Honeywell Modutrol IV Interface Modules Q7130A Installation Instructions Manual Download Page 6

Q7130A, Q7230A, Q7330A MODUTROL IV INTERFACE MODULES

63-2235—07

6

(+) and (-) denotes terminals on the controller

Q7330A Adjustments (Fig. 9 and Table 4)

The Q7330A provides control interface for W936 and W945 

controllers. This module consists only of the terminal block 

and does not require any adjustments. See Fig. 9 for 

terminals.

After the motor stroke is adjusted (if necessary), simply plug 

the module onto the motor quick-connect terminals and 

secure to the motor. See Fig. 10 for typical system wiring.

To check proper motor operation:

1.

Provide power to the motor.

2.

Jumper terminals 1 and 2 to drive motor open (clock-

wise

 as viewed from power end).

3.

Jumper terminals 1 and 3 to drive motor closed. Con-

nect field wiring to appropriate screw terminals.

Fig. 9. Q7330A terminals.

Fig. 10. Typical wiring diagram for Q7330A Interface 

Module and M91XX Modutrol IV Motor.

Table 3. Q7230/M91XX Checkout Procedure.

Step

Proper Motor Response Switch in 

Clockwise Position

Switch in Counterclockwise Position

1.

Open terminals (+), (-), F

Motor closes fully ccw

Motor opens fully cw

2.

Jumper F to (-)

Motor opens fully cw

Motor closes fully ccw

3.

Remove either T terminal

Spring return motors return to normal spring position (fully ccw

 for 

mechanically normally closed motors, fully cw

 for mechanically normally 

open motors).

M27214

T1 T2

4

3

1

2

4

L1
(HOT) L2

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQURED.

SEE APPROPRIATE SYSTEM CONTROL INSTRUCTIONS
FOR CONNECTIONS TO CENTRAL PROCESSOR.  
(LABELED E1 ON W936 OR T1 ON W945).

FIVE PERCENT CARBON RESISTOR.  VALUE VARIES WITH
NUMBER OF MOTORS PARALLELED (1000 OHMSÐ2 MOTORS,
820 OHMSÐ3 MOTORS.

AUTHORITY OF MINIMUM POSITION POTENTIOMETER IF USED,
INCREASES WITH NUMBER OF MOTORS PARALLELLED (135
OHMS ON MOTORÐ50 PERCENT STROKE, ON 2 MOTORSÐ
100 PERCENT STROKE, ON 3 MOTORSÐ150 PERCENT STROKE).

USE AUXILIARY END OF M9185 TO REPLACE M945B; M745D
MOTORS TO SPRING RETURM TO THE NORMALLY OPEN
POSITION.

1

M487C

1

5

2

3

4

T1

T2

1

2

3

4

T1

T2

1

2

3

4

T1

T2

1

2

3

4

OPTIONAL
MINIMUM 
POSITION
POTENTIOMETER

CHANGEOVER
CONTROLLER

3

ELECTRONIC
MODULATING
DAMPER MOTORS

ELECTRONIC
CENTRAL PROCESSOR

1

2

3

2

5

Summary of Contents for Modutrol IV Interface Modules Q7130A

Page 1: ...ure provides easy handling and protection for circuitry Q7130A provides selectable voltage range 4 7 6 9 or 10 5 13 5 Vdc Adapts M91XX Modtrol IV Motor to function as M71XX model for M734H J M744D M745G P replacements Includes reversing switch to allow replacement of electrically normally open or electrically normally closed motors Q7230A provides current or voltage control 4 20 mA and 2 10 Vdc wi...

Page 2: ...r applications Module controls only one motor See Table 1 Electrical Ratings Input Voltage 24 Vac 50 60 Hz Power Consumption 2 VA Input Impedance Q7130A 100k ohms Q7230A voltage input 100k ohms current input 67 ohms Temperature Rating 40 F to 150 F 40 C to 66 C Dimensions See Fig 1 Fig 1 Q7130 Q7230 Q7330 Modutrol IV Interface Module dimensions in in mm a Refer to customer honeywell com for cross ...

Page 3: ...om the motor 4 If motor has an internal transformer make sure trans former is not powered and disconnect secondary wires from T1 and T2 terminals Clip quick connect termina tions from transformer secondary brown wires Trim 1 8 to 1 4 in 3 to 6 mm of insulation from the ends of the wire Tin wire ends with solder 5 Plug terminal block onto quick connect terminals inside wiring box 6 Connect field wi...

Page 4: ... motor starts to open 8 Turn the zero potentiometer slowly clockwise until the motor is fully closed This is defined as the zero setting 9 Set the controller to output the signal required to drive the motor to the fully open position Wait for the motor to stop driving open 10 Turn the span potentiometer slowly clockwise until the motor starts to drive closed The difference between the fully open p...

Page 5: ...MOTOR 1 PROPORTIONS BETWEEN 4 AND 12 mA FULLY CLOSED AT 4 mA FULLY OPENED AT 12 mA MOTOR 2 PROPORTIONS BETWEEN 8 AND 16 mA FULLY CLOSED AT 8 mA FULLY OPENED AT 16 mA MOTOR 3 PROPORTIONS BETWEEN 12 AND 20 mA SIGNAL FULLY CLOSED AT 12 mA FULLY OPENED AT 20 mA UP TO 6 MOTORS CAN BE DRIVEN SEQUENTIALY OR IN UNISON FROM ONE CONTROLLER ADJUST ZERO ADJUST AND SPAN ADJUST POTENTIOMETERS TO ACHIEVE DESIRED...

Page 6: ...unterclockwise Position 1 Open terminals F Motor closes fully ccw Motor opens fully cw 2 Jumper F to Motor opens fully cw Motor closes fully ccw 3 Remove either T terminal Spring return motors return to normal spring position fully ccw for mechanically normally closed motors fully cw for mechanically normally open motors M27214 T1 T2 4 3 1 2 4 L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OV...

Page 7: ... Fully ccw as viewed from power end Motor opens Fully cw as viewed from the power end 2 With motor powered jumper terminals 1 and 2 Motor drives open clockwise as viewed from powered end Motor drives closed counterclockwise as viewed from the power end 3 Remove either T terminal or disconnect power supply Spring return motors return to normal spring position fully ccw for mechanically normally clo...

Page 8: ...ions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 63 2235 07 T D Rev 01 11 Printed in U S A ...

Reviews: