background image

60-2026—10    G.R. Rev. 12-00 

www.honeywell.com

Home and Building Control Home and Building Control

Honeywell

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN  55422

Scarborough, Ontario
M1V 4Z9

Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers.

TROUBLESHOOTING

WARNING

Electrical Shock Hazard.
Can cause serious injury or death.
Be extremely careful while troubleshooting the 
detector; line voltage is present on some of the 
terminals when power is on.

Open the master switch to disconnect power before 
removing or installing the detector.

Inadequate Flame Signal

If a satisfactory flame signal cannot be obtained while 
adjusting the sighting position of the detector, perform the 
procedures indicated in steps 1 through 7. If other difficulties 
are encountered in the system, refer to Troubleshooting in the 
Instructions for the appropriate Honeywell flame safeguard 
control.

1.

Check for proper line voltage. Make sure the master 
switch is closed, connections are correct, and power 
supply is the correct voltage and frequency.

2.

Check the detector wiring for defects, including:
a. incorrect connections.
b. wiring type or size of wire.
c. deteriorated wire.
d. open circuits.
e. short circuits.
f.

leakage paths caused by moisture, soot, or dirt.

3.

With the burner running, check the temperature at the 
detector.  When it exceeds 215°F (102°C) for a C7027, 
C7927 or C7044, or 250°F (121°C) for a C7035:
a. use a heat block (part no. 136733) if using a 

C7027A Flame Detector.

b. add the additional insulation between the wall of the 

combustion chamber and the detector.

c. add a shield or screen to reflect radiated heat away 

from the detector, or

d. add cooling (refer to Sight Pipe Ventilation, page 6).

4.

Remove the detector and clean the viewing window with 
a soft, clean cloth.

5.

Clean the inside of the sight pipe (if one is used) before 
reinstalling the detector.

6.

If the flame signal continues to be too low, replace the 
plug-in amplifier (if the control has one).

7.

If you still cannot obtain a proper flame signal, replace 
flame detector (C7027A, C7044A) or UV radiation 
sensing tube (C7035A).

IMPORTANT:

 At the completion of troubleshooting, be sure to 
perform the Adjustments and Checkout beginning on 
page 8.

MAINTENANCE

Periodic Maintenance

1.

Clean the viewing window and sight pipe (if used) when 
necessary. Remove the detector and use a soft, clean 
cloth to remove accumulated contaminants from the 
UV radiation sensor tube glass envelope.

2.

Ultraviolet sensing tubes have a life expectancy of 
40,000 hours of continuous use within the ambient 
temperature and voltage ratings. Replace the sensing 
tube in the C7035, or replace the C7027, C7927 or 
C7044 Detector, at appropriate intervals.

3.

Keep the flame detection system adjusted for the 
smoothest, most reliable operation as recommended by 
the burner manufacturer.

Cleaning the C7044A Detector

When necessary, clean the C7044 Flame Detector by using 
the following procedure:

1.

Loosen the two screws holding the C7044 mounting 
bracket to the blast tube. To remove, twist the bracket 
and detector. Do not loosen the clamp screw that holds 
the mounting bracket to the detector.

2.

Clean the viewing window with a soft, clean cloth.

3.

Insert the detector into the mounting hole, and to realign 
it, twist against the mounting screws. Tighten the two 
mounting screws.

Summary of Contents for Minipeeper C7027A

Page 1: ...nting on a one inch sight pipe C7035A housing meets Underwriters Laboratories Inc requirements for rain tightness and complies with NEMA enclosure standards types 4 and 4X C7044A mounts with a two screw bracket The UV sensor tube is enclosed in a stainless steel housing C7044A has the capability of side or end viewing in flame monitoring applications Because of their compact size the C7027A and C7...

