Honeywell MICRONIK 200 R7426A Installation & Start-Up Instructions Download Page 8

R7426A,B,C  TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK

 

EN1B-0203GE51 R0507C 

 

Summer / Winter Time Change  

AddHour / SubHour (C.16 / C.17) 

These configuration parameters are only available on 
controllers with RTC. The configuration parameter 

AddHour 

or 

SubHour

 are required to adjust the month for 

summer/winter time change or vice versa. 
The actual clock is incremented by one hour at 2:00 on the 
last sunday of the month for winter/summer time change 
(

AddHour

). The actual clock is decremented by one hour at 

2:00 on the last sunday of the month for summer/ winter time 
change (

SubHour

). 

 

Prestart Gradients PSTG_H / PSTG_C 

(C.18 / C.19) 

The configuration parameter 

PSTG_H 

or

 PSTG_C

 are 

necessary for the optimum start program on controllers with 
RTC. For heating and cooling applications, these parameters 
determine the prestart gradient to reach the comfort setpoint 
at occupancy start. 
If the comfort setpoint will be reached earlier or later than 
expected, the controller corrects the prestart gradient by self-
adaption routine to optimize the start cycle. 
The optimum start cycle for heating or cooling can be 
disabled by setting 

PSTG_H 

or

 PSTG_C 

to 0. 

 

Optimum Start Self Adaption Speed 

Adapt (C.21: Controller with RTC only) 

This parameter is used by the self-adaption routine to 
optimize the energy consumption during the start cycle. For 
this optimization, a corrected prestart gradient is calculated 
once per day. The adaption to the actual prestart gradient for 
the next optimum start cycle is determined by the self 
adaption speed 

Adapt 

(0% = adaption disabled and 100% = 

max. adaption speed). 
 

Damper Prestart Time tvd  

(C.20: Controller with RTC only) 

The damper prestart time 

tvd

 is active with the optimum start 

program only and is used to set the time before occupancy 
start (scheduled comfort mode) at which the output signal Y1 
(damper) switches to normal operation to supply fresh air to 
the space in mixed air applications. 

Serial Communication Address Adr (C.22) 

The configuration parameter 

Adr

 sets the serial 

communication address. 
The serial communication bus allows the connection of the 
PC-based Operator’s Terminal to one or several controllers. It 
provides access to all application configuration and control 
parameters, time schedules, input and output values of the 
connected controllers and easy setting of these via the bus by 
mouse click or keyboard. 

Default Programming DefProg (C.23) 

Setting the control parameter 

DefProg

 to 1 resets all control 

and configuration parameters to defaults (see Table 4 and 
Table 5). Default programming is indicated by a display of 

def

After default programming, the parameter 

DefProg

 is reset to 

0. 
 

PARAMETER SETTINGS AND 
ADJUSTMENT 

Main Setpoint W1 (P.01) 

The main setpoint is either set by the control parameter 

W1

 or 

by the external setpoint potentiometer if the configuration 
parameter 

CPATYP

 = 3, 5 or 6. 

 

High/Low Limit Setpoint W

lim

 (P.02) 

For high or low limit control, the control parameter 

W

lim

 is 

used as setpoint. 
During limit control, the throttling range 

Xp2

 and reset time 

tr2

 are active. 

Limit control will be active only if the T2 temperature signal 
(control parameter 

T2ext

 = 0) is available or alternatively the 

sensor T1 (control parameter 

T2ext

 = 1) is used also for limit 

control. 
For cascade control, the limit setpoint 

W

lim

 

determines the 

control point at which the submaster setpoint

 

(

W

cas

) maintains 

the limit value and is not shifted anymore by the master 
control loop. 
High or low limit control is in accordance with the con-
figuration parameter 

LimTyp

 (C.13). 

 

Submaster Setpoint W

cas

 

(P.06) 

The R7426A,B,C controllers provide cascade control which 
uses two control loops, master and submaster to maintain the 
master setpoint CTRP1. Cascade control will be active if 
temperature sensor T2 is connected and the control para-
meter 

W

cas

 is set to any value other than OFF. 

This adjustment sets the control point of the submaster 
control loop, discharge temperature (T2), at zero room 
temperature deviation. If the room temperature deviates, the 
submaster setpoint 

W

cas

 is automatically altered. 

Cascade control is disabled if the submaster setpoint 

W

cas

 is 

set to OFF. 
Low limit of CTRP2 is performed if control parameter 

LimTyp

 = 0 and high limit of CTRP2 is performed if control 

parameter 

LimTyp

 = 1. 

