
32
www.honeywell.com
Installing the NetAXS-123 Panels
Installation
Table 7
lists the factory Add-On Board default settings for a door 3. These mappings should be used
for the readers, inputs, and outputs when either a 1- or 2-door Add-On Board is attached to the
board-to-board connector on the controller board.
Table 7:
Factory Default Configuration Settings for Door 3
a
Readers A and B share the same connection.
Notes:
• Reader LEDs, while they are outputs, should never be used to control anything other than their
associated reader LEDs.
• Incorrect wiring of the reader to the panel can cause the panel to abnormally stop operating or
to operate erratically.
Type
Purpose
Web
Default
Name
Terminal
Block
Label
Reader A
Reader B
Other
Input
Egress/
Request to
Exit (REX)
Input 9:
Door 2
Egress
IO-TB2
IN9 (REX)
Input 9
a
Input 9
a
Door Status
Input 10:
Door 2
Status
IO-TB2
IN10 (STS)
Input 10
a
Input 10
a
Reader
Tamper
Input 11:
Door
TMPR-A
IO-TB3
TMPR A
Input 11
Reader
Tamper
Input 12:
Door
TMPR-B
IO-TB4
TMPR B
Input 12
Output
Lock Relay
Output #11
IO-TB5
LOCK
Output 11
a
Output 11
a
Reader LED
Output #12
IO-TB7
LED
Output 12
a
Output 12
a
AUX Relay
Output #13
IO-TB5
AUX
Output 13
Reader
Buzzer
Future
Feature
IO-TB7
BZR
Output 14
a
Output 14
a
Summary of Contents for NetAXS-123
Page 6: ...vi www honeywell com ...
Page 8: ...viii www honeywell com ...