8.7.3 Alarm Thresholds / Hysteresis
For each measuring point four alarm thresholds are available for free definition. If the gas concentration is
higher than the set alarm threshold, the associated alarm is activated. If the gas concentration falls below the
alarm threshold minus the hysteresis the
alarm is reset again. In the mode “Alarm at falling” the corr
esponding
alarm is set in case of falling below the set alarm threshold and reset again when exceeding the threshold plus
hysteresis.
The presentation of the alarm thresholds depends on the set measuring range: See chapter Gas Type and
Measuring Range.
The alarm thresholds are freely selectable in the range from 0 to 100 % of the measuring range.
The alarm threshold is
only stored, if the value is ≥
than the lower alarm threshold
Unused alarm thresholds have to be defined with 0, in order to avoid undesired alarms.
Higher-level alarms automatically activate the lower-level alarms.
Lowest hysteresis: 3 % of the lowest alarm threshold
Highest hysteresis: 50 % of the lowest alarm threshold
Symbol Description
Default Function
C
Evaluation
C
C = Alarm evaluation with current value of MP
A = Alarm evaluation with average value of MP
10 %
LEL
Threshold 1
Threshold 2
Threshold 3
Threshold 4
Hysteresis
XX
XX
XX
XX
XX
Gas concentration > Threshold 1 = Alarm 1
Gas concentration > Threshold 2 = Alarm 2
Gas concentration > Threshold 3 = Alarm 3
Gas concentration > Threshold 4 = Alarm 4
Gas concentration < (Threshold X
–
Hysteresis) = Alarm X OFF
= Alarm release at increasing concentrations
= Alarm release at falling concentrations
Alarm Threshold 1
C 10.0 % LEL
↗
Alarm Threshold 2
C 20.0 % LEL
↗
Alarm Threshold 3
C 0.0 % LEL
↗
Alarm Threshold 4
C 0.0 % LEL
↗
Hysteresis
1.0 % LEL