 

Reset Span Adjustment R

cas

 

(P.07) 

The reset span adjustment 

R

cas

 determines the reset effect in 

Kelvin. The submaster setpoint 

W

cas

 is altered if the tem-

perature (T1) deviates by 50% of the throttling range 

Xp1

 

Throttling Range Xp1 / Xp2 (P.08 / P09) 

Proportional band (throttling range X

p

) adjustment determines 

the temperature change, required at the main sensor (T1) and 

Summary of Contents for MICRONIK 200 R7426A

Page 1: ...installation information and mounting location Verify the controllers will be adequately separated from the main power supply relays or other equip ment which can possibly generate electromagnetic interference Verify that the ambient temperature and the humidity at the controllers will not exceed 0 50 C 32 122 F and 5 to 95 rh Use shielded wiring in areas with high EMI All wiring should be separat...

Page 2: ...by this controller W303 open T3 supplied from another controller 1 Default jumper position closed Cut open jumper W303 only if the T3 input is fed from another controller parallel connection max six devices This disconnects the T3 input from the internal power supply Wiring should be done only according to the actual job wiring diagrams or wiring diagrams shown in the mounting instruction sheet EN...

Page 3: ...CPA 5K internal 1 953 1053Ω CPA 5K T7412B1016 Pt 1000 2 100kΩ 0Ω CPA 5K T7412B1057 T7412C1030 Pt 1000 T7412B1008 T7412C1006 NTC 20kΩ 43193982 001 3 10 20kΩ SPA 15 30 C T7412B1024 BALCO 500 T7412B1040 Pt 1000 4 0 10kΩ CPA 5K HCW 23 setpt wheel printed with 5 K 5 0 100kΩ SPA 15 30 C 43193982 001 6 0 100kΩ SPA 0 50 C or 0 130 C 43193982 001 C 06 YRange Selects the output control range for all outputs...

Page 4: ... Adjusts the month for summer winter time change 10 x x x Min Max 0 disables summer winter time change 12 Oct C 18 PSTG_H 2 3 Determines the prestart gradient to reach the comfort setpoint for heating 0 K min x x x Min Max 0 disabled 2 C 19 PSTG_C 2 3 Determines the prestart gradient to reach the comfort setpoint for cooling 0 K min x x x Min Max 0 disabled 2 C 20 tvd2 Determines the damper presta...

Page 5: ... P 13 tr2 1 Reset time cascade control loop OFF 20 sec 20 min OFF 10 0 5 sec min x x x P 14 MINPOS Minimal pos for air damper actuators 0 50 20 1 x x P 15 Ystart Start point for mid range shift of output Y1 20 20 0 0 5 K x x x P 16 SOFFS Offset of main setpoint in Standby mode 0 10 2 0 1 K x x x P 17 T1Cal Calibration of temperature sensor T1 20 20 0 0 1 K x x x P 18 T2Cal Calibration of temperatu...

Page 6: ...guration parameter Ctrltyp value from Hi to Lo control range or vice versa causes the controller to change all parameter values to default depending on the selected Ctrltyp value For a direct parameter reset by the user refer to chapter How to reset Parameter Values to Default Values on page 12 Control Point Setpoint Adjustment CPATYP C 05 The control point or setpoint can be adjusted via the inte...

Page 7: ...T1 and T2 input internally and the sensor has to be connected only to the T1 input By using a limit temperate sensor T2 the parameter T2ext has to be set to 0 default Limit Type LimTyp C 13 The configuration parameter LimTyp allows the selection of high or low limit control High limit control is performed if configuration parameter LimTyp 1 low limit control is performed if configuration parameter...

Page 8: ...tion and control parameters time schedules input and output values of the connected controllers and easy setting of these via the bus by mouse click or keyboard Default Programming DefProg C 23 Setting the control parameter DefProg to 1 resets all control and configuration parameters to defaults see Table 4 and Table 5 Default programming is indicated by a display of def After default programming ...

Page 9: ...oling valve Setting Guidelines for Proportional Band of P and P I Control To estimate the proportional band throttling range Xp for stable control under all different load conditions the control or correcting range Xh of the heating or cooling coil must be known This is the maximum air temperature increase pro duced by the heating coil or decrease of a cooling coil if the control valve is fully op...