Page 2: ... rated for 221 F 105 C C7027A1064 has 24 ft 7 32 m leadwires Rear of detector has a clamp type connector for 1 2 in flexible metallic conduit Models are available with 1 2 in internally threaded spud connector instead of the clamp C7027A1114 has 44 in 1 118 m leadwires and 22 in 558 mm flexible conduit Dimensions See Fig 1 Replacement Part 129685 Flange Gasket NOTE The ultraviolet radiation sensin...

Page 3: ...ls C7027A1056 C7035A1049 C7035A1064 Accessory 118367A Swivel Mount provides adjustable positioning of the C7027A or C7035A Fig 3 Installation dimensions of C7044A in in mm C7044A Minipeeper Ultraviolet Flame Detector Flame Detection Housing has two openings to permit either side or end viewing Side viewing is 1 8 as sensitive as end viewing Mounting Bracket included in 4074BVK Bag Assembly secured...

Page 4: ... hours of continuous use within the flame detector s specified ambient temperature and voltage ratings Wearout of an ultraviolet radiation sensing tube results in failure of the UV sensor to properly discriminate between flame conditions The C7027A C7035A and C7044A Flame Detectors should only be used on burners that cycle on off periodically or in the absence of cycling are periodically checked f...

Page 5: ...ng the axis of the pilot flame The smallest pilot flame that can be sighted must be capable of igniting the main burner see Pilot Turndown Test page 9 2 Main flame only Sighting must be at the most stable part of the flame for all firing rates 3 Pilot and main flame Sighting must be at the junction of both flames Other Radiation Sources Sensed By The UV Detector Examples of radiation sources other...

Page 6: ...prayed on the body of the detector use a C7035A Internal threads in its base permit the use of waterproof flexible conduit for this type of application Prepare Hole In Wall Of Combustion Chamber Cut a hole of the proper diameter for the sight pipe in the wall of the combustion chamber at the selected location Flare the hole to leave room for small adjustments of the sighting angle The taper of the...

Page 7: ...separately onto the sight pipe before mounting the detector Fig 6 Mounting a C7027A or C7927A on a combustion chamber viewed from above C7035A mounting is similar Fig 7 Mounting dimensions of 136733 Heat Block in in mm Mounting a C7044A On a Blast Tube Fig 9 The C7044 is designed to be mounted on the blast tube of a burner The exact location should be determined by the burner manufacturer Contact ...

Page 8: ...properly supervise the combustion flame 1 Disconnect power supply before beginning installation to prevent electrical shock and equipment damage All wiring must comply with applicable electrical codes ordinances and regulations Use NEC Class 1 wiring 2 If the leadwires are not long enough to reach the terminal strip or wiring subbase make the required splices in a junction box 3 If splicing is nec...

Page 9: ...al location or before tightening the C7044A clamp screw complete both the adjustments and checkout tests that follow and any required by the burner manufacturer Uv Sensor Tube Test NOTE For initial burner lightoff consult the burner manufacturer instructions or the instructions for the flame safeguard control During the initial burner lightoff make sure the flame safeguard control starts i e the l...

Page 10: ... or voltage reading is desirable The flame signal must be above the minimum acceptable level for the flame safeguard control and associated amplifier as indicated in Table 1 Measure the flame signal for the pilot alone the main burner flame alone and both together unless monitoring pilot only when using an intermittent pilot or supervising the main flame only when using direct spark ignition Also ...

Page 11: ... the leads on the Q624 or Q652 Response to Other Ultraviolet Sources Some sources of artificial light produce small amounts of ultraviolet radiation Under certain conditions an ultraviolet detector will respond to them as if it is sensing a flame Do not use an artificial light source to check the response of an ultraviolet detector To check for proper flame detector operation test for flame failur...

Page 12: ...ll of the combustion chamber and the detector c add a shield or screen to reflect radiated heat away from the detector or d add cooling refer to Sight Pipe Ventilation page 6 4 Remove the detector and clean the viewing window with a soft clean cloth 5 Clean the inside of the sight pipe if one is used before reinstalling the detector 6 If the flame signal continues to be too low replace the plug in...

Reviews: