs Twisted Pair Shielded 18 2 000 610 ...

Page 71: ...y associated with the particular reader input The card is valid when it is in the card database on the panel and the current time and date conforms to the time zone associated with the card If it is not a valid card the door relay remains locked 6 2 Door Egress Door Lock Door Status Operation 1 Activate the door egress input 2 The panel energizes the door relay associated with the particular door ...

Page 72: ... AC power Note The power supply contains no serviceable parts There is no replaceable fuse inside the power supply Use the following procedure to change the 1A 250V Bussan type GMA fuse in the power inlet terminal block Warning Be sure to disconnect the AC power before removing the fuse holder from the power inlet terminal block Warning To reduce the risk of fire replace the fuse only with a 1A 25...

Page 73: ...etting and reapply the power Note that if the panel is normally not a Gateway on a Multidrop communication bus then the Host RS 485 connection C TB9 should also be disconnected while DIP switch 6 is ON After completion of the Ethernet session turn off the power including the battery change the switch setting re connect the Host RS 485 terminal block and re apply the power The panel address is unkn...

Page 74: ...nels Technical Support 9 0 Technical Support 9 1 Normal Support Hours Monday through Friday 7 00 a m to 7 00 p m Central Standard Time CST except company holidays 800 323 4576 9 2 Web For technical assistance please visit http www honeywellaccess com ...

Page 75: ...Installing the NetAXS 123 Panels Technical Support NetAXS 123 Access Control Unit Installation Guide Document 800 05779 Revision A 67 This page is left blank for printing purposes ...

Page 76: ...ems 135 W Forest Hill Avenue Oak Creek WI 53154 United States 800 323 4576 414 766 1798 Fax www honeywellaccess com Specifications subject to change without notice Honeywell All rights reserved Document 800 05799 Revision A ...

Reviews: