INSTALLATION INSTRUCTIONS

Put Bar Code Here

63-2235-07

Q7130A, Q7230A, Q7330A

Modutrol IV Interface Modules

APPLICATION

The Q7130, Q7230, and Q7330 Modutrol IV Interface 

Modules are used with Series 90 Modutrol IV Motors (M91XX) 

for conversion to electronic (Series 70) control.

FEATURES

• Mounts inside the wiring box of any Series 90 Modutrol 

IV Motor (M91XX models). Module protected from 

weather by the Modutrol IV NEMA 3 wiring box.

• Mates to quick-connect terminals in motor wiring box 

and provides screw terminals for control wiring 

connections.

• Features solid state circuitry with surface mount 

components.

• Plastic enclosure provides easy handling and 

protection for circuitry.

• Q7130A provides selectable voltage range (4-7, 6-9, or 

10.5-13.5 Vdc). Adapts M91XX Modtrol IV Motor to 

function as M71XX model for M734H,J, M744D, 

M745G,P replacements. Includes reversing switch to 

allow replacement of electrically normally open or 

electrically normally closed motors.

• Q7230A provides current or voltage control (4-20 mA 

and 2-10 Vdc) with adjustable zero and span. Adapts 

the M91XX Modutrol IV Motor to function as M72XX 

model for M744S,T,Y or M745S,T,Y replacements. 

Includes reversing switch to allow replacement of 

electrically normally open or electrically normally 

closed motors.

• Q7330A is an interface to W936 and W945 controls. 

Adapts the M91XX Modutrol IV Motor to function as 

M73XX model for M734D, M744A, M745A replacements.

Q7130A

Q7230A

Q7330A

Summary of Contents for Modutrol IV Interface Modules Q7130A

Page 1: ...ure provides easy handling and protection for circuitry Q7130A provides selectable voltage range 4 7 6 9 or 10 5 13 5 Vdc Adapts M91XX Modtrol IV Motor to function as M71XX model for M734H J M744D M745G P replacements Includes reversing switch to allow replacement of electrically normally open or electrically normally closed motors Q7230A provides current or voltage control 4 20 mA and 2 10 Vdc wi...

Page 2: ...r applications Module controls only one motor See Table 1 Electrical Ratings Input Voltage 24 Vac 50 60 Hz Power Consumption 2 VA Input Impedance Q7130A 100k ohms Q7230A voltage input 100k ohms current input 67 ohms Temperature Rating 40 F to 150 F 40 C to 66 C Dimensions See Fig 1 Fig 1 Q7130 Q7230 Q7330 Modutrol IV Interface Module dimensions in in mm a Refer to customer honeywell com for cross ...

Page 3: ...om the motor 4 If motor has an internal transformer make sure trans former is not powered and disconnect secondary wires from T1 and T2 terminals Clip quick connect termina tions from transformer secondary brown wires Trim 1 8 to 1 4 in 3 to 6 mm of insulation from the ends of the wire Tin wire ends with solder 5 Plug terminal block onto quick connect terminals inside wiring box 6 Connect field wi...

Page 4: ... motor starts to open 8 Turn the zero potentiometer slowly clockwise until the motor is fully closed This is defined as the zero setting 9 Set the controller to output the signal required to drive the motor to the fully open position Wait for the motor to stop driving open 10 Turn the span potentiometer slowly clockwise until the motor starts to drive closed The difference between the fully open p...

Page 5: ...MOTOR 1 PROPORTIONS BETWEEN 4 AND 12 mA FULLY CLOSED AT 4 mA FULLY OPENED AT 12 mA MOTOR 2 PROPORTIONS BETWEEN 8 AND 16 mA FULLY CLOSED AT 8 mA FULLY OPENED AT 16 mA MOTOR 3 PROPORTIONS BETWEEN 12 AND 20 mA SIGNAL FULLY CLOSED AT 12 mA FULLY OPENED AT 20 mA UP TO 6 MOTORS CAN BE DRIVEN SEQUENTIALY OR IN UNISON FROM ONE CONTROLLER ADJUST ZERO ADJUST AND SPAN ADJUST POTENTIOMETERS TO ACHIEVE DESIRED...

Page 6: ...unterclockwise Position 1 Open terminals F Motor closes fully ccw Motor opens fully cw 2 Jumper F to Motor opens fully cw Motor closes fully ccw 3 Remove either T terminal Spring return motors return to normal spring position fully ccw for mechanically normally closed motors fully cw for mechanically normally open motors M27214 T1 T2 4 3 1 2 4 L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OV...

Page 7: ... Fully ccw as viewed from power end Motor opens Fully cw as viewed from the power end 2 With motor powered jumper terminals 1 and 2 Motor drives open clockwise as viewed from powered end Motor drives closed counterclockwise as viewed from the power end 3 Remove either T terminal or disconnect power supply Spring return motors return to normal spring position fully ccw for mechanically normally clo...

Page 8: ...ions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 63 2235 07 T D Rev 01 11 Printed in U S A ...