Page 10: ...Summer Winter Compensation Authority Su Wi P 04 P 05 These authority settings determine the reset effect OATComp the compensation sensor T3 has on the main setpoint W1 in percentages Outside temperature reset in summer and winter time are commonly used applications To calculate winter and summer authority the throttling range must be considered in proportional only control according to Table 12 Ta...

Page 11: ...controllers only and determines the minimum open position to which an outdoor air damper actuator can be driven from the controller In mixed air damper applications it maintains the minimum outdoor air damper setting even though the temperature input condition calls for a fully closed position If the controller is in OFF mode the time schedule program overrides the minimum position by the ON OFF i...

Page 12: ... controller returns to selection mode by pushing the SET or SEL button Pushing the SEL button leads back to standard display mode Pushing the SET and SEL button simultaneously for approx 1 sec causes the controller to leave the standard display mode and to enter the output data selection mode Fig 11 Pushing the SET button causes the controller to accept the selected output data no and to enter the...

Page 13: ...TIME CLOCK ONLY R7426B C ONLY R7426B C ONLY DATE COMPENSATION TEMPERATURE T3 SUBMASTER LIMIT SETPOINT CTRP2 MAIN TEMPERATURE T1 HUMIDITY DEVIATION XWrh MAIN SETPOINT CTRP1 OUTPUT Y1 OUTPUT Y2 OUTPUT Y3 LIMITATION CASCADE TEMPERATURE T2 A A B A B OUTPUT TYPE FLOATING 0 10VDC 2 10VDC 0 100 0 100 0 120 0 12V DIR 20 100 12 0V REV 25 125 0 12V 0 100 0 100 CONTROL RANGE OUTPUT RANGE THE OUTPUT DATAS Y1 ...

Page 14: ...f the selected parameter Ranges are shown in Table 4 and Table 5 An adjustment example is shown in Fig 18 Pushing the SEL button retains the old parameter value Pushing the SET button accepts the parameter value and returns to parameter configuration selection mode Resetting Param Values to Default Values Pushing simultaneously the and button during the power up or setting the control parameter De...

Page 15: ...e SEL button leads back to standard display mode R7426B AND R7426C ONLY WITHOUT CONTROL LOOP IS ACTIVE WITH MANUAL OVERRIDE IS ACTIVE Fig 11 Output Selection Mode AND TO ADJUST OUTPUT VALUE OUTPUT VALUE ADJUSTMENT OUTPUT VALUE ADJUSTMENT AUTOMATIC DISPLAY FOR APPROX 1 SEC OUTPUT SELECTION OUTPUT SELECTION OUTPUT SELECTION RELEASE OF MANUAL OVERRIDE NO MANUAL OVERRIDE MANUAL OVERRIDE OR Fig 12 Outp...

Page 16: ...ts of the used holiday types H1 H2 or H3 must be programmed in the standard schedule Table 15 shows a programmed example of the holiday schedule 2 7 till 28 7 holiday type H1 and 1 5 holiday type H3 The H1 and H2 holidays will not be influenced if the user changes the actual date If power supply is interrupted for more than one day all H1 and H2 holidays within the date of power supply error and t...

Page 17: ...like a controller without real time clock If the occupancy input is inactive the controller will be assumed as occupied Date Date Date TO ADJUST YEAR OR TO ADJUST MONTH OR TO ADJUST DAY OR TO ADJUST MINUTES OR TO ADJUST HOURS OR TIME ADJUSTMENT DATE ADJUSTMENT Fig 14 Date and time adjustment mode Programming Standard Schedule with RTC only The standard schedule programming is used to program up to...

Page 18: ...e Th Sa Fig 16 Holiday schedule programming Interpreting Error Messages Different analog input errors can be identified by the controller Error handling The defective analog input T1 T2 T3 or Xwrh will be displayed in the standard display mode see Fig 17 after the corresponding value is selected NOTE For the external CPA SPA potentiometer input no error message is indicated if the potentiometer or...

Page 19: ...y Jan Feb March April May June July August Sept Oct Nov Dec 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 1 30 31 1 If the 29th of February is programmed to be a H1 or H2 holiday and the current year is not a leap year this holiday will be deleted on March 1 Table 16 Annual schedule ...

Page 20: ...l GmbH Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to EN1B 0203GE51 R0507C point 1 point 2 point 3 point 4 point 5 point 6 day 1 time SMode 2 time SMode 2 time SMode 2 time SMode 2 time SMode 2 time SMode 2 Mo Tu We Th Fr Sa Su H1 H2 H3 1 Weekday or ho...

Reviews: