R7426D UNIVERSAL INPUT CONTROLLER
3
EN1B-0204GE51 R0403
CONFIGURATION AND CONTROL PARAMETERS
Config. Par.
No. Name
Description
Default Setting Actual Value
C.01 DIR/REVY1
Selects the output action of Y1 to adapt the valve or damper direction
Dir
Dir
Rev
Direct acting output signal
Reverse acting output signal
C.05 CPATYP
Selects the
C
ontrol
P
oint /
S
et
P
oint
A
djustment type
0
Potentiometer
range
CPA/SPA
range
Sensor / Remote Setpoint Unit
Type Numbers
0
internal
CPA:
±
10%
internal
1
100k
Ω
...0
Ω
CPA:
±
10%
43193982-001
2
100k
Ω
...0
Ω
SPA: 0...100%
43193982-001
C.06 YRange
Selects the output control range
1
0
1
2 ... 10Vdc
0 ... 10Vdc
C.12 X2ext
Enable / Disables the X1 sensor input to be used for both X1 and X2 inputs
0
0
1
2
X2 installed
X1 signal used for X2
X2 disabled
C.13 LimTyp
Limitation type determines whether the limit function is low or high.
1
0
1
Low limit
High limit
C.14 Senstyp
Sensor type determines automatic detection or manual selection of
NTC sensor type
0
0
1
Auto detection T3
NTC sensor type T3
C.15 Y1CTRF
Control function
1
0
1
Direct control behaviour
Reverse control behaviour
C.22 Adr
1)
Sets the serial communication address, used for service or maintenance.
254
0
255
Min.
Max.
C.23 DefProg
Initiates the default programming.
0
0
1
No Defaultprogramming
Initiates Defaultprogramming
C.24
UStartPoint
Start point (0%) of X1 and X2 span adjustment
0
0
10V
Min.
Max. (resolution 0.1V)
C.25 UEndPoint
End point (100%) of X1 and X2 span adjustment
10
0
10V
Min.
Max. (resolution 0.1V)
C.26 OffDelay
Off delay for On/Off output
0
0
60min
Min.
Max. (resolution 1min)
1)
actual value will not be changed during reset to default parameter
For detailed information of configuration parameters see chapter
Configuration Settings
.
Table 3. Configuration Parameters R7